• Title/Summary/Keyword: main control room(MCR) simulator

Search Result 10, Processing Time 0.024 seconds

Fire Simulations for the Abandonment Risk Assessment of Main Control Room Fire in Domestic Nuclear Power Plant (국내 원자력발전소의 주제어실 화재 피난 리스크 평가를 위한 화재 시뮬레이션)

  • Kang, Dae Il;Kim, Kilyoo;Jang, Seung-Cheol;Yoo, Seong Yeon
    • Journal of the Korean Society of Safety
    • /
    • v.29 no.4
    • /
    • pp.199-207
    • /
    • 2014
  • In this paper, to systematically assess the abandonment risk of main control room (MCR) fire, fire simulations with Fire Dynamics Simulator were performed and abandonment probabilities were estimated for the MCR bench-board fire of domestic reference nuclear power plant. The fire simulation scenarios performed in this study included propagating and non-propagating fires of the MCR bench-board, and the availability and unavailability of heating, ventilation, and air conditioning system (HVACS). The following results were obtained. First, temperature was the major abandonment impact factor for the MCR bench-board fire if the HVACS was available and optical density was that if the HVACS was unavailable. Second, the fire scenario contributing the MCR bench-board fire abandonment risk was identified to be only the propagating fire. Third, it was confirmed that the abandonment probability of the MCR bench-board fire for domestic reference nuclear power plant could be reduced by using the fire modeling.

Effectiveness of Crew Resource Management Training Program for Operators in the APR-1400 Main Control Room Simulator (국내 원자력발전소 첨단 주제어실의 Crew Resource Management 교육훈련 효과 분석)

  • Kim, Sa-Kil;Byun, Seong-Nam;Lee, Dhong-Hoon;Jeong, Choong-Heui
    • IE interfaces
    • /
    • v.22 no.2
    • /
    • pp.104-115
    • /
    • 2009
  • The objective of the study is to evaluate the effectiveness of Crew Resource Management (CRM) training program for operators in the Main Control Room (MCR) simulator of APR-1400 Nuclear Power Plant. The experiments were conducted for two different crews of operators performing six different emergency operating scenarios during four-week period. Each crew consisted of the five operators: senior reactor operator, safety technical advisor, reactor operator, turbine operator, and electric operator. All crews (Crew A and B) participated in the training program for the technical knowledge and skills which were required to operate the simulator of the MCR during the first week. To verify the effectiveness of the CRM training program; however, only Crew A was selected to attend the CRM training after the technical knowledge and skills training. The results of the experiments showed that the CRM training program improved the individual attitudes of Crew A significantly. Team skills of Crew A were found to be significantly better than those of Crew B. The CRM training did not have positive effects on enhancing the individual performance of Crew A; however, as compared to that of Crew B. Implication of these findings was discussed further in detail.

The Development of Full-Scope Replica Type Simulator for PWR Nuclear Power Plants (가압경수로 원자력 발전소의 전범위 복제형 시뮬레이터 개발)

  • 이중근
    • Journal of the Korea Society for Simulation
    • /
    • v.6 no.1
    • /
    • pp.85-96
    • /
    • 1997
  • Designing and constructing a proper simulator for real power plants requires extensive research in human engineering and computer science and integration of different fields of technologies such as system analysis, operational knowledge for nuclear plant, etc. A full scope replica type simulator for nuclear power plant is developed. The simulator has the same feature and operational functions as one in the main control room (MCR) of a reference power plant. The simulator provides the necessary training to recover or reduce damages from accidents that usually are unpredictable. This paper describes the configurations and characteristics for the simulator that is developed for Younggwang Nuclear Power Plant #3,4 which is the basic model of the Korean Nuclear Power Plant. The paper also describes technical aspects of Auto Code Generator that is used for developing the simulator. The successful development of the simulator will contribute to improve safety in operation of nuclear power plants.

  • PDF

Modeling and simulation of foxboro control system for YGN#3,4 power plant (영광 3,4호기 Foxboro 제어시스템 모델링 및 시뮬레이션)

  • 김동욱;이용관;유한성
    • 제어로봇시스템학회:학술대회논문집
    • /
    • 1997.10a
    • /
    • pp.179-182
    • /
    • 1997
  • In a training simulator for power plant, operator's action in the MCR(Main Control Room) are given to plant process and computer system model as an inputs, and the same response as in real power plant is provided in real time. Inter-process communication and synchronization are especially important among various inputs. In the plant simulator, to simulate the digital control system such as FOXBORO SPEC-200 Micro control system, modification and adaptation of control card(CCC) and its continuous display station(CDS) is necessary. This paper describes the modeling and simulation of FOXBORO SPEC-200 Micro control system applied to Younggwang nuclear power plant unit #3 & 4, and its integration process to the full-scope replica type training simulator. In a simulator, display station like CDS of FOXBORO SPEC-200 Micro control system is classified as ITI(Intelligent Type Instrument), which has a micro processor inside to process information and the corresponding alphanumeric display, and the stimulation of ITI limits the important functions in a training simulator such as backtrack, replay, freeze and IC reset. Therefore, to achieve the better performance of the simulator, modification of CDS and special firmware is developed to simulate the FOXBORO SPEC-200 Micro control system. Each control function inside control card is modeled and simulated in generic approach to accept the plant data and control parameter conveniently, and debugging algorithms are applied for massive coding developed in short period.

