• 제목/요약/키워드: smoke temperatures

검색결과 42건 처리시간 0.022초

초고층 건축물에서 배연창 개방이 연돌효과에 미치는 영향 (The Influence on the Stack Effect with the Opening of Smoke Ventilators in High-rise Buildings)

  • 임채현;김범규;여용주;박용환
    • 한국화재소방학회:학술대회논문집
    • /
    • 한국화재소방학회 2008년도 춘계학술논문발표회 논문집
    • /
    • pp.209-213
    • /
    • 2008
  • The effects on the performance of natural smoke exhaust ventilators installed in high-rise buildings were analyzed depending on the wind velocities and smoke temperatures using CONTAMW tool. The results showed that the smoke exhaust ventilators can maintain given performances in such conditions as low smoke temperatures and low wind velocities. However, high smoke temperatures and high wind velocities can prevent the smoke ventilators to exhaust smokes from the fire room. Significant changes in stack effects in high-rise buildings can also occur with the opening of smoke ventilators in the fire floor.

  • PDF

터널화재시 환기방식에 따른 연기거동에 관한 실험적 연구 (An Experimental Study of Smoke Movement in Tunnel Fires According to Ventilation Method)

  • 이성룡;정진용;김충익;유홍선
    • 설비공학논문집
    • /
    • 제14권9호
    • /
    • pp.691-698
    • /
    • 2002
  • In this study, reduced-scale experiments were conducted to analyze smoke movement in tunnel fires according to vepntilation method. The 1/20 scale experiments were carried out under the Froude scaling using gasoline pool fires ranging from 6.6 to 10 cm in diameter corresponding to total heat release rate from 0.714 to 2.5 kW. Temperatures near the ceiling were lowered by installing the vent, and much lowered by operating fan compared wiht tile case without vent. In case of forced ventilation, the exhaust fan was more effective than the intake fan. Vertical temperatures at the upper part of the tunnel were also lowered by installing the vent. But, when suction fan was operated, temperatures at the lower part of the tunnel were higher than that without vent.

터널 화재시 터널 단면의 종횡비에 따른 연기 거동에 관한 (An Experimental Study of Smoke Movement in Tunnel Fires with Aspect Ratio of Tunnel Cross Section)

  • 이성룡;유홍선;김충익
    • 대한기계학회:학술대회논문집
    • /
    • 대한기계학회 2003년도 추계학술대회
    • /
    • pp.115-120
    • /
    • 2003
  • In this study, smoke movement in tunnel fires was investigated with various aspect ratio(0.5, 0.667, 1.0, 1.5, 2.0) of tunnel cross section. Reduced-scale experiments were carried out under the Froude scaling using 8.27 kW ethanol pool fire. Temperatures were measured under the ceiling and vertical direction along the center of the tunnel. Smoke front velocity and temperature decrease rate were reduced as higher aspect ratio of the tunnel cross-section. Smoke movement was evaluated by analysis of vertical temperature distribution 3 m downstream from the fire source. Elevation of smoke interface according to N percent rule was under about 60% of tunnel height.

  • PDF

고층건물의 수직방향 연기거동에 미치는 발코니의 영향에 관한 실험적 연구 (An Experimental Study on the Effect of the Balcony on the Vertical Smoke Movement of the High Rise Building)

  • 양승신;김성찬;유홍선;심상훈
    • 한국안전학회지
    • /
    • 제20권1호
    • /
    • pp.42-48
    • /
    • 2005
  • The present study investigates the effect of balcony on external smoke movement of high rise building through the fire tests of the 1/10 reduced model scale using Froude scaling. A hexane pool fire is used to examine the smoke movement for various opening sizes of balcony and temperature distributions are measured by T-type thermocouples. Also, hydrogen bubble technique is applied to visualize the smoke movement near the balcony. Measured temperatures of the closed balcony is 2.5 times higher than those of the open balcony because the external smoke in case of the closed balcony rise along the vertical wall. The maximum vertical temperature of partially closed balcony is similar with fully closed balcony and mean temperature inside of balcony increases as opening size of balcony decreases. The experimental results show that the balcony space plays an important roles in preventing fire propagation and cooling of smoke layer. In order to ensure the fire safety in high rise building design, a series of systematic researches are required to examine the various type of balconies.

Study on Fire Simulation in College Dormitories Based on Pyrosim

  • Zechen Zhang;Hasung Kong
    • International journal of advanced smart convergence
    • /
    • 제13권3호
    • /
    • pp.321-327
    • /
    • 2024
  • In recent years, the frequency of fires in college dormitories has been increasing, primarily due to outdated electrical wiring and improper use of electrical appliances. Given the high population density in such buildings, fires can cause significant damage to life and property. To better understand the dynamics of dormitory fires, this study uses Pyrosim fire simulation software to model fire scenarios in a six-story male dormitory. The study focuses on analyzing key factors such as heat release rates, smoke spread, temperature changes, and carbon monoxide concentrations during a fire. Simulation results indicate that smoke spreads rapidly after a fire breaks out, significantly reducing visibility and hindering evacuation efforts. Simultaneously, temperatures near the fire source rise quickly, exceeding safe levels, and carbon monoxide concentrations reach dangerous thresholds in a short time, greatly increasing the risk of poisoning. Based on these findings, the study proposes several recommendations to improve fire prevention in dormitories, including installing smoke barriers, improving evacuation routes, adding mechanical smoke extraction systems, and enhancing students' fire safety awareness and skills through regular training. These measures are crucial for reducing fire risks and enhancing fire safety in college dormitories.

