• 제목/요약/키워드: superconducting transformer

검색결과 172건 처리시간 0.025초

초전도 한류기 투입저항 변화에 따른 여자돌입전류 저감률 분석 (Analysis of Inrush Current Reduction Rate According to Insertion Resistance of the Superconducting Fault Current Limiter)

  • 박세호;서훈철;이상봉;김철환;김재철;현옥배
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2008년도 제39회 하계학술대회
    • /
    • pp.257-258
    • /
    • 2008
  • The inrush current of a transformer is a high-magnitude and harmonic-rich current generated when the transformer core is driven into saturation during energizing. The inrush current usually leads to undesirable effects, for example potential damage to the transformer, misoperation of a protective relay, and power quality deterioration in the distribution power system. Inrush current reduction is therefore important for power system operation. In this paper, to reduce the inrush current, the insertion resistance of the Superconducting Fault Current Limiter (SFCL) that is connected in series with the transformer in the distribution system is used. This paper implements the SFCL by using the Electromagnetic Transient Program-Restructured Version (EMTP-RV) to model the SFCL in the distribution system. The simulation results show the beneficial effects of the SFCL for reduction of the inrush current.

  • PDF

초전도변압기 시장진입가격 예측을 통한 경제성 분석 (Economic Evaluation of HTS Transformer by Predicting Market Penetration Price)

  • 김종율;이승렬;윤재영
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제53권9호
    • /
    • pp.507-512
    • /
    • 2004
  • HTS (High Temperature Superconducting) Transformer has the several useful characteristics in the viewpoints of technical and economical. Especially, an HTS transformer replaces the copper wire coils in a conventional transformer with lower loss HTS wire. In addition, inexpensive, environmentally benign liquid nitrogen replaces the conventional oil as the electrical insulation (dielectric) and provides the necessary cooling for the HTS transformer Therefore, the Life-cycle cost of an HTS transformer is much more attractive than conventional because it is more energy efficient, lighter in weight, smaller in size, and environmentally compliant. HTS transformer can be the best way to replace with conventional transformer in the future. In these days, companies world-wide have conducted researches on HTS transformer. A development project for a 154kV HTS transformer is proceeding at a research center and university in Korea. In this paper, we investigate the expected price of HTS transformer to have a merit in viewpoint of economic aspect. First, life-cycle cost of conventional transformer is calculated and based on this, the expected price of HTS transformer is evaluated. which HTS transformer is competitive against conventional transformer.

초전도기기 전류레벨협조와 절연협조를 고려한 초전도전력시스템구성을 위한 기초연구 (A Configuration of Superconducting Power System Considering the Current Level & Electric Insulation Coordination of Superconducting Apparatus)

  • 홍원표
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1999년도 하계학술대회 논문집 C
    • /
    • pp.1208-1210
    • /
    • 1999
  • Design & operation power systems for meeting increase of electric power demand is becoming more difficult and complex. Some of limitations of conventional technology can be broken through by the application of superconductivity technology. This paper presents a new concept & image for the configuration of superconducting power system which has introduced superconducting(SC) generator, cable, transformer, fault current limiter(SFCL), SMES, etc. Engineering evaluation of each power apparatus and its assessment of application to power system were conducted. Futhermore, it is pointed that superconducting power system require a new operating condition. This is, SFCL should play a important part of quenching current level coordination to prevent the other superconducting devices from quenching. Its designing & operating condition including SFCL was discussed in viewpoint of quenching current level and insulation coordination of SC coil.

  • PDF

A Study on Joint Resistance between Nb-Ti Superconducting Wires for MRI Magnet

  • Oh, Sang-Soo;Yingming Dai;Ha, Dong-Woo;Jang, Hyun-Man;Ryu, Kang-Sik
    • Journal of Electrical Engineering and information Science
    • /
    • 제2권6호
    • /
    • pp.90-94
    • /
    • 1997
  • The joints between the superconducting wires are inevitably needed from the requirement of a high magnetic stability with respect to time in the superconducting MRI magnet. In this study, a new superconducting joint using Cu/Nb-Ti sleeve has been tried on the MRI type Nb-Ti superconducting wires. The transformer induction type apparatus was made and applied to measure the joint resistance. A very low joint resistance of 10\ulcorner $\Omega$ could be successfully obtained from this joint method. It was confirmed that the initial rapid current decay occurs before the very stable current decay due to only superconducting joint. Some unstable part in the joint like exposed filaments causes the initial induced current to lower and influence on the increase of the joint resistance.

