Measurement and Analysis of Electric and Magnetic Fields near a Transmission Tower

송전철탑 주변에서 전장과 자장의 측정과 분석

  • Published : 1997.07.21

Abstract

In this paper, measurement and analysis of ELF electric and magnetic fields due to a transmission line have been carried out and the power frequency field strength measuring system is designed. In order to evaluate electric and magnetic fields associated with 60 Hz electric power transmission and distribution lines, the actual survey near a transmission tower has been made and analyzed. It may be inferred from these results that the maximum electric and magnetic fields strength in the vicinity of a line tower do not exceed 3.5[kV/m] and 20[${\mu}T$]. The results of the field measurements agree with limits and guidelines recommended by various authorized international institutes.

Keywords