A Study on Position and Induced Voltage of ADSS Using CSM

CSM을 이용한 ADSS유도전압 해석 및 위치선정에 관한 연구

  • Published : 1997.07.21

Abstract

Tracking currents related to field exposure for ADSS in T/L is of importance. At phase-ta-phase voltage in excess of 100 kV self-supporting aerial cables with solid insulation tend to suffer damage in regions close to the tower. The damage can be put down to surface tracking currents resulting from different degrees of surface contamination and moisture. Main characteristic of this exposure is the induced voltage analysis and position of ADSS. For complicated calculation of induced voltage on ADSS, this paper described an effective numerical calculation method based on CSM. The proposed methods are applied to 275 kV T/L of Malaysia.

Keywords