• Title/Summary/Keyword: subcooling system

Search Result 91, Processing Time 0.021 seconds

Study on Performance of Heat Pump using a subcooled refrigerant (냉매과냉각에 의한 열펌프의 성능향상에 관한 연구)

  • 박승준
    • Proceedings of the Korean Society of Marine Engineers Conference
    • /
    • 2000.05a
    • /
    • pp.159-164
    • /
    • 2000
  • In this paper a new type refrigerant liquid subcooling system which adopts ice storage system is proposed. And the cycle characteristicso of a new system was investigated. Since this system subcools a refrigerant in the daytime using the ice storaged by electric power in the night it is high efficiency heat pump system which have the merit of ice storage system and possible to improve the performance of the heat pump. The running to storage the ie was carried out for 10 hours in the night and th evaporating temperature was set on $-5^{\circ}C.$ Subcooling operation stayed as 430^{\circ}C$ subcooling degree and perfomed till the water in the IST(Ice storage tank) was reached $12^{\circ}C$. The experimental result showed that a new system was superior to the existing refrigeration system generally. The total cooling capacity of a new system was about 11% higher than that of the existing refrigeration system. And the COP of a new system was improved by 22% compared to the existing refrigeration system.

  • PDF

A Study on the Cooling Characteristics and Subcooling Improvement of TMA-Water Clathrate Compound (TMA-물계 포접화합물의 냉각특성과 과냉각 개선에 대한 연구)

  • Park, Seul-Hyun;Kim, Chang-Oh
    • Journal of the Korean Solar Energy Society
    • /
    • v.34 no.6
    • /
    • pp.85-92
    • /
    • 2014
  • This study carried out experimental on the cooling characteristics of clathrate compound including TMA(Tri-Methyl-Amine ; $(CH_3)_3N$) as a low temperature latent heat storage material. And additive was used for subcooling improvement of TMA-water clathrate compound. The conclusion of above study is as following ; TMA 25wt%-water clathrate compound is shown stable phase change and low subcooling degree. The subcooling was improved in the case ethanol($CH_3CH_2OH$) 0.5wt% is added to TMA 25wt%-water clathrate compound.

Performance Analysis of Two-stage Compression and Two-stage Expansion Refrigeration System using Freon Refrigerants (친환경 프레온 냉매를 이용하는 단압축 단팽창 냉동시스템의 성능예측)

  • Roh, Geun-Sang;Kim, Jong-Ryeol
    • Journal of Fisheries and Marine Sciences Education
    • /
    • v.25 no.2
    • /
    • pp.301-306
    • /
    • 2013
  • In this paper, cycle performance analysis of two-stage compression and two-stage expansion refrigeration system using alternative freon refrigerants is presented to offer the basic design data for the operating parameters of the system. Alternative freon refrigerant for freon refrigerant R22 were used as working fluids in this study. The operating parameters considered in this study included evaporation temperature, condensation temperature, subcooling degree, superheating degree, and mass flow rate ratio of inter-cooler. The main results were summarized as follows : The COP of two-stage compression and two-stage expansion refrigeration system increases with the increasing subcooling degree and mass flow rate ratio of inter-cooler, but decreases with the increasing evaporating temperature, condensing temperature and superheating degree. Therefore, subcooling degree, mass flow rate ratio of inter-cooler of two-stage compression and two-stage expansion refrigeration system using alternative freon refrigerants have an effect on COP of this system.

Performance Characteristics of R744 OTEC Power Cycle with Operation Parameters (운전조건에 따른 R744용 해양온도차 발전 사이클의 성능 특성)

  • Yoon, Jung-In;Son, Chang-Hyo;Baek, Seung-Moon;Kim, Hyeon-Ju;Lee, Ho-Saeng
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.36 no.5
    • /
    • pp.580-585
    • /
    • 2012
  • In this paper, the cycle performance analysis for condensation and evaporation capacity, total work and efficiency of ocean thermal energy conversion power system using R744 ($CO_2$) is presented to offer the basic design data for the operating parameters of this system. The operating parameters considered in this study include superheating and subcooling degree, evaporation and condensation temperature, pump and turbine efficiency. The main results were summarized as follows : The evaporation capacity of R744 increases with superheating and subcooling degree, but decreases with the increasing condensation temperature. The total work increases with superheating and subcooling degree of R744, but decreases with the increasing evaporating temperature. And, the efficiency increases with subcooling and superheating degree, but decreases with the increasing condensation temperature. Therefore, superheating and subcooling degree, evaporation and condensation temperature and pump and turbine efficiency of R744 OTEC power system have an effect on the evaporation and condensation capacity, total work and efficiency of this system. With a thorough grasp of these effect, it is necessary to design the OTEC power cycle using R744.

Experimental Study on CHF Enhancement of Plate by Ultrasonic (초음파에 의한 평판에서의 임계열유속 증진에 대한 실험적 연구)

  • Kim, Dae-Hun;Kweon, Young-Chel;Jeong, Ji-Hwan
    • Proceedings of the KSME Conference
    • /
    • 2003.04a
    • /
    • pp.1512-1517
    • /
    • 2003
  • Augmentation of CHF by ultrasonic is experimentally studied under subcooling pool boiling condition. Experiment is carried out for downward-facing plate with and without the ultrasonic. The working fluid is distilled water. Experimental apparatus is composed of a bath, power supply, test section, ultrasonic generator, DAQ system. Experiment is performed with the subcooling temperature of $5^{\circ}C$, $20^{\circ}C$, $40^{\circ}C$ and the inclined angle of $0^{\circ}$, $10^{\circ}$, $20^{\circ}$, $45^{\circ}$, 90. From the experimental results, it is found that ultrasonic effect enhances CHF of the downward-facing plate. As increasing the degree of subcooling, the rate of CHF increase is enhanced. As increasing the inclined angle, the rate of CHF increase decreases. Also, we can see that the heat transfer mechanism of CHF augmentation is closely connected with the dynamic behavior of bubble generation and departure.