구난역을 갖는 철도 터널 내부의 연기거동 특성 (Characteristics of Smoke Propagation in Railway Tunnels with Rescue Station)

  • 장원철;김동운;이성혁;유홍선
    • 한국화재소방학회논문지
    • /
    • 제23권4호
    • /
    • pp.13-18
    • /
    • 2009
  • 본 연구의 목적은 구난역을 갖는 철도 터널 내부의 연기 거동 특성을 분석하는 것이다. 특히 화재 위치 변화에 따른 연기 전파 특성에 대해 수치해석을 수행하고 이때 해석 조건으로 사용되는 발열량은 터널내 풀 화재(pool fire) 실험을 통해 결정된다. 사용된 연료는 n-heptane($C_7H_{16}$)이고, 각 변의 길이가 4cm인 정사각형 풀을 이용하였다. 본 연구에서는 상용코드인 FLUENT(Ver.6.3) 를 사용하여 수치해석을 수행하였고 화원 생성 현상은 MVHS(Modified Volumetric Heat Source) 모델을 통해 모사되었다. 해석 결과, 연기가 터널을 따라 전파되면서 구난역까지 영향을 미치는 것을 확인할 수 있었으며 따라서 배연시스템의 설치가 요구됨을 알 수 있다. 또한 교행로와 방화벽이 연기 제어에 기여함을 확인하였다.

터널내 수분무 시설 설치시 연기유동 특성 연구 (A Study on Smoke Movement Characteristics for Water spray system Installation in Tunnel)

  • 임경범;김하영;유지오;이동호
    • 한국화재소방학회:학술대회논문집
    • /
    • 한국화재소방학회 2008년도 춘계학술논문발표회 논문집
    • /
    • pp.230-233
    • /
    • 2008
  • 본 연구는 수분무 소화설비의 효용성에 대한 기초평가를 수행할 목적으로 FDS 수치시뮬레이션을 수행하였다. 화재강도 및 풍속의 변화에 따른 화재시 온도 및 연기농도에 대한 안전성 확보 효과를 분석하였다. 터널내 풍속이 없는 경우 수분무는 냉각효과에 의한 온도 및 연기농도 감소효과가 아주 우수하여 대피자의 안전성 확보에 효과적이었다.

  • PDF

급기가압 댐퍼의 설정 기준압에 따른 부속실 차압 특성 연구 (Pressure Differentials in the Elevator Lobby Depending on the Reference Pressures of the Pressurizing Dampers)

  • 박용환
    • 한국화재소방학회논문지
    • /
    • 제21권4호
    • /
    • pp.12-17
    • /
    • 2007
  • 본 연구는 최근 우리나라 고층아파트에서 많은 문제가 되고 있는 승강장 부속실의 급기가압 시스템에 있어서 댐퍼 적정차압의 기준 압력에 대한 문제를 FDS 화재모델링을 이용하여 현상학적으로 살펴보았다. 화재 초기 누설틈새만 있는 밀폐된 화재실의 온도와 압력은 연소에너지와 고온 연소가스의 발생으로 온도와 압력이 크게 상승하는 것으로 나타났다. 따라서 자동차압조절 급기댐퍼의 기준압을 옥내 대기압으로 설정 시에는 화재 시 실제 차압의 감소와 방연풍속 부족으로 상황에 따라 피난안전 공간인 부속실로의 연기 유입이 발생할 우려가 있는 것으로 나타났다.

미세물분무를 이용한 PPV의 화재진압효과 (Fire Suppression Effect of PPV with Water Mist System)

  • 김성원;신창섭
    • 한국안전학회지
    • /
    • 제18권4호
    • /
    • pp.71-77
    • /
    • 2003
  • To inject fresh air into a fire room, Positive Pressure Ventilation (PPV) can be used and the blower of PPV increases inside pressure of the room. It makes high flow rate of products of combustion, smoke and heat from the structure, and it is very helpful to fireman on the fire extinguishing work. The flame moves to the direction of airflow and the temperature of flame can be decreased rapidly. In this experiment, a water mist system is applied to PPV to increase the effectiveness, and various effective factors are studied. n-Heptane and pine wood stick were used as fuel. Temperatures at the above and behind the combustion pan were strongly reduced by the water mist system and by the convective cooling with airflow. The smoke density was also decreased by PPV with water mist system and it can be explained by the absorption of smoke particles on the water mist droplet and by the strong exhausting effects of mobile fan.

터널 내 차량 화재에 따른 연기 확산 거동에 관한 연구 (A Study on the Behaviour of Smoke Spread Caused by Vehicle Fire in a Road Tunnel)

  • 윤용균;주은혜
    • 터널과지하공간
    • /
    • 제22권5호
    • /
    • pp.365-372
    • /
    • 2012
  • 본 논문에서는 환기구의 존재, 환기구 설치 대수, 환기구 용량, 복수 화원의 존재가 도로터널에서 발생한 차량 화재에 의한 연기 온도 분포에 미치는 영향을 평가하였다. 6개의 시나리오를 가정하였으며 FDS를 이용하여 시나리오 해석을 실시하였다. 해석 결과 환기구의 설치 대수가 증가함에 따라 연기의 온도는 감소하는 것으로 나타났지만, 환기구의 설치 대수가 2대인 경우와 3대인 경우에 온도 감소 효과는 거의 같은 것으로 나타났다. 환기구의 설치 용량은 환기구의 설치 대수 보다 연기 온도 감소에 더 큰 영향을 주는 것으로 해석되었다. 환기구가 없는 시나리오 No. 1과 복수 화원을 갖는 시나리오 No. 6를 제외한 나머지 시나리오에 대해서 해석한 결과 화원 상부에서의 연기 온도는 모두 $400^{\circ}C$ 이하로 나타났는데, 이는 화원 상부 연기층에서 발생하는 복사에 의해 화원 주변 가연물의 착화가 어렵다는 것을 나타낸다.