직류급전시스템에서의 귀환전류 변화비를 이용한 표유전류 실시간 감시기법에 관한 연구 (A Study on the Real Time Measuring Technique of Stray Current by Using Return Current Ratio in the DC Railway System)

  • 정호성;박영;김형철;민명환;신명철
    • 전기학회논문지
    • /
    • 제60권4호
    • /
    • pp.892-898
    • /
    • 2011
  • In DC electric railways, while an electric rail car is driving, a part of the working current returned to the substation through rails leaks into the ground. Such a stray current causes railway facilities and metal objects to corrode electrolytically. Therefore, change of stray current needs to be monitored constantly. But so far in domestic, the research on stray current measuring techniques and system adaption are insufficient. To estimate stray current, this paper addresses a method of monitoring the return current that is returned into the negative pole of the substation in real time.

비접지 DC 급전시스템에서의 Delta-I 지락보호계전 시스템 (Development of Delta-I ground fault Protective Relaying Scheme for DC Traction Power Supply System)

  • 정상기;권삼영;정호성;김주락
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제55권12호
    • /
    • pp.529-535
    • /
    • 2006
  • In DC tracking power supply system, ground faults are currently detected by the potential relay, 64P. Though 64P relay detects ground fault, it cannot identify the faulted region which causes long traffic delays and safety problem to passengers. A new ground fault protective relay scheme, ${\Delta}I$ ground fault protective relay, that can identify the faulted region is presented in this paper. In ${\Delta}I$ ground fault protective relaying scheme, ground fault is detected by 59, overvoltage relay, which operates ground switch installed between the negative bus and the ground. It preliminarily chooses the faulted feeder after comparing the current increases among feeders and trips the corresponding feeder breaker. After some time delay, it then recloses the breaker if it finds the preselected feeder is not the actual faulted feeder. Whether or not the preselected feeder is the actual faulted feeder is determined by checking the breaker trip status in the neighboring substation in the direction of the tripped breaker. If the corresponding breaker in the neighboring substation is also tripped, it finally judges the preselected feeder is actually a faulted feeder. Otherwise it recloses the tripped breaker. Its algorithms is presented and verified by EMTP simulation.

직류 방전과 펄스 직류 방전에 의한 플라즈마 형상 관찰 (Observation of Plasma Shape by Continuous dc and Pulsed dc)

  • 양원균;주정훈
    • 한국표면공학회지
    • /
    • 제42권3호
    • /
    • pp.133-138
    • /
    • 2009
  • Effects of bipolar pulse driving frequency between 50 kHz and 250 kHz on the discharge shapes were analyzed by measuring plasma characteristics by OES (Optical Emission Spectroscopy) and Langmuir probe. Plasma characteristics were modeled by a simple electric field analysis and fluid plasma modeling. Discharge shapes by a continuous dc and bipolar pulsed dc were different as a dome-type and a vertical column-type at the cathode. From OES, the intensity of 811.5 nm wavelength, the one of the main peaks of Ar, decreased to about 43% from a continuous dc to 100 kHz. For increasing from 100 kHz to 250 kHz, the intensity of 811.5 nm wavelength also decreased by 46%. The electron density decreased by 74% and the electron temperature increased by 36% at the specific position due to the smaller and denser discharge shape for increasing pulse frequency. Through the numerical analysis, the negative glow shape of a continuous dc were similar to the electric potential distribution by FEM (Finite Element Method). For the bipolar pulsed dc, we found that the electron temperature increased to maximum 10 eV due to the voltage spikes by the fast electron acceleration generated in pre-sheath. This may induce the electrons and ions from plasma to increase the energetic substrate bombardment for the dense thin film growth.

