A Study on the Laser Aided Measurement of Salt Contamination of Porcelain Insulators

레이저를 이용한 활선 염해 측정

  • Published : 1997.07.21

Abstract

The salt contamination on the surface of the porcelain insulators used electric power systems causes flash-over accidents. Therefore the quantity of salt contamination should be monitored not to exceed a limit. In this study, we tried laser aided measurement of salt contamination. The Nd:YAG laser beam was focused on the surface of the porcelain insulators which were artificially contaminated, and we detected the D-Line (${\cong}589nm$) of spontaneous emission from the excited sodium atoms with a PMT and an oscilloscope. And we deduced the relation between the detected signals and degree of salt contamination.

Keywords