Development of PLC by using micro controller for the distributed fire alarm system

마이크로 콘트롤러를 이용한 분산형 방재 시스템용 중계기 개발

  • Published : 1996.07.22

Abstract

In this paper, a small PLC system is designed and developed for the distributed building control and fire control system. It uses 8031, a 8-bit micro controller from Intel Inc. The size of the PLC is $7cm{\times}8cm$ and the PLC can accept 4 sensor inputs and drive 4 relay outputs, which operates at 24V. Multiple access of PLC by one host computer is implemented by assigning a unique 10 to each PLC, which ranges from 0 to 126. The operation starts by sending a command packet from host computer to a PLC and the PLC of the same 10 fetches the command packet by comparing the first byte of the command packet with its own 10. The PLC is programmed to perform a various functions and the function is selected by the content of the command byte, which is the second byte of the command packet. The third byte, which is the last byte, is a checksum byte. The checksum byte is the sum of the first byte and the second byte and is used to detect the communication error. Depending on the content of the command byte, PLC performs the desired function and returns the response packet back to the host computer. The response packet is also a three-byte packet, 10 byte, response byte and checksum byte. For the independent operation of PLC without being controlled by the host computer, variable length RULE data packet is sent to PLC. In case the communication line is broken, the PLC perform the independent operation by referencing the RULE data. The applicable areas are; building automation system, distributed factory automation, measurement of temperature of toxic or dangerous area.