• Title/Summary/Keyword: three phase transformer

Search Result 224, Processing Time 0.023 seconds

Test Results of a Three Phase 10㎸A HTS Transformer With Double Pan Cake Coils (3상 10kVA 더블 팬케익 코일형 고온초전도 변압기 특성시험 결과)

  • 이승욱;이희준;차귀수;이지광;최경달;류경우;한송엽
    • The Transactions of the Korean Institute of Electrical Engineers B
    • /
    • v.52 no.3
    • /
    • pp.101-106
    • /
    • 2003
  • The high temperature superconductor transformers gain interests from the industries. This paper described construction and test results of 10㎸A HTS transformer Three phase transformer with double pancake windings were constructed. To reduce the leakage magnetic field, secondary coil were placed between the two primary coils. BSCCO-2223 wire. silicon sheet steel core and FRP cryostats were used to construct the transformer. Three coils were stacked in one cryostat. Two double pancake coils were connected in series for the primary coil and one double pancake coil was used for the secondary coil. Total number of turns of the primary winding and the secondary winding were 112turns and 98urns, respectively, The rated voltages of each winding were 440/220V. The rated currents of each winding were 13.1/26.2A. After the tests of basic properties of the three phase HTS transformer using no-load test, short-circuit test and full-load test, continuous operation of 100 hours with pure resistive load has been carried out. Test results proved over-load capability and reliability of the HTS transformer.

Characteristic Analysis of a Three Phase HTS Transformer (3상 고온초전도 변압기의 특성해석)

  • Lee, S.W.;Lee, H.J.;Cha, G.S.;Lee, J.K.;Choi, K.D.;Ryu, K.W.;Hahn, S.Y.
    • Proceedings of the KIEE Conference
    • /
    • 2001.07b
    • /
    • pp.720-722
    • /
    • 2001
  • The high temperature superconductor transformer gains interests from the industries. This paper examined characteristics of the laboratory scale three phase HTS transformer and Brandt equation is used to calculate the loss by perpendicular magnetic field in transformer winding. To estimate the performance of the three phase HTS transformer no load characteristics, short circuit characteristics are calculated by using finite element method. Transient characteristics of sudden short circuit during full load operation have been examined. Effect of the resistance growth in the HTS wire from the quench of the wire is included in the calculation.

  • PDF

Study on Steady State Analysis of High Power Three-Phase Transformer using Time-Stepping Finite Element Method (시간차분 유한요소법을 이용한 대용량 삼상 변압기의 정상상태 해석에 관한 연구)

  • Yoon, Hee-Sung;Seo, Min-Kyu;Koh, Chang-Seop
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.61 no.8
    • /
    • pp.1123-1129
    • /
    • 2012
  • This paper presents the fast steady state analysis using time-stepping finite element method for a high power three-phase transformer. The high power transformer spends huge computational cost of the time-stepping finite element method. It is because that the high power transformer requires a lot of time to reach steady state by its large inductance component. In order to reduce computational cost, in this paper, the adaptive time-step control algorithm combined with the embedded 2nd 4th singly diagonally implicit Runge-Kutta method and the analysis strategy using variation of the winding resistance are studied, and their numerical results are compared with those from the typical time-stepping finite element method.

Simulation of Three Phase Supercoducting Transformer using PSCAD/EMTDC (PSCAD/EMTDC를 이용한 3상 초전도 변압기 시뮬레이션)

  • Lim, Chae-Hyung;Park, Min-Won;Yu, In-Keun
    • Proceedings of the KIEE Conference
    • /
    • 2003.07b
    • /
    • pp.958-960
    • /
    • 2003
  • Although the researches and developments are performed for superconducting technologies, many problems such as AC loss and quench phenomenon still remain to design the superconducting transformer. In addition, pre-study on the three phase high temperature superconducting (HTS) transformer is a sort of time and expense consuming work, thus it is very worthy of being analyzing the characteristics of HTS transformer in advance through proper simulation programs and skills. This paper presents an effective simulation method for the three phase HTS transformer using components developed in the PSCAD/EMTDC.

  • PDF

Analysis of Reduction Effect of Three Harmonic Currents by Zigzag Wiring of Single Phase Transformer (단상 변압기 지그재그 결선에 의한 3고조파 전류 저감 효과 분석)

  • Kim, Jong-Gyeum;Kim, Ji-Myeong
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.66 no.3
    • /
    • pp.99-104
    • /
    • 2017
  • The three-phase four-wire power distribution system can be used to supply power to single-phase and three-phase loads at the same time. There are linear loads and nonlinear loads as single-phase loads connected to each phase. The nonlinear load generates a harmonic current during the power energy conversion process. In particular, the single-phase nonlinear load has a higher proportion of generation of the third harmonic current than the harmonics of the other orders. In a three-phase four-wire system, the third harmonic current flows through the neutral wire to the power supply side, affecting the power supply side and the line. Furthermore, the magnitude of the current flowing in the neutral line can be higher than the current flowing in the individual phase. If the neutral current is higher than the phase current, the breaker may be blocked. Therefore, it is necessary to reduce the amount of current flowing in the neutral line by harmonics. There is a method of zigzag connecting a single phase transformer by a method of reducing 3 harmonic current. In this study, the method of reducing the magnitude of the three harmonic currents flowing through the zigzag wire by comparing the polarity and the negative polarity characteristics of the single phase transformer was compared through measurement and simulation.