  • PDF

The development of full-scope replica simulator for variable supercritical pressure once-through fossil power plants (변압 관류형 초임계압 화력발전소 전범위 시뮬레이터 개발)

  • Lee, Jung-Kun;Ahn, Yeon-Shik;Jung, Hoon;Lee, Yong-Kwan;Han, Byoung-Sung
    • Journal of Institute of Control, Robotics and Systems
    • /
    • v.4 no.3
    • /
    • pp.392-399
    • /
    • 1998
  • A full-scope replica type simulator whose MCR(main control room) has the same features and operation functions as MCR of the reference power plant has been developed for a fossil power plant. This simulator was developed with the model of Poryung Fossil Power Plant #3,4 which is the standard model of the Korean fossil power plant. It is the first localized simulator for the supercritical, variable boiler pressure type fossil power plant. The simulator provides various kinds of accidents which are in normal plant operation and thus enables operators to recover or reduce possible damages. To design and develop this kind of simulator, we need to integrate high technologies such as system analysis, plant operation and system integration of mechanics, physics, computer science. CASE(Computer Aided Software Engineering) tools were used to develop the dynamic model. This simulator will greatly contribute to the improvement of the safety and efficiency of the fossil power plant by implementing operator training. In this paper, the outline of software and hardware configuration and characteristics of the simulator are described, and the results of 30%, 50%, 75%, 100% load operation test will be discussed.

  • PDF

Simulation of Intelligent Type Instrument For Power Plant Simulator (발전소 시뮬레이터를 위한 지능형계기의 시뮬레이션)

  • Kim, Dong-Wook
    • Proceedings of the KIEE Conference
    • /
    • 1999.07b
    • /
    • pp.686-689
    • /
    • 1999
  • 발전소 운전원 훈련용 시뮬레이터는 중앙제어실(MCR:Main Control Room) 운전원의 운전결과가 실시간 운영체계하에 발전소 프로세스 모델 및 컴퓨터 시스템과 통합되어 실제 발전소와 같은 반응을 운전원에게 제공하여야 한다. 따라서 시뮬레이터에는 프로세스의 동특성 이외에도 제어시스템의 모델링 및 운전원과 인터페이스되는 제어기들이 실제적으로 구성되어야하며, 이들 제어기와 컴퓨터시스템간 다양한 입력간의 통신 및 동기(Synchronization)가 중요하다. 본 논문에서는 원자력 발전소 시뮬레이터에서 쓰이는 지능형 계기(Intelligent Type Instrument)로 분류된 기기를 살펴보고 시뮬레이션을 위해 개발 구현된 방법들을 기술하고자한다.

  • PDF

Data Transporting between Dynamic Model and Display Model of Power Plant Simulator (발전소 시뮬레이터의 다이나믹 모델과 디스플레이 모델간 데이터전송)

  • 김동욱
    • Proceedings of the Korea Society for Simulation Conference
    • /
    • 1998.03a
    • /
    • pp.86-90
    • /
    • 1998
  • The safety and reliability of nuclear power plant operations relies heavily on the plant operators ability to respond to various emergency situations. It has become standard industry practice to utilize simulators to improve the safety and reliability of nuclear power plants operations. The simulators built for Younggwang#3,4, which is the basic model of the Korean Nuclear Power Plant design, has been developed precisely for this purpose. Dynamic Model and Display Model are developed under US3(UNIX Simulation Software Support System) environment in simulator for Younggwang#3,4. Since these two models are developed under each own operating system, it is necessary to develop a method for transporting data between these two systems. This paper descirves communication environment between Dynamic Model and Display Model, and addresses a file generation method for the Display Model, which will be necessary for designing MMI of MCR(Main Control Room) in the furture.

  • PDF

The effect of communication quality on team performance in digital main control room operations

  • Kim, HyungJun;Kim, Seunghwan;Park, Jinkyun;Lee, Eun-Chan;Lee, Seung Jun
    • Nuclear Engineering and Technology
    • /
    • v.52 no.6
    • /
    • pp.1180-1187
    • /
    • 2020
  • A team of operators is required for nuclear power plant operation, and communication between the operators is an important aspect of the team's ability to successfully carry out tasks. It has been difficult to evaluate the quality of this communication though, and as the relationship between communication quality and team performance has yet to be clarified, it has not been applied to most human reliability analysis (HRA) methodologies. This study investigates the relationship between the quality of communication and team performance using data from a full-scope training simulator of a digital main control room (MCR). Two important characteristics of communication were considered to determine quality: each operator's ability to self-confirm the status of a given task in a digital MCR, and the type of communication, as divided into 1-way, 2-way, and 3-way between operators. To measure team performance, the concept of an unsafe act was employed, which is defined as a human error that has the potential to negatively affect plant safety. Analysis results showed that the communication quality and team performance were related to each other. With this more clearly defined relationship, the results of this study can be applied to related performance shaping factors to improve HRA.

