• Title/Summary/Keyword: smoke scale

Search Result 154, Processing Time 0.024 seconds

Experimental Study on the Designed Ventilation Effect on the Smoke Movement at Rescue Station fire in Railway Tunnel (터널 내 화재발생시 구난역 내의 연기 거동에 미치는 설계된 환기 영향에 대한 실험적 연구)

  • Kim, Dong-Woon;Lee, Seong-Hyeok;Ryou, Hong-Sun;Yoon, Sung-Wook
    • 한국전산유체공학회:학술대회논문집
    • /
    • 2008.03b
    • /
    • pp.163-167
    • /
    • 2008
  • In this study, the 1/35 reduced-scale model experiment were conducted to investigate designed ventilation effect on the smoke movement at rescue station fire in railway tunnel. A model tunnel with 2 mm thick, 10 m long, 0.19 m high and 0.26 m was made by using Froude number scaling law. The cross-passages installing escape door at the center were connected between incident tunnel and rescue tunnel. The n-heptane pool fires with heat release rate 698.97W were used as fire source. The fire source was located at the center and portal of incident tunnel as worst case. A operating ventilation system extracted smoke amount of 0.015 cms(cubic meters per second). The smoke temperature and CO gas concentration in cross-passage were measured to verify designed ventilation system. The result showed that, at center fire case without ventilation, smoke did not propagate to rescues station. In portal fire case, smoke spreaded to rescues station without ventilation. But smoke did not propagated to rescues station with designed ventilation.

  • PDF

An Experimental Study on the Effect of the Balcony on the Vertical Smoke Movement of the High Rise Building (고층건물의 수직방향 연기거동에 미치는 발코니의 영향에 관한 실험적 연구)

  • Yang Seung-Shin;Kim Sung-Chan;Ryou Hong-Sun;Shim Sang-Hoon
    • Journal of the Korean Society of Safety
    • /
    • v.20 no.1 s.69
    • /
    • pp.42-48
    • /
    • 2005
  • The present study investigates the effect of balcony on external smoke movement of high rise building through the fire tests of the 1/10 reduced model scale using Froude scaling. A hexane pool fire is used to examine the smoke movement for various opening sizes of balcony and temperature distributions are measured by T-type thermocouples. Also, hydrogen bubble technique is applied to visualize the smoke movement near the balcony. Measured temperatures of the closed balcony is 2.5 times higher than those of the open balcony because the external smoke in case of the closed balcony rise along the vertical wall. The maximum vertical temperature of partially closed balcony is similar with fully closed balcony and mean temperature inside of balcony increases as opening size of balcony decreases. The experimental results show that the balcony space plays an important roles in preventing fire propagation and cooling of smoke layer. In order to ensure the fire safety in high rise building design, a series of systematic researches are required to examine the various type of balconies.

Analysis of Smoke Behavior in Fire within Real-scale Theater Using FDS: Influences of Fire Curtain and Natural Smoke Vent Area (FDS를 이용한 실규모 공연장 무대 내 화재 시 연기 거동 분석: 방화막 및 자연배출구 면적의 영향)

  • Kim, Jae Han;Lee, Chi Young;Jeong, Lee Gyu;Kim, Duncan
    • Fire Science and Engineering
    • /
    • v.32 no.6
    • /
    • pp.7-14
    • /
    • 2018
  • This study investigated numerically the influences of fire curtain and natural smoke vent area on smoke movement in the stage fire of a theater using FDS (Fire Dynamics Simulator). The dimension of the theater stage was 31 m in width, 34 m in depth, and 32 m in height. The area ratios between the natural smoke vent and stage were approximately 10%, 8%, 5%, and 1%. The gap distance between the fire curtain and proscenium wall was 0.5 m. The fire curtain and natural smoke vent area were observed to affect significantly the behavior of smoke movement to the auditorium and the mass flow rates of inflow and outflow through the natural smoke vent and proscenium opening. In addition, under the same natural smoke vent area, the pressure in the stage with a fire curtain was lower than that without a fire curtain.

