Couette 흐름현상을 이용한 초고압변압기의 유동대전 기구 연구 (A Study on the Electrification Mechanism in UHV Transformer by Couette Flow)

  • 곽희로;정용기;권동진
    • 한국조명전기설비학회지:조명전기설비
    • /
    • 제9권4호
    • /
    • pp.93-102
    • /
    • 1995
  • The purpose of this paper is to analyze the streaming electrification mechanism (SEM) generated in UHV transformer. This experiment used Couette Charger and interpreted the mechanism hydromechanically and electromagnetically. This work estimated the turbulent core density ($\rho$o) by measuring the short circuit current (isc) and the open circuit voltage (νoc) generated in Couette Charger and also studied the changes of the short circuit (isc), the open circuit voltage (νoc), the turbulent core density ($\rho$o) and the conductivity ($\sigma$) with adding BTA to restrain streaming electrification. as a result adding BTA increased the conductivity of oil and decreased the turbulent core density($\rho$o).

  • PDF

유동대전(流動帶電)에 미치는 변압기(變壓器) 재질(材質)의 영향(影響) (Effect of Materials on Streaming Electrification in Transformer)

  • 권동진;강창구;곽희로;김재철;이덕철
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1990년도 추계학술대회 논문집 학회본부
    • /
    • pp.170-172
    • /
    • 1990
  • In a large power transformer, an insulating oil is forced to circulate for cooling the heat generated by the losses within the windings and core. When oil flows and rubs against various materials, including insulating paper and steel, electrostatic charges are separated at the interface of the oil and the solid material. This paper considers the polarity and the streaming electrification of the various materials which are used in transformer. As a result of this study, it is confirmed that the leakage current on the solid material, such as paper, is charged negative. On the other hand, the solid material, such as steel, is positively charged.

  • PDF

유동대전 억제제가 첨가된 변압기유의 전기전도 특성 (The Electrical Conduction Characteristics of Transformer Oils added the Anti-static Agent for Streaming Electrification)

  • 이용우;이태훈;오세영;이종필;차광훈;홍진웅
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1997년도 하계학술대회 논문집 C
    • /
    • pp.1213-1215
    • /
    • 1997
  • In order to investigate the electrical characteristics due to the BTA(Benzotriazole) additive in the transformer, the electrical characteristics of the transformer oils contained benzotriazole as an anti-static agent for streaming electrification is studied by measuring the electric conduction. As a result of the electrical conduction characteristics, it is confirmed that the conduction current of virgin specimen is more higher than that of specimen contained the BT A 10[ppm] over 35[$^{\circ}C$], but that of specimen contained the BT A 10[ppm] over 50[$^{\circ}C$] is increased.

  • PDF

이온성 및 양성 계면 활성제가 변압기유의 화학적 특성 및 유동대전에 미치는 영향 (Influence of Interface Active substances(Ionic and Amphoteric) on Chemical property and Streaming Electrification of Transformer Oil)

  • 김용운;이덕출
    • E2M - 전기 전자와 첨단 소재
    • /
    • 제10권7호
    • /
    • pp.719-726
    • /
    • 1997
  • This research was conducted to analyze the change of surface tension, viscosity, streaming current and conductivity of transformer oil when it were injected with the interface active substances.(anionic:S-111, cationic:S-121, amphoteric:S-131) The changes properties of the surface tension and viscosity of the oil which were injected with the interface active substances were divided into the changes area and the minimum reduction area. The surface tension and viscosity of the oil which were injected with three different kinds of interface active substances showed remarkable change at the point where the concentration of the substance in anionic, in cationic and in amphoteric were 100[ppm], 10[ppm] and 1[ppm] respectively. The streaming current and conductivity of the same sample oil were also changed at the same densities of the surface tension and viscosity. For this factor, it was possibile for us to interpret the mechanism of the streaming current and conductivity. Therefore the interface active substances of the three kinds were injected into the oil within the limit of optimal volume, prevention effects of electrification were showed more excellence than unmixed insulating oil.

