The conceptual design and analysts of three phase superconducting fault current limiter

일체형 삼상 고온 초전도 한류기의 단락 특성 해석

  • Published : 1998.07.20

Abstract

The conceptual design of integrated three phase superconducting fault current limiter (SFCL) is presented. And through simulation of power system where this SFCL is installed, the characteristics of this SFCL is analyzed. It is like three-phase transformer. So it has the same characteristics with inductive single phase SFCL. But it has more merits than single phase SFCL. Differently to single phase SFCL, integrated three phase SFCL induces impedance at all phase by any single phase fault to protect the power system more safely.

Keywords