Multivariate Analysis among Leaf/Smoke Components and Sensory Properties about Tobacco Leaves Blending Ratio

  • Lee Seung-Yong;Lee Whan-Woo;Lee Kyung-Ku;Kim Young-Hoh
    • Journal of the Korean Society of Tobacco Science
    • /
    • v.27 no.1 s.53
    • /
    • pp.141-152
    • /
    • 2005
  • This study focused on the relationships among leaf and smoke components and sensory properties following tobacco leaf blending. A completely randomized experimental design was used to evaluate components of leaf and smoke and sensory properties for sample cigarettes with four mixtures of flue cured and burley tobacco (40:60, 60:40, 80:20 and 100:0). Eleven leaf components, six smoke components, and eight sensory properties of smoking taste were analyzed. A sensory evaluation method known as quantitative descriptive analysis was used to evaluate perceptual strength on a fifteen score scale. Raw data from ten trained panelists were obtained and statistically analyzed. Based on the MANOVA, clustering analysis, correlation matrix and partial least square (PLS) method were applied to find out which smoke component most affected sensory properties. The PLS method was used to remove the influence between explanatory variables in the leaf, smoke components derived from the results. High correlations (p<0.0l) were found among ten specific leaf and smoke components and sensory attributes. Total nitrogen, ammonia, total volatile base, and nitrate in the leaf were significantly correlated (p<0.05) with impact, bitterness, tobacco taste, irritation, smoke volume, and smoke pungency. From the results of PLS analysis, influence variables are used to explain about the correlation. In terms of bitterness, with only two explanatory variables, Leaf $NO_3$ and Leaf crude fiber were enough for guessing their correlation. In the distance weighted least square fitting analysis, carbon monoxide highly influenced bitterness, hay like taste, and smoke volume.

A Study on the Characteristics of Smoke Control using PIV in Tunnel Fires (터널내 화재시 PIV를 이용한 연기제어 특성에 관한 연구)

  • Ko, Jae-Woong;Kim, Jong-Yoon;Seo, Tae-Beom;Lim, Kyung-Bum;Rie, Dong-Ho
    • Journal of the Korean Society of Safety
    • /
    • v.21 no.5 s.77
    • /
    • pp.6-11
    • /
    • 2006
  • This study aims to measure a smoke density and velocity by using the PIV method in case a fire occurs in tunnels. By doing so, this will estimate a critical velocity, examine its appropriateness, and present the basic materials necessary for designing a smoke control equipment. For this study, a visualization test was conducted based on the 1/20 miniature of a real tunnel according to the Froude scaling. As a part of basic experiments, a correlation between smoke density and brightness was analyzed here, and a critical velocity was estimated on the condition that a fire breaks out in tunnels. As a result, this study finds that there is a correlation between smoke density and brightness within a range of 100% to 30% transmittance, from which a quantitative smoke density can be obtained. The study also suggests that a critical velocity calculated from the Kennedy formula shows about 10% difference from that estimated in the test.

A Study on the Application of Fire Protection Facilities in Large Enclosure Gymnasium (대규모 실내경기장의 소방방재설비 적용현황 분석)

  • Choi, Dong-Ho;Kim, Choon-Dong;Yang, Jeong-Hoon;Cho, Young-Hum
    • Journal of Korean Association for Spatial Structures
    • /
    • v.10 no.2
    • /
    • pp.135-145
    • /
    • 2010
  • The objective of this study is to draw basic data for the application of the fire protection planning for the future plan large enclosure buildings in Korea through an analysis of its characteristics by case studies of the domestic and foreign large scale gymnasiums. In this study, domestic building codes for the fire protection are investigated and fire detection systems, fire extinguishing systems, smoke control systems and evacuation systems of three large scale gymnasiums located at Korea and eight foreign countries are compared and analyzed. The results of this study show that infrared light fire detection system and flame detector for spacial characteristics are potentially used in fire protection systems of large scale gymnasiums: dry type sprinkler and sprinkler water gun are adopted in fire detection system; and smoke accumulation system is widely utilized in smoke control system.

