• Title/Summary/Keyword: water-mist system

Search Result 89, Processing Time 0.027 seconds

Performance of Fire Extinguishing of Water Mist Nozzle for Power Transformer Fire Scenario (주 변압기실 화재시나리오에 적용한 미세물분무 노즐의 소화성능)

  • Lee, Kyoung-Duck
    • Journal of the Korean Society of Safety
    • /
    • v.21 no.6 s.78
    • /
    • pp.46-54
    • /
    • 2006
  • Fire extinguishing experiment was conducted with water mist nozzle in case of the pool fire, cascade fire and spray fire on flammable liquid of class B whether water mist system can be effective system for power transformer fire scenario. In the event of a pool fire, flow rate and time to extinguish was inclined to be increased according to the obstruction rate of ignition space. Furthermore, the performance of fire extinguishing depended upon the spraying angle of the nozzles. In case of cascade fire, the effect of extinguishment was began to show from a combustion pan filled with fuel and fuel flowing plate later on.

Effectiveness of Friction Loss Calculation Used for Water Mist Fire Extinguishing System on Marine Vessels

  • Lee Kyung-Woo;Kim You-Taek;Lee Young-Ho;Kim Mann-Eung
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.29 no.1
    • /
    • pp.86-97
    • /
    • 2005
  • Nowadays, Water Mist Fire Extinguishing System is increasingly used in maritime field for various application. The fire extinguishing capability of the system should be verified by hydraulic calculation in the same manner as the conventional water based fire extinguishing system such as sprinkler system. water spray system and etc. Additionally, the review of effectiveness of friction loss calculation method used for hydraulic calculation is needed because the pipe flow characteristic of its piping system has higher Reynolds number than that of the conventional system. In this paper the review work was carried out based on the NFPA Code 750.

Optimum Fire Extinguishing Modeling using Impact Factor Analysis on Water Mist System of Pool Fire (영향인자 분석을 통한 고임화재의 미분무수 최적소화 모델링)

  • Hwang, Won-Jun;Kim, Hwang-Jin;Lee, Sung-Eun;Kim, Sung-Won;Oh, Kyu-Hyung
    • Fire Science and Engineering
    • /
    • v.23 no.5
    • /
    • pp.84-89
    • /
    • 2009
  • In this study, the fire extinguishing experiment was performed using a water mist nozzle with variation of factors which affect on the extinguishing time. The variables were distance from nozzle center to fire location, droplet size, height of nozzle and opening or not. With the experimental data, interaction and sensitivity between factors were analysed with Mini tab and deduce a optimum model of fire extinguishing of water mist system. Based on the experiment and modeling of fire extinguishing with water mist system, the most important factor on extinguishing time is the distance from the center of nozzle to fire and the opening effect was small compare with other factors.

Analysis of Fire Suppression Efficiency for Intermittent Water Spray Pattern by Fire Dynamics Simulator (FDS를 이용한 교번식 미분무방식의 소화 성능 분석)

  • Jee, Moon-Hak;Lee, Byung-Kon
    • Fire Science and Engineering
    • /
    • v.22 no.3
    • /
    • pp.216-220
    • /
    • 2008
  • Water mist fire suppression system utilizes the fire suppression features such as cooling of fire source, dilution of ambient oxygen, and shielding of radiation heat with the evaporation of microscopic water droplets. The momentum of water mist is relatively lower than that of larger water droplet and the infiltration of water mist to the fire source is not effective. Contribution of evaporated water vapor is liable to decline to limited portion of fire source due to its light weight and sparse density. On the other hand, the cycling water mist pattern is expected to improve the penetration force of water mist as well as the air expelling capability with the stratified spray characteristics. At this paper, we present the analyzed fire suppression capability of intermittent water spray pattern by use of FDS which is computational fire dynamics fire model. We expect this analysis can support the basic concept to the development of the prototype of water mist nozzle.

A Sturdy on Water Mist Fire Extinguishment System for the Transformer Room (전력공급용 주변압기실 Water Mist 소화설비 적용에 관한 연구)

  • Noh, Soon-Cheol;Baek, Doo-Hyun;Choi, Young-Hwan;Ji, Sung-Gu
    • Proceedings of the KIEE Conference
    • /
    • 2004.11b
    • /
    • pp.39-42
    • /
    • 2004
  • 주변압기실에 Water Mist 소화설비의 적용을 위하여 과거 화재사례 분석, 변압기의 형태, 변압기실의 구조 등을 검토하여 3가지 화재유형을 상정하였고, 발생 가능한 화재규모 및 종류를 검토하여 소화성능 평가를 위한 6가지 화재 시나리오를 제시하고 이를 검증하기 위한 모의실험을 수행하였다. 본 연구를 통하여 주변압기실에 적용 가능한 최적의 Water Mist 소화설비의 시험기준을 정립하였으며, 향후 본 시험기준에 의한 전력공급용 주변압기실 Water Mist 소화설비가 화재에 의한 대형 재난을 예방함과 동시에 안정적인 전력공급에 이바지할 것으로 기대된다.