Three-Winning Transformer Protection Based on Flux Linkage Ratio (쇄교자속비를 이용한 3권선 변압기 보호)

  • 강용철;이병은;김은숙;원성호
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.53 no.7
    • /
    • pp.375-381
    • /
    • 2004
  • This paper describes a three-winding transformer protective relaying algorithm based on the ratio of increments of flux linkages (RIFL). To minimize the approximation errors, the algorithm uses integration approximation. The RIFL of the two windings is equal to the turns ratio for all operating conditions except for an internal fault. For a single-phase and three-phase transformer containing the wye-connected windings, the increments of flux linkages (IFL) are calculated. For a three-phase transformer containing the delta-connected windings, the difference of IFL between the two phases are calculated to use the line currents, because the winding currents are practically unavailable. Their ratios are compared with the turns ratio. The comparative study between the proposed and differential approximation methods was conducted. The test results show that the algorithm can reduce the errors resulting from the conventional methods.

Research on a New 12-Pulse Step-Up and Step-Down Aviation Auto-Transformer Rectifier

  • Jiang, Fan;Ge, Hong-juan;Dong, Xiao-xu;Zhang, Lu
    • Journal of Power Electronics
    • /
    • v.18 no.1
    • /
    • pp.266-276
    • /
    • 2018
  • This paper presents a new step-up and step-down multi-pulse auto-transformer rectifier unit (ATRU) topology. This structure can achieve a wide range of output voltages, which solves the problem of auto-transformer output voltage being difficult to regulate. Adding middle taps to the primary winding and reasonably setting the number of auto-transformer windings, constituted two groups of three-phase output voltages with a $30^{\circ}$ phase difference. Multi-pulse output DC voltage is obtained after a three-phase output voltage across two rectifier bridges and inter-phase reactor. Thus, the output DC voltage is related to the number and configuration of the auto-transformer winding. In this paper, the relationship between the voltage ratio of the auto-transformer and the ratio of winding, input current and auto-transformer kilovoltampere rating are deduced and validated by simulations. On this basis, the output voltage range is optimized. An experiment on two different voltage ratio principle prototypes was carried out to verify the correctness of the analysis design.

Series Compensated Step-down AC Voltage Regulator using AC Chopper with Transformer

  • Ryoo, H.J.;Kim, J.S.;Rim, G.H.
    • KIEE International Transaction on Electrical Machinery and Energy Conversion Systems
    • /
    • v.5B no.3
    • /
    • pp.277-282
    • /
    • 2005
  • This paper describes a step-down AC voltage regulator using an AC chopper and auxiliary transformer, which is a series connected to the main input. The detail design of the AC regulator, logic and PWM pattern of the AC chopper is described and the three-phase AC regulator using two single­phase AC choppers with a three transformer configuration is proposed for three-phase application. The proposed three-phase system has the advantages of lower system cost due to reduced switch number and gate driver circuit as well as advantages of decreased size and weight because it uses a series compensated scheme. The proposed AC regulator has many benefits such as fast voltage control, high efficiency and simple control logic. Experimental results indicate that it can be used as a step-down AC voltage regulator for power saving purposes very efficiently.

Power Loss Analysis of Transformer Caused By Current Harmonics (전류 고조파에 기인하는 변압기 손실 해석)

  • Jang, Seungyong;Han, Sanghoon;Choi, Jaeho
    • The Transactions of the Korean Institute of Power Electronics
    • /
    • v.21 no.1
    • /
    • pp.34-41
    • /
    • 2016
  • This study investigates transformer losses caused by current harmonics. Electrical transformers are designed to work under sinusoidal voltage and current waves at a rated frequency. Recently, various nonlinear loads, such as power electronic converters, are connected to a power system; these converters generate current harmonics. Current harmonics increase power loss in transformers, which results in several problems, including temperature increase of the transformer and insulation damage. These problems will eventually shorten the operational life of the transformer. In this study, different types of losses caused by current harmonics in three-phase transformers are studied under linear and nonlinear load conditions. Linear loads are simulated and experimented on using pure resistance load, whereas nonlinear loads are simulated and experimented on using a three-phase twelve-pulse thyristor full-bridge rectifier. The different types of losses in three-phase transformers are evaluated analytically through the experimental result and simulation in PSiM.

A Three-Winding Transformer Protective Relaying Algorithm Based on Flux Linkages Ratio (쇄교자속비를 이용한 3권선 변압기 보호 알고리즘)

  • Kang, Y.C.;Lee, B.E.;Jin, E.S.;Won, S.H.;Lim, U.J.
    • Proceedings of the KIEE Conference
    • /
    • 2003.11a
    • /
    • pp.341-344
    • /
    • 2003
  • This paper proposes a tree-winding transformer protective relaying algorithm based on the ratio of increment of flux linkages (RIFL). The RIFL of the two windings is equal to the turns ratio for all operating conditions except an internal faults. For a single-phase transformer and three-phase transformer containing the wye-connected windings, the increments of flux linkages are calculated. for a three-phase transformer containing the delta-connected windings, the difference of the increments of flux linkages between the two phases are calculated using the line currents, because the winding currents are practically unavailable. Their ratios are compared with the turns ratio. The results of various tests show that the algorithm successfully discriminates internal faults from normal operation conditions such as magnetic inrush, overexcitation and external faults. The algorithm can not only detect internal winding faults, but reduce the operating time of a relay.

  • PDF