  • PDF

Development of a Computer Program to Evaluate Smoke Volume Flow rate and Temperature for Tunnel Fires (터널 화재시 연기발생량 및 온도 예측 프로그램 개발)

  • Park, Won-Hee
    • Journal of the Korean Society for Railway
    • /
    • v.10 no.5
    • /
    • pp.506-510
    • /
    • 2007
  • Smoke temperature and volume flow rate in a tunnel fire are calculated. To obtain realistic results, enthalpy of smoke which composites combustion gases and entrainment air is calculated from curvefit polynomials by temperature. A user-friendly computer program for them is also developed. This program might be used for a good engineering tool in design of fire safety and mock/reduced-scale fire tests in a tunnel.

An Experimental Study of Smoke Movement in Tunnel Fires with Natural Ventilation (터널 화재시 자연 배기에 의한 연기 거동에 관한 실험적 연구)

  • 이성룡;김충익;유홍선
    • Fire Science and Engineering
    • /
    • v.15 no.1
    • /
    • pp.1-6
    • /
    • 2001
  • In this study, reduced-scale experiments were conducted to understand smoke movements in tunnel fires with the natural ventilation. The 1/20 scale experiments were conducted under the Froude scaling since the smoke movement in tunnels is governed by buoyancy force. Three cases of experiments, in which a natural vent location varied from 1 m, 2 m and 3 m from the fire source symmetrically, were conducted in order to evaluate the effect of the position of ventilation systems on smoke movement. In case of a poo1 whose diameter is 4.36 cm, the temperature of smoke layer passed through the vent was maintained 7~$8^{\circ}c$ less than that of smoke layer without a vent. In case of a pool whose diameter is 5.23 cm, the average velocity passed through the vent was decreased when it was close to the fire source. And the maximum delay time was 3.86s. In CASE 1, the ceiling temperature was decreased by approximately 8$^{\circ}C$ and the vertical temperature was decreased by approximately $7^{\circ}c$. In CASE 2, both ceiling and vertical temperature wert decreased by $3^{\circ}c$ and in CASE 3, they were decreased by $2^{\circ}c$ each. It was confirmed that the thickness of smoke layer was maintained uniformly under the 25% height of tunnel through the visualized smoke flow by a laser sheet and the digital camcoder.

  • PDF

Smoke Characteristics of a Small Scale Pool Eire (작은 풀화재에서의 연기 특성)

  • Lee Eui-Ju;Ahn Chan-Sol;Shin Hyun-Joon;Oh Kwang-Chul;Lee Uen-Do
    • Fire Science and Engineering
    • /
    • v.19 no.3 s.59
    • /
    • pp.58-63
    • /
    • 2005
  • Experimental measurements of flames and the product properties were performed for small kerosene pool fires. which is widely used as a fire source of laboratory scale experiments with scaling modeling. The flame length and flickering frequency were investigated for the flame structures, and compared with the theory. Three measurement methods were introduced to clarify the smoke characteristics, i.e. various gas concentrations, smoke density and thermophoretic sampling with transmission electron microscopy (TEM). The yield of carbon dioxide and the consumption of oxygen were proportional to the heat release rate of pool fires, but there is no trend on carbon monoxide emission. Smoke density of turbulent flames was exponentially increased with the heat release rate. The morphology of the soot particle was investigated to address the degree of soot maturing. The results show that the similar smoke morphology between an inverse jet flame and a pool fire exists despite of different combustion controlling mechanisms.

Reduced-Scale Experiments of the Partial Smoke Extraction System in Tunnel Fires (풀화재를 이용한 터널화재 부분배연 모델실험)

  • Lee, Eui-Ju;Yoo, Yong-Ho
    • Fire Science and Engineering
    • /
    • v.20 no.4 s.64
    • /
    • pp.58-64
    • /
    • 2006
  • Smoke extraction in tunnel fire is investigated experimently with thermal model. The object is a immersed tunnel, of which the partial extraction system exists between the tubes. The model tunnel is measured 12 m long, 0.5 m wide and 0.35 m high. The fire is simulated to pool fire and the size corresponds to full scale fire of 5 MW based on Froude modeling. The performance of partial extraction system is determined under two ventilations, natural and longitudinal ones. The results show that compared with longitudinal ventilation, the smoke extraction efficiency of natural ventilation is increased about 30% because of smoke stratification in tunnel. Also the efficiency is identical to the iso-thermal model. The results will be help for activation of the ventilation system in emergency such as in the event of tunnel fires.