침전극 곡률 반경에 따른 절연유의 절연파괴 특성

Breakdown Characteristic of Transformer Oil Depending on Tip Radius

  • 발행 : 1997.07.21

초록

We investigated the breakdown characteristic of mineral oil according to applied voltage and tip radius. In this experiment, electrode system was point-plane geometry. The tip radius of needle was 5, 10, 20 and $25{\mu}m$, respectively. Applied voltage was AC and DC. We measured breakdown voltage for each tip radius with increasing electrode gap, 2mm to 10mm. Under nonuniform electric field, breakdown strength was higher when needle was negative than when needle was positive. Because it is polarity effects due to space charge. And the more sharp tip radius, whether we applied AC or DC, the higher breakdown strength. As tip radius increase, breakdown strength decreases exponentially.

키워드