  • PDF

Performance Characteristics of a Cascade Refrigeration System with Internal Heat Exchanger using Carbon Dioxide (R744) and Propane (R290) (내부 열교환기 부착 $CO_2-C_3H_8$용 캐스케이드 냉동시스템의 성능 특성)

  • Son, Chang-Hyo
    • Transactions of the Korean hydrogen and new energy society
    • /
    • v.20 no.6
    • /
    • pp.526-533
    • /
    • 2009
  • In this paper, cycle performance analysis of $CO_2-C_3H_8$ (R744-R290) cascade refrigeration system with internal heat exchanger is presented to offer the basic design data for the operating parameters of the system. The operating parameters considered in this study include subcooling and superheating degree and gas cooling pressure and evaporating temperature in the propane (R290) low temperature cycle and the carbon dioxide (R744) high temperature cycle. The main results were summarized as follows : The COP of cascade refrigeration system of $CO_2-C_3H_8$ (R744-R290) increases with the increasing subcooling degree, but decreases with the increasing superheating degree. The COP of cascade refrigeration system increases with the increasing evaporating temperature, but decreases with the increasing gas cooling pressure. Therefore, superheating and subcooling degree, compressor efficiency, evaporating temperature and gas cooling pressure of $CO_2-C_3H_8$ (R744-R290) cascade refrigeration system have an effect on the COP of this system.

Phase change process of the initially subcooled material in a vertical cylinder (초기적으로 과냉각된 수직실린더 내부 물질의 상변화 과정)

  • Baek, Yeong-Ryeol;Lee, Jae-Heon
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.21 no.1
    • /
    • pp.24-35
    • /
    • 1997
  • Melting process inside in a vertical cylinder has been investigated numerically to observe heat transfer characteristics in the latent heat storage vessel applied to the thermal storage system. The time-dependent boundary fitted coordinate system was introduced to overcome the difficulty caused by the moving boundary. The present results are in good agreement with the available previous data when the initial subcooling effect of the solid phase is not considered. It is found that the melting is promoted by the natural convection, but is delayed by the initial subcooling effect of the solid phase.

Critical Heat Flux of an Impinging Water Jet on a Heated Surface with Boiling (비등을 수반하는 발열면에 충돌하는 수분류의 임계열유속에 관한 연구)

  • Lee, Jong-Su;Kim, Heuy-Dong;Choi, Kuk-Kwang
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.24 no.4
    • /
    • pp.485-494
    • /
    • 2000
  • The purpose of this paper is to investigate a critical heat flux(CHF) during forced convective subcooled and saturated boiling in free water jet system impinged on a rectangular heated surface. The surface is supplied with subcooled or saturated water through a rectangular jet. Experimental parameters studied are a width of heated surface, a height of supplementary water and a degree of subcooling. Incipient boiling point is observed in the temperature of 6${\~}8^{\circ}C$ of superheat of test specimen. CHF depends on jet velocity for various boiling-involved coolant system. CHF also is proportional to the nozzle exit velocity to the power of n, where n is 0.55 and 0.8 for subcooled and saturated boiling, respectively. CHF is enhanced with a higher jet velocity, higher degree of subcooling and smaller width of a heated surface.

The Study of Thermal Properties of TMA Clathrate on Additives (첨가제를 첨가한 TMA 물계-포접화합물의 열물성 연구)

  • Kim, K.I.;Chung, N.K.;Kim, J.H.;Kim, C.O.
    • Proceedings of the KSME Conference
    • /
    • 2003.11a
    • /
    • pp.250-255
    • /
    • 2003
  • TMA clathrate that is used as PCM of low temperature thermal storage system in this research creates hydrate crystallization at higher temperature then pure water, and its application is expected as PCM because of comparatively big latent heat without phase separation phenomenon. Acetone, Ethylen Glycol, and Ethanol is used as additive and evaluated experimentally for the purpose of the improvement in subcooling of TMA clathrate. In view of the results so far achieved subcooling is improved, the running time of the refrigerator is reduced. Thus the results are expected to use for the increase of coefficient of performance of low temperature thermal storage system in the building.

  • PDF

Performance Analysis of Cascade Refrigeration System with Respect to Refrigerants Appling to High Temperature Cycle (고온측 냉매에 따른 이원 냉동시스템의 성능 분석)

  • Yoon, Jung-In;Jeon, Min-Ju;Son, Chang-Hyo
    • Journal of Power System Engineering
    • /
    • v.21 no.3
    • /
    • pp.45-50
    • /
    • 2017
  • This paper presents the Coefficient of performance(COP) and mass flow ratio of cascade refrigeration system with respect to refrigerants appling to high temperature cycle. The operating parameters considered in this study include degree of superheating and subcooling, compressor efficiency, evaporating temperature, condensing temperature and internal heat exchanger effectiveness in high temperature cycle. The result of this study is as follows : The COP of cascade system increases with increasing degree of superheating and subcooling, compressor efficiency and internal heat exchanger effectiveness except increasing condensing temperature. The mass flow ratio of low and high temperature cycle increases with increasing evaporating temperature and condensing temperature, but decreases with increasing internal heat exchanger effectiveness, degree of superheating and subcooling. Also, the mass flow ratio has no correlation with compressor efficiency at high temperature cycle.