Lift-Off Voltage and Partial Discharge Characteristics of Free Conducting Particles in GIS

GIS 내 금속입자의 부상전압과 부분방전특성 연구

  • Published : 1998.07.20

Abstract

Gas Insulated Switchgear(GIS) acts as an indispensible part in power transmission network. In order that GIS may have its high reliability, it is necessary to pay careful attention to its whole process e.g., designing, manufacturing, installation, and operation. The main hazard in GIS comes from free conducting particles, which can move and cause breakdown under the influence of the electric field. Although the concentration on protecting the GIS inner part against the free conducting particles is made, it is, actually, almost impossible to avoid the hazard from the particles throughly. In this paper, using the EHV test chamber, partial discharge quantity in GIS was measured when free conducting particles initiate to discharge for providing fundamental data for the purpose of developing predictive diagnosis technology on site GIS.

Keywords