직류전기철도 전식대책 실증실험(2) 속응형 정전위 정류기 (Field Test of Mitigation Methods for Stray Currents from DC Electric Railroad(2) Rapid Potential-Controlled Rectifier)

  • 하윤철;하태현;배정효;이현구;김대경;최정희
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2007년도 추계학술대회 논문집 전기기기 및 에너지변환시스템부문
    • /
    • pp.217-219
    • /
    • 2007
  • With the wide spread of direct current(DC) electric railroads in Korea, the stray current or leakage currents from negative return rails become a pending problem to the safety of nearby underground Infrastructures. The most widely used mitigation method for this interference is the stray current drainage method, which connects the underground metallic structures to the rails with diodes (polarized drainage) or thyristor (forced drainage). This method, however, inherently possesses some drawbacks such as an increase of total leakage torrents from rails, expansion of interference zone, etc. In order to resolve these drawbacks, we developed a rapid potential-controled rectifier and applied to a depot area where stray current inference is very severe. The effect of this method was analyzed from the field tell data and we suggest this method can be an excellent alternative to the drainage-bond-based mitigation methods.

  • PDF

펄스 플라즈마에 의한 나노입자 제조 시 하전이 입자의 포집에 미치는 영향 (Effect of Charging on Particle Collection during Synthesis of Nanoparticles by Pulse Plasma)

  • 김광수;김태성
    • 대한기계학회:학술대회논문집
    • /
    • 대한기계학회 2007년도 춘계학술대회A
    • /
    • pp.210-214
    • /
    • 2007
  • Silicon nanoparticles are widely studied as a material with great potential for wide applications. For application to present industry, it should be easy to control the characteristics of nanoparticle including the size and structure. In this paper, we investigated the formation of Si nanoparticle using pulse plasma technology. Plasma technology is already quite common in device industry and the size of nanoparticle can be easily controlled according to plasma pulse duration. An inductively-coupled plasma chamber with RF power (13.56 MHz) was used with DC-biased grid $(-200\sim+200\;V)$ installed above the substrate. In order to measure the shape and size of nanoparticle, TEM was used. It was found that the size of nanoparticles can be controlled well with the plasma pulse duration and the collection efficiency is increased with the use of either negative or positive DC-bias.

  • PDF

지뢰탐지를 위한 ECR 플라즈마에서 타깃에 고전압 DC 펄스 인가시 전압-전류 특성 분석 (I-V Characteristics of Negatively DC Pulsed Target in ECR Plasma for Landmine Detection)

  • 김성봉;이희재;박승일;유석재;조무현;한승훈;임병옥
    • 한국표면공학회지
    • /
    • 제47권1호
    • /
    • pp.53-56
    • /
    • 2014
  • I-V characteristics of a cylindrical target in an ECR plasma were studied for sheath spatial evolutions when the target was pulsed biased to a high negative potential. The magnetic field effects on sheath thickness and sheath boundary speed were investigated by comparison between the experimental results and the theoretical results using the Child-Langmuir sheath model. The results showed that the magnetic field suppressed electron motion away from the target so that sheath thickness and sheath boundary speed decreased.

주조용 Al합금의 내식성에 관한 전기화학적 평가 (An Electrochemical Evaluation on the Corrosion Resistance of a Al Alloy)

  • 윤대현;이명훈;김기준;문경만
    • Journal of Advanced Marine Engineering and Technology
    • /
    • 제29권5호
    • /
    • pp.495-501
    • /
    • 2005
  • Al is a active metal that owes its resistance to a thin, protective, barrier oxide surface layer, which is stable in air and neutral aqueous solution. Thus Al alloys are widely used in architectural trim. cold & hot-water storage vessels and piping. However Al and most of its alloy may corrode with some forms such as pitting corrosion, intergranular corrosion and galvanic corrosion in the case of exposure to various industrial and marine atmosphere. Therefore a correct evaluation of corrosion resistance for their Al and Al alloys may be more important in a economical point of view. In this study. a relative evaluation of corrosion resistance for three kinds of Al alloys such as ALDC2, ALDC3, and ALDC8 series was carried out with electrochemical method. There is a tendency that corrosion potential is shifted to positive or negative direction by alloying components regardless of corrosion resistance. Moreover the data of corrosion properties obtained from cathodic Polarization curve, cyclic voltammogram and AC. DC impedance respectively showed a good correspondence each other against the corrosion resistance but variation of corrosion potential. passivity current density of anodic polarization curve and corrosion current density by Tafel extrapolation and Stern-Geary method didn't correspond with not only each other but also considerably the data of corrosion properties discussed above. Therefore it is suggested that an optimum electrochemical evaluation for corrosion resistance of Al alloy is to calculate the diffusion limiting current density of cathodic polarization curve, impedance of AC or DC and polarization resistance of cyclic voltammogram.