A Study on Construction and Application of Nuclear Grade ESF ACS Simulator (원자력등급 ESF 공기정화계통 시뮬레이터 제작 및 활용에 관한 연구)

  • Lee, Sook-Kyung;Kim, Kwang-Sin;Sohn, Soon-Hwan;Song, Kyu-Min;Lee, Kei-Woo;Park, Jeong-Seo;Hong, Soon-Joon;Kang, Sun-Haeng
    • Journal of Nuclear Fuel Cycle and Waste Technology(JNFCWT)
    • /
    • v.8 no.4
    • /
    • pp.319-327
    • /
    • 2010
  • A nuclear plant ESF ACS simulator was designed, built, and verified to perform experiment related to ESF ACS of nuclear power plants. The dimension of 3D CAD model was based on drawings of the main control room(MCR) of Yonggwang units 5 and 6. The CFD analysis was performed based on the measurement of the actual flow rate of ESF ACS. The air flowing in ACS was assumed to have $30^{\circ}C$ and uniform flow. The flow rate across the HEPA filter was estimated to be 1.83 m/s based on the MCR ACS flow rate of 12,986 CFM and HEPA filter area of 9 filters having effective area of $610{\times}610mm^2$ each. When MCR ACS was modeled, air flow blocking filter frames were considered for better simulation of the real ACS. In CFD analysis, the air flow rate in the lower part of the active carbon adsorber was simulated separately at higher than 7 m/s to reflect the measured value of 8 m/s. Through the CFD analyses of the ACSes of fuel building emergency ventilation system, emergency core cooling system equipment room ventilation cleanup system, it was confirmed that all three EFS ACSes can be simulated by controlling the flow rate of the simulator. After the CFD analysis, the simulator was built in nuclear grade and its reliability was verified through air flow distribution tests before it was used in main tests. The verification result showed that distribution of the internal flow was uniform except near the filter frames when medium filter was installed. The simulator was used in the tests to confirm the revised contents in Reg. Guide 1.52 (Rev. 3).

Research of KNPEC-2 Simulator Upgrade(I) (원자력 교육원 #2 시뮬레이션 성능개선에 관한 연구(I))

  • 유현주
    • Proceedings of the KIPE Conference
    • /
    • 2000.07a
    • /
    • pp.249-252
    • /
    • 2000
  • 원자력 교육원 #2(KNPEC-2) 시뮬레이터는 1980년도 중반에 웨스팅하우스에 의해 공급되어 계속 사용되어 오다가 현재 성능개선 연구가 진행 중이다. 이번 성능개선을 통해 기존의 컴퓨터 시스템(Gould MPX)와 소프트웨어의 전면 교체가 이루어지고 있으며 최적 계산 코드를 이용한 실시간 열수력 모델 (ARTS; Advanced Real-Time Thermal-Hydraulics Simulation) 개발 , 2-Group 3D 실시간 노심모델(REMARK ; REal Time Multigroup Advanced Reactor Kinetics)를 이용한 노심 주기개선 (Cycle Update) 가상현실 기술 등을 이용한 컴퓨터 교육지원 시스템(CATS: Computer Assister Training System)등 새로운 시도가 이루어지고 있으며 본 논문은 이러한 새로운 시도가 이루어지고 있으며 본 논문은 이러한 새로운 시도들 및 그 결과에 대해 기술하고 있다. 기준발전소(Reference Plant)인 영광 1호기 12주기의 노심모델로 주기개선(Cycle Update)을 위한 REMARK의 입력자료 생성을 위해 핵설계 전산체계인 APA(ALPHA-PHOENIX-ANC) 시스템의 출력으로부터 자동으로 REMARK 입력데이타를 생성하기 위한 GUI툴 개발하였다. 또 이를 이용하여 개발된 노심모델은 최적계산코드(RETRAn 3D) 의 열수력 해법을 이용하여 개발된 NSSS 열수력코드(ARTS) 와 결합(Integration) 되어 안정 및 과도 상태 시험에 사용되었으며 원자로 냉각재 펌프 정지등의 몇 가지 과도 시험 계산결과 기존 해석 결과와 잘 일치하였다 중앙제어실(MCR; Main Control Room)내의 운전원 행동만 훈련하도록 되어있는 기존시뮬레이터의 한계를 극복하기 위해 가상현실 (VR) 저작도구를 이용한 발전소 현장 내부를 표현하는 가상발전소 (Virtual Plant) 발전소 현장에 소재하여 기존 시뮬레이터의 모의한계 밖에 있던 패널을 표현한 가상판넬(Virtual Panel)등과 강의실에서 발전소 모의 훈련을 가능케 하기 위해 가상현실 기술을 이용한 컴퓨터 지원 교육훈력 시스템(CATS ; Computer Assister Training System)을 개발 중이며 일부 개발부분을 소개하였다.

  • PDF