  • PDF

Assembling and Insulation Test of 1MVA Single Phase HTS Transformer for Power Distribution

  • Kim, S. H.;Kim, W. S.;Kim, J. T.;Park, K. D.;H. G. Joo;G. W. Hong;J. H. Han;Lee, S. J.;S. Hahn
    • 한국초전도ㆍ저온공학회논문지
    • /
    • 제5권3호
    • /
    • pp.30-33
    • /
    • 2003
  • 1MVA high temperature superconducting (HTS) transformer with double pancake windings made of BSCCO-2223 HTS tapes was designed and manufactured. And prototype transformer with the same capacity was manufactured also. The each rated voltage of the HTS transformer is 22.9 kV and 6.6 kV. Four parallel BSCCO-2223 HTS tapes were wound in the double pancake windings of low voltage side. In order to distribute the currents equally in each HTS tapes, the three times transposition was performed between the double pancake windings. The windings of prototype transformer were wound using copper tape with the same size as BSCCO-2223 HTS tape. The core of the transformer was designed and manufactured as a shell type core made of laminated silicon steel plate. The several characteristics tests for the prototype transformer were performed in liquid nitrogen and insulation tests were accomplished also.

3상 10kVA 고온초전도 변압기의 특성 (Characteristics of a 10kVA three phase superconducting power transformer)

  • 이승욱;이희준;차귀수;이지광;류경우;한송엽
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2001년도 추계학술대회 논문집 전기기기 및 에너지변환시스템부문
    • /
    • pp.24-26
    • /
    • 2001
  • The high temperature super-conductor transformer gains interests from the industries. This paper described construction and test results of a 10kVA HTS transformer. Three phase transformer with double pancake windings were constructed. BSCCO-2223 wire, silicon sheet steel core and FRP cryostats were used in that transformer After the test of basic properties of the 3 phase HTS transformer using no load test, short ciucuit test and full load test, continuous operation of 100 hours with pure resistive load has been carried out. Test proved over-load capability and reliability of the HTS transformer.

  • PDF

The progresses of superconducting technology for power grid last decade in China

  • Xiao, Liye;Gu, Hongwei
    • 한국초전도ㆍ저온공학회논문지
    • /
    • 제17권1호
    • /
    • pp.1-5
    • /
    • 2015
  • With the increasing development of renewable energy, it is expected that large-scale renewable power would be transported from the west and north area of China to the east and south area. For this reason, it will be necessary to develop a wide-area power grid in which the renewable energy would be the dominant power source, and the power grid will be faced by some critical challenges such as long-distance large-capacity power transmission, the stability of the wide-area power grid and the land use problem for the power grid. The superconducting technology for power (STP) would be a possible alternative for the development of China's future power grid. In last decade, STP has been extensively developed in China. In this paper, we present an overview of the R&D of STP last decade in China including: 1) the development of high temperature superconducting (HTS) materials, 2) DC power cables, 3) superconducting power substations, 4) fault current limiters and 5) superconducting magnetic energy storage (SMES).

초전도 변압기 교류 손실 해석 (Analysis of AC Losses in HIS Transformer with Double Pancake Windings)

  • 김종태;김우석;김성훈;최경달;주형길;홍계원;한진호;이희균
    • 대한전기학회논문지:전기기기및에너지변환시스템부문B
    • /
    • 제54권1호
    • /
    • pp.17-21
    • /
    • 2005
  • AC loss is one of the important parameters in HTS (High Temperature Superconducting) AC devices. Among the HTS AC power devices, the transformer is the essential part in the electrical power system. But unfortunately, the transformer is the worst HTS device concerning AC loss because of very large magnetization loss due to high magnetic field applied to the HTS wire. We calculated the magnetization losses in HTS pancake windings for transformer according to the operating temperature. Two kinds of arrangement of HTS pancake windings were adopted for calculation of AC losses of a shell type transformer, and the analysis results were presented and discussed.

10kVA고온초전도변압기의 특성해석 및 제작 (Development and Characteristic Analysis of a 10kVA HTS Power Transformer)

  • 이희준;차귀수;이지광;최경달;류경우;한송엽
    • 한국초전도ㆍ저온공학회논문지
    • /
    • 제2권2호
    • /
    • pp.37-43
    • /
    • 2000
  • This paper describes the construction and test results of a 10kVA single phase HTS transformer. Double pancake windings with BSCCO-2223 HTS tape and G10-FRP cryostat with room temperature bore are used in the transformer. Two double pancake windings are connected in series to provide 188 turns and other two double pancake windings are connected in parallel to conduct the secondary current of 45.4[A]. Coefficients of the constructed transformer are obtained using the fundamental teats of the transformer. According to the test results, larger leakage reactance than expected is observed due to the bulky core which surrounds the sryostat.

  • PDF

고온초전도변압기의 특성해석 및 시험 (Test and Characteristic Analysis of an HTS Power Transformer)

  • 이희준;차귀수;이지광;최경달;류경우;한송엽
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2000년도 추계학술대회 논문집 학회본부 B
    • /
    • pp.321-323
    • /
    • 2000
  • This paper describes the construction and test results of a 10kVA single phase HTS transformer. Double pancake windings with BSCCO-2223 HTS tape and GFRP cryostat with room temperature bore are used in the transformer. Two double pancake windings are connected in series to provide 184 turns and two double pancake windings are connected in parallel to conduct the secondary current of 45.4A. Coefficients of the constructed transformer are obtained using the fundamental tests of the transformer. According to the test results, larger leakage reactance than expected is observed due to the bulky core which surrounded the cryostat.