• Title/Summary/Keyword: steady-state voltage stability

Search Result 73, Processing Time 0.023 seconds

Effects of HTS Cable Applied to the Voltage Stability Limited Power System (전압 안정도 제약계통에 대한 고온초전도 케이블 적용효과)

  • Lee, Geun-Joon;Hwang, Si-Dol
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.18 no.5
    • /
    • pp.169-173
    • /
    • 2004
  • This paper presents the basic application idea of superconductor cable for voltage stability limited power system. In bulk power system, the transfer capability of transmission line is often limited by the voltage stability, and superconductor cable could be one of the countermeasure to enhance heat transfer limit as well as voltage stability limit. Steady state voltage stability approach by P-V curve is used to calculate the maximum transfer capability of initial system and superconductor applied system. IEEE-14 bus system is used to demonstrate its applicability.

The Implementation of Probabilistic Security Analysis in Composite Power System Reliability (복합전력계통 신뢰도평가의 확률론적 안전도 도입)

  • Cha, Jun-Min;Kwon, Sae-Hyuk;Kim, Hyung-Chul
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.55 no.5
    • /
    • pp.185-190
    • /
    • 2006
  • The security analysis relates to the ability of the electric systems to survive sudden disturbances such as electric short circuits or unanticipated loss of system elements. It is composed of both steady state and dynamic security analyses, which are not two separate issues but should be considered together. In steady state security analysis including voltage security analysis, the analysis checks that the system is operated within security limits by OPF (optimal power flow) after the transition of a new operating point. On the other hand, dynamic security analysis deals that the transition will lead to an acceptable operating condition. Transient stability, which is the ability of power systems to maintain synchronism when subjected to a large disturbance, is a principal component in dynamic security analysis. Usually any loss of synchronism will cause additional outages. They make the present steady state analysis of the post-contingency condition inadequate for unstable cases. This is the reason of the need for dynamics of systems. Probabilistic criterion can be used to recognize the probabilistic nature of system components and shows the possibility of system security. A comprehensive conceptual framework for probabilistic static and dynamic assessment is presented in this paper. The simulation results of the Western System Coordinating Council (WSCC) system compare an analytical method with Monte-Carlo simulation (MCS). Also, a case study of the extended IEEE Reliability Test System (RTS) shows the efficiency of this approach.

Design and Analysis of Large Capacity Lithium Polymer Battery Charger for Hybrid Electrical Vehicle (HEV용 중대형 2차전지 충전기 설계 및 해석)

  • Oh Dong-Seob;Oh Sung-up;Seong Se-jin;Choi Jae-dong
    • Proceedings of the KIPE Conference
    • /
    • 2004.07a
    • /
    • pp.87-91
    • /
    • 2004
  • In this paper, the paralleled forward converter, that is generally used as the power supply for the low voltage, high current load, is described. The proposed forward converter for battery charging could be provided the power without failure not only in steady state but also in the transient period by the step load variation or the unexpected faults among the converter modules. Each converter nodule designed is operated alone with the self closed controller for the elevation of stability, performance, reliability, and maintainability. The frequency response of the designed converter module is analyzed, and the stability is confirmed in analytic method. And the experiments of the paralleled battery charger are carried out in steady state, in the step load variation.

  • PDF

Modeling and Stability Analysis of Automotive HID Lamp Ballast (자동차 헤드라이트용 고압 방전등 안전기 시스템의 모델링 및 안정도 해석)

  • 이인규;최성진;이규찬;조보형
    • Proceedings of the KIPE Conference
    • /
    • 1999.07a
    • /
    • pp.411-414
    • /
    • 1999
  • This paper presents design and analysis of an HID lamp ballast for a fast turn on characteristics and stable operation. It produces a high open circuit voltage for the ignition and it is controlled to supply effectively the power required to shorten the warm-up period after the breakdown. The lamp modeling by empirical data is presented. It is very effective in the designing of the control loop in the steady-state operating region. A stable operation of the lamp power regulation in the steady state is achieved, which is crucial for the long life time and constant light output. Stability analysis of the system is performed and the results are verified through various simulation results and the hardware experiments.

  • PDF

Analysis of Response of a Wind Farm During Grid/inter-tie Fault Conditions (그리드/연계선 사고 시 풍력발전단지의 응동 분석)

  • Lee, Hye-Won;Kim, Yeon-Hee;Zheng, Tai-Ying;Lee, Sang-Cheol;Kang, Yong-Cheol
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.60 no.6
    • /
    • pp.1128-1133
    • /
    • 2011
  • In a wind farm, a large number of small wind turbine generators (WTGs) operate whilst a small number of a large generator do in a conventional power plant. To maintain high quality and reliability of electrical energy, a wind farm should have equal performance to a thermal power plant in the transient state as well as in the steady state. The wind farm shows similar performance to the conventional power plant in the steady state due to the advanced control technologies. However, it shows quite different characteristics during fault conditions in a grid, which gives significant effects on the operation of a wind farm and the power system stability. This paper presents an analysis of response of a wind farm during grid fault conditions. During fault conditions, each WTG might produce different frequency components in the voltage. The different frequency components result in the non-fundamental frequencies in the voltage and the current of a wind farm, which is called by "beats". This phenomenon requires considerable changes of control technologies of a WTG to improve the characteristics in the transient state such as a fault ride-through requirement of a wind farm. Moreover, it may cause difficulties in protection relays of a wind farm. This paper analyzes the response of a wind farm for various fault conditions using a PSCAD/EMTDC simulator.

