A Modified Selective Ground Relay for Ungrounded Distribution Systems

  • Nam Soon-Ryul;Kang Sang-Hee;Park Jong-Keun
    • Journal of Electrical Engineering and Technology
    • /
    • v.1 no.1
    • /
    • pp.16-22
    • /
    • 2006
  • Selective ground relays (SGRs) are useful fur distinguishing a faulted feeder from the sound feeders in ungrounded systems. However, they sometimes mis-operate due to human or device errors. Particularly, the reversed polarity of zero-sequence current transducers (ZCTs) is the most frequent cause of mis-operation. This paper presents a modified SGR for reducing the probability of mis-operations caused by the reversed polarity of ZCTs. The modification is achieved by introducing an adaptive time delay, which depends on the magnitude of the zero-sequence current and the phase angle deviation from the reference. The modified SGR was successfully demonstrated on a sample ungrounded system without mis-operation.

Development of residual current detector for DC distribution system (직류배전용 누설전류 검출기 개발)

  • Lee, Won-Ki;Han, Byunghun;Jung, Hae-Min;Kim, Hyosung
    • Proceedings of the KIPE Conference
    • /
    • 2013.07a
    • /
    • pp.53-54
    • /
    • 2013
  • 디지털 제품의 사용 증가로 직류를 사용하는 부하가 급증하고, 태양광발전 등 직류발전의 보급이 확대 되며 직류배전에 대한 관심이 높아지고 있다. 기존 영상변류기(ZCT; Zero phase sequence Current Transformer)를 사용하여 누설전류를 감지하는 교류배전용 차단기는 영상변류기의 특성상 직류에서 적용이 불가능하다. 이에 따라 직류배전에서 누설전류에 의한 사고를 방지하기 위해서 누설전류를 검출하고 차단할 수 있는 장치 개발이 필요하다. 본 논문에서는 직류에서 검출에 문제가 없는 Fluxgate current transducer를 이용하여 직류배전에서 사용 가능한 검출기를 개발하였다.