  • PDF

He Study of Fire Suppression Capability of Low Pressure Water-Mist System for Wooden Cultural Properties (목조한옥에 대한 저압식 미분무 소화설비의 소화성능에 관한 연구)

  • Roh, Sam-Kew;Kim, Dong-Cheol;Ham Eun-Gu
    • Journal of the Society of Disaster Information
    • /
    • v.8 no.4
    • /
    • pp.401-410
    • /
    • 2012
  • The study verified the extinguishing performance of the low pressure water-mist system, which is used to extinguish fire at domestic wooden architecture, through a fire test. Made of inflammable materials, a wooden house is vulnerable to fire, and the size of fire may vary from the early stage in case of arson. With the discharging pressure of 8 bar and the flow rate of 35 lpm, the low pressure water-mist nozzle used in the experiment has considerable discharging amount compared to other water-mist nozzles. The extinguishing performance was tested based on the size of fire and architecture. Test results demonstrated that the extinguishing performance was not affected by the size of a house, but decreased significantly when the size of fire was above unit 1. Taking into account that the environment of actual wooden cultural properties is more vulnerable than that of the experiment model, sufficient investigation on extinguishing performance is required to apply the water-mist extinguishing system to wooden architecture.

A Study on the performance test of Water mist system as a fire extinguish system for Ships (선박용 미분무수 소화설비의 성능평가연구)

  • Kim, Sung-Yoon;Ahn, Bung-Ho;Kim, Dong-Seuk;Kim, You-Taek
    • Proceedings of the Korean Society of Marine Engineers Conference
    • /
    • 2006.06a
    • /
    • pp.155-156
    • /
    • 2006
  • Developed and conducted a performance test of the Water mist system that is satisfied with the requirement of a fire test requiring Class 3 Engine Mock-up exceeding net volume $3,000m^3$ as per IMO's MSC/Circ. 668 Appendix B(Test method for fire testing equivalent water-based fire-extinguishing systems for machinery spaces of category A and cargo pump rooms).Even though fuel atomizing was continued for 15 sec. after stopping of the system according to the test method relating to the atomizing fire type, no fire was reignited. This result shows the excellence of the system. There was no damage to the contents of the system after the test.

  • PDF

An Experimental Study on the Improvement of Fire Extinguishing Performance of Water Mist with Foam (포 소화약제를 혼합한 미분무수 소화시스템의 소화성능 향상 방안에 관한 실험적 연구)

  • Hwang, Won-Jun;Kim, Hwang-Jin;Oh, Kyu-Hyung;Lee, Sung-Eun;Kim, Sung-Won
    • Fire Science and Engineering
    • /
    • v.23 no.3
    • /
    • pp.61-66
    • /
    • 2009
  • We carried out the water mist fire extinguishing experiments with the 3 kinds of foaming agents varied on the nozzle height. Test result showed that 2% AFFF (Aqueous Film Forming Foam) and 1% synthetic foaming agent for water mist system are the faster extinguishing time than the pure water mist and 3% AFFF solution. Additionally, the best fire extinguishing performance of pure water mist was shown at 3.5m nozzle height and that of the foaming agents shown at 4m nozzle height.

A Study on Fire Extinguishing Performance of Closed Type Water Mist Nozzles for Ship's Accommodation (선박 거주구역의 방호를 위한 폐쇄형 미분무 노즐의 화재진압성능평가 연구)

  • Kwark, Ji-Hyun;Kim, Young-Han
    • Fire Science and Engineering
    • /
    • v.26 no.1
    • /
    • pp.1-9
    • /
    • 2012
  • Since accommodation, public space and service areas where people stay for all day occupy about 70% of a huge cruise ship, they have to be protected from the fire. International Maritime Organization has resolved that a water mist system should be equipped in this cruise ship according to SOLAS II-2 Reg. 10.6 and FSS code Ch. 7. The water mist system consists of mist nozzles, pressure vessels, section valves and pump unit etc. In particular, the water mist nozzles should be recognized by fire tests in accordance with IMO Res. MSC 265(84). In this study, the fire tests for cabin, corridor, public space and storage area have been conducted to develop the water mist nozzles appropriate to the regulation. Totally 5 types of nozzles were developed and have satisfied the whole performance requirements.