  • PDF

수분 및 머지의 첨가에 따른 절연유의 대전경향 (Electrification Tendency of Oil Adding Moisture and Dust)

  • 김두석;권동진;강창구
    • 한국조명전기설비학회지:조명전기설비
    • /
    • 제6권5호
    • /
    • pp.50-56
    • /
    • 1992
  • This paper presents the effect of moisture and dust on streaming electrification in transformer oil, in order to investigate the electrification tendency of oil adding moisture an dust. Authors designed series electrification device to analyse streaming electrification phenomena easily. Experimental results show that the streaming current is linearly increased with oil velocity and it has a peak value at about a 50 [%]. Adding of moisture and dust in oil decreased charging level and it was dominant in case of moisture.

  • PDF

유로형상에 의한 절연지의 유동대전 특성 (Streaming Electrification of Pressbord by Oil Path Form)

  • 이동훈;최창락;박재윤;이충식;고희석;이덕출
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 1995년도 추계학술대회 논문집
    • /
    • pp.332-335
    • /
    • 1995
  • Electrification pipe modeled on the oil path of the high power transformer is designed and manufactured. Distributions of oil flow velocity are simulated as spacer form in the electrification pipe. Streaming currents are investigated as each electrification pipe. The surface oil velocity of spacer is small the streaming current.

  • PDF

변압기유의 유동대전 현상에 관한 연구 (A Study on the Streaming Electrification Phenomena of the Transformer Oil)

  • 강성화;임기조;주상범;김명녕;강도열;김봉협
    • 대한전기학회논문지
    • /
    • 제39권6호
    • /
    • pp.568-576
    • /
    • 1990
  • Recently, streaming electrification in forced oil cooled power transformer has been taken up as a serious problem. In this paper, the charging tendency of various insulation oils, such as mineral oil, polybutene and silicone oil has been measured by means of an injection type charging tendency measuring apparatus under various condition. The experimental data of the dependence of the leakage current on flow velocity and temperature of oil can be explained by considering the flow state such as laminar and turbulent flow. The effect of additives on the charging tendency of mineral oil has been investigated. BTA is regarded as the most effective retardant to electrification of oil among the additives chose for this investigation.

  • PDF

변압기 절연유의 열화에 따른 대전특성 (Characteristics of Static Electrification on Insulation Oil Aging)

  • 권동진;김한상;정용기;김경화;김두석;곽희로;박동화
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1994년도 하계학술대회 논문집 C
    • /
    • pp.1615-1618
    • /
    • 1994
  • This paper studied the streaming electrification of the U.H.V. transformer with the spinning cylinder system, and compared and analyzed it with the conventional forced flowing system which uses a pump or gas for oil flowing. Also, accumulated surface voltage in its electrified material was measured with the electrostatic voltmeter, and the effect of insulation oil aging was measured. As results, in spinning cylinder system, characteristics of the streaming electrification to its rotational speed and oil temperature are same tendency as those of tile forced flowing system and it showed the spinning cylinder system is useful to study the streaming electrification. And, aging of insulation oil increases the electricity of streaming electrification at initial stage of aging.

  • PDF

먼지의 첨가에 따른 절편유의 대전경향 (Electrification tendency of oil adding dust)

  • 곽희로;김두석;권동진;조국희
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 1992년도 추계학술발표회논문집
    • /
    • pp.60-63
    • /
    • 1992
  • This paper presents the effect of moisture and dust on streaming electrification in transformer oil, in order to investigate the electrification tendency of oil adding moisture and dost. Authors designed series electrification device to analyse streaming electrification phenomena easily. Experimental results show that adding of moisture and dust in oil decreased charging level and it was dominant in case of moisture.

  • PDF

재질이 변압기 절연유의 유동대전에 미치는 영향

  • 곽희로;김재철;김두석;권동진
    • 한국조명전기설비학회지:조명전기설비
    • /
    • 제5권3호
    • /
    • pp.72-77
    • /
    • 1991
  • In a large power transformer, insulating oil is forced to circulate for cooling the heat generated by the losses within windings and core. When insulating oil flows and rubs against various materials, such as insulating paper or core, the electrostatic charges are separated at the interface of the oil and the solid material. This paper considers the streaming electrification of various materials used in the transformer. In this study, we show that a solid material such as paper is negatively charged. On the other hand, a solid material such as core is positively charged.

  • PDF