A Method of Determining the Maximum Interface Flow Limit Using Continuation Algorithm (연속알고리듬을 이용한 연계선로의 송전운용한계 결정)

  • Kim, Seul-Gi;Song, Hwa-Chang;Lee, Byeong-Jun;Gwon, Se-Hyeok
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.49 no.2
    • /
    • pp.78-84
    • /
    • 2000
  • This paper introduces a method of determining the maximum real power transfer limit of interface lines, which connect two areas of a power system, using locally parameterized continuation algorithm. This method traces the path of power flow solutions as interface flow is gradually increased under a certain load demand condition and finds the steady state voltage stability limit, the interface flow limit. Voltage stability index is used to indicate how close the maximum limit is reached. Also, this study presents a procedure to determine the security-constrained interface flow limit using the above method. Contingency ranking index is proposed to identify the severity of contingencies. The case study is performed according to the suggested procedure.

  • PDF

Application of ULTC and load models in dynamic voltage stability analysis (동적 전압안정도 해석에서의 ULTC 및 부하모델의 적용)

  • Song, Hwa-Chang;Lee, Byong-Jun
    • Proceedings of the KIEE Conference
    • /
    • 2005.07a
    • /
    • pp.411-413
    • /
    • 2005
  • Static approaches usually employed in voltage stability analysis are based on the pre-determined scenarios of varying load and generation patterns. Thus, even though the approaches are applied to the same system condition, one may obtain different voltage instability phenomena using different scenarios. In the stage of concrete control strategy determination against voltage instability, dynamic approaches with full-time and/or quasi steady-state simulations need to be applied in order to confirm the effectiveness of the established control strategies. This paper describes the ULTC and dynamic load models, and discusses characteristics of the models.

  • PDF

Simulation of Reactive Power Compensation in Grid-Connected Wind Power Generation System (계통연계 풍력발전시스템의 무효전력 보상에 대한 시뮬레이션)

  • Ro, Kyoung-Soo;Jang, Bo-Kyoung
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.25 no.6
    • /
    • pp.82-89
    • /
    • 2011
  • Reactive power support is considered to be necessary for dealing with a voltage stability issue with wind turbine system employing squirrel-cage induction generator(SCIG). This paper analyses steady-state characteristics of the SCIG wind turbine system by simulating torque-slip characteristics of SCIG with respect to variations of interconnecting network strength and generator terminal voltage. It also presents dynamics analysis of SCIG wind turbine system on Simulink to investigate the impact of static var compensator(SVC) and static synchronous compensator(STATCOM) on transient stability enhancement. It analysed transient stability with varying fault duration times and compared the transient stability characteristics with varying rated capacities of SVC and STATCOM. It is shown that the STATCOM has a better performance and reactive power support compared to SVC.

An Interior Point Method based Reactive Optimal Power Flow Incorporating Margin Enhancement Constraints

  • Song Hwa-Chang;Lee Byong-Jun;Moon Young-Hwan
    • KIEE International Transactions on Power Engineering
    • /
    • v.5A no.2
    • /
    • pp.152-158
    • /
    • 2005
  • This paper describes a reactive optimal power flow incorporating margin enhancement constraints. Margin sensitivity at a steady-state voltage instability point is calculated using invariant space parametric sensitivity, and it can provide valuable information for selection of effective control parameters. However, the weakest buses in neighboring regions have high margin sensitivities within a certain range. Hence, the control determination using only the sensitivity information might cause violation of operational limits of the base operating point, at which the control is applied to enhance voltage stability margin in the direction of parameter increase. This paper applies an interior point method (IPM) to solve the optimal power flow formulation with the margin enhancement constraints, and shunt capacitances are mainly considered as control variables. In addition, nonlinearity of margin enhancement with respect to control of shunt capacitance is considered for speed-up control determination in the numerical example using the IEEE 118-bus test system.

DIRECT COMPUTATION OF MARGINAL OPERATING CONDITIONS FOR VOLTAGE COLLAPSE

  • Lee, Kyung-Jae;Jung, Tay-Ho
    • Proceedings of the KIEE Conference
    • /
    • 1989.07a
    • /
    • pp.195-201
    • /
    • 1989
  • Voltage collapse is a serious concern to the electirc utility industry. It is common to associate steady-state stability with the ability of the transmission system to transport real power and to associate voltage collapse with the inability to provide reactive power at the necessary locations within the system. An algorithm to directly calculate the critical point of system voltage collapse was presented by the authors. The method (based on the ordinary power flow equations and explicit requirement of singularity of the Jacobian matrix) is basically one degree of freedom with proper load distribution factors. This paper suggests a modified algorithm to increase the degree of freedom, introducing the nonlinear programming technique. The objective function is a distance measure between the present operating point and the closest voltage collapse point. Knowledge of the distance and the most vulnarable bus from the voltage collapse point of view may be used as a useful index for the secure system operation.

  • PDF