직류전기철도 전식대책 실증실험(1) 누설전류 배류시스템 (Field Test of Mitigation Methods for Stray Currents from DC Electric Railroad(1) Stray Current Drainage System)

  • 하윤철;배정효;하태현;이현구;김대경;최정희
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2007년도 추계학술대회 논문집 전기기기 및 에너지변환시스템부문
    • /
    • pp.220-222
    • /
    • 2007
  • With the wide spread of direct current (DC) electric railroads in Korea, the stray currents or leakage currents from negative return rails become a pending problem to the safety of nearby underground infrastructures. The most widely used mitigation method for this interference is the stray current drainage method, which connects the underground metallic structures to the rails with diodes (polarized drainage) or thyristor (forced drainage). Although this method inherently possesses some drawbacks, its cost effectiveness and efficiency to protect the interfered structures has been the main reason for the wide adoption. In this paper, we show the field test results for the application of stray current drainage system to a city gas pipeline paralleling a depot area of a metropolitan rapid transit system. The process for optimal positioning is briefly illustrated. The effectiveness of constant voltage, constant current, and constant potential drainage schemes was also described.

  • PDF

CCD Image Sensor with Variable Reset Operation

  • Park, Sang-Sik;Uh, Hyung-Soo
    • JSTS:Journal of Semiconductor Technology and Science
    • /
    • 제3권2호
    • /
    • pp.83-88
    • /
    • 2003
  • The reset operation of a CCD image sensor was improved using charge trapping of a MOS structure to realize a loe voltage driving. A DC bias generating circuit was added to the reset structure which sets reference voltage and holds the signal charge to be detected. The generated DC bias is added to the reset pulse to give an optimized voltage margin to the reset operation, and is controlled by adjustment of the threshold voltage of a MOS transistor in the circuit. By the pulse-type stress voltage applied to the gate, the electrons and holes were injected to the gate dielectrics, and the threshold voltage could be adjusted ranging from 0.2V to 5.5V, which is suitable for controlling the incomplete reset operation due to the process variation. The charges trapped in the silicon nitride lead to the positive and negative shift of the threshold voltage, and this phenomenon is explained by Poole-Frenkel conduction and Fowler-Nordheim conduction. A CCD image sensor with $492(H){\;}{\times}{\;}510(V)$ pixels adopting this structure showed complete reset operation with the driving voltage of 3.0V. The resolution chart taken with the image sensor shows no image flow to the illumination of 30 lux, even in the driving voltage of 3.0V.

지하철 직류 급전시스템의 표유전류 실태 분석(II) 부산 지역 (Analysis of the Stray Current Conditions in Subway DC Electrification System (II) Busan Metropolitan Area)

  • 하윤철;하태현;배정효;김대경;이현구
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2004년도 하계학술대회 논문집 B
    • /
    • pp.1367-1369
    • /
    • 2004
  • When an underground pipeline runs parallel with subway DC electrification system, it suffers from stray current corrosion caused by the stray current from the rails negative returns. Perforation due to the stray current corrosion may bring about disastrous accidents such even in cathodically protected systems. Traditionally, bonding methods such as direct drainage, polarized drainage and forced drainage have been used in order to mitigate the damage on pipelines. In particular, the forced drainage method is widely adopted in Busan. In this paper, we report the real-time measurement data of the pipe-to-soil potential variation in the presence and absence of the IR compensation. The drainage current variation was also measured using the Stray Current Logger developed. By analyzing them, the problems of current countermeasures for stray current corrosion are discussed.