• 제목/요약/키워드: line discharge

검색결과 529건 처리시간 0.025초

사축식 액셜 피스톤 펌프의 압력맥동 감소 (Reduction in Pressure Ripples for a Bent-Axis Piston Pump)

  • 김경훈;손권;장주섭
    • 한국자동차공학회논문집
    • /
    • 제12권2호
    • /
    • pp.109-116
    • /
    • 2004
  • Bent-axis piston pump have been commonly used in hydraulic systems because of high pressure level, best efficiency, low shear force on pistons and low operating costs. The other side, they have a few demerits like that they have the relatively high number of moving parts and more discharge pressure ripples. Especially, the discharge pressure ripples bring about vibrations and noises in hydraulic system components such as connecting pipes and control valves, so that these deteriorate the stability and accuracy of the systems. Therefore, the hydraulic systems having the bent-axis piston pump require the methods to reduce the discharge pressure ripples. So, the purpose of this paper is to reduce the discharge pressure ripples by the phase interference of pressure wave and to develope the analysis model of the pumps to predict the discharge pressure ripples. In this paper, the analysis model of the bent-axis piston pump was developed using the AMESim software, and the reliability of that was verified by the comparison with the experimental results. The hydraulic pipeline with a parallel line was used as the method to generate the phase interference of pressure wave. the dynamics characteristics of the hydraulic pipeline with a parallel line were analyzed by a transfer matrix method. the usefulness of the phase interference of pressure wave was investigated through the experiment and simulation. The results from the experiment and simulation said that the phase interference of pressure wave by the hydraulic pipeline with a parallel line could reduce the discharge pressure wave of the pump well. The analysis model of the bent-axis piston pump developed in this paper and the method of the phase interference by the hydraulic pipeline with a parallel line are expected to be helpful to achieve the design of the pump and to reduce the discharge pressure wave of the pump effectively.

가스터빈 발전기 고정자 권선의 절연상태 평가 (Assessment of Insulation Condition in Gas Turbine Generator Stator Windings)

  • 김희동;양규현;주영호
    • 전기학회논문지
    • /
    • 제59권8호
    • /
    • pp.1423-1428
    • /
    • 2010
  • The results of off-line and on-line diagnostic tests performed on the stator winding of an air-cooled gas turbine(G/T) generator are reported in this paper. Off-line diagnostic tests included measurements of the ac current, dissipation factor(tan${\delta}$), and partial discharge(PD). Six epoxy-mica capacitors were installed in the three phases of G/T generator for performing on-line diagnostic testing with the turbine generator analyzer(TGA). The TGA showed that the normalized quantity number(NQN) and the PD magnitude($Q_m$) were high in phase A of the stator winding. Internal discharges were generated in phases B and C, and slot discharge occurred in phase A. According to the trend analyses of the NQN and $Q_m$ values available for insulation condition assessment for G/T generator stator windings, it was concluded that phases B and C were in good condition, whereas phase A has been significantly deteriorated.

고압 전동기 고정자 권선의 절연진단을 위한 운전중 부분방전 측정기법 (On-Line Partial Discharge Detecting Method for Insulation Diagnosis of High-Voltage Motor Stator Windings)

  • 황돈하;신병철;심우용;박도영;김용주;송상옥
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2001년도 하계학술대회 논문집 C
    • /
    • pp.1727-1729
    • /
    • 2001
  • Partial discharge testing are rapidly becoming the most powerful tool to assess the condition of high voltage generator and motor stator windings. Recently, on-line monitoring scheme with trending technique is widely applied in insulation diagnosis. This paper describes the on-line partial discharge detecting techniques in the high voltage motor stator windings. Also, on-line monitoring system for an insulation diagnosis are proposed.

  • PDF

대형발전기 고정자권선 절연재료의 열 사이클에 의한 열화에 관한 연구 (A study on the heat cycle aging of insulation materials in large generator stator windings)

  • 김희곤;박영관
    • 대한전기학회논문지
    • /
    • 제45권4호
    • /
    • pp.553-557
    • /
    • 1996
  • Heat cycle aging of insulating materials in large generator stator winding has been investigated using both on-line and off-line test methods. On this study, principally, off-line test against actual generator in service was carried out to acquire information about polarization index(PI) and dissipation factor, dissipation factor tip-up, maximum partial discharge for the purpose of remnant breakdown voltage and life assessment. It was found from the tests that both dissipation factor and maximum partial discharge decreased with the increase of operating hours and starting numbers. It was found from off-line tests that the remnant breakdown voltage had a strong relationship with both dissipation factor and maximum partial discharge the remnant breakdown voltage as a results of both operating hours and starting number and the nondestructive tests were proposed as parameters which can predict the remnant lifetime of insulating materials in large generator stator windings. (author). 8 refs., 8 figs., 2 tabs.

  • PDF

고압전동기 운전중 부분방전 감시 시스템 개발 (Development of On-Line Partial Discharge Monitoring System in High Voltage Motors)

  • 김희동;공태식;주영호
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2004년도 하계학술대회 논문집 Vol.5 No.2
    • /
    • pp.1175-1178
    • /
    • 2004
  • On-line partial discharge(PD) monitoring system has been developed to monitor in operating large motor stator insulations. This system makes use of remote diagnosis techniques for the evaluation of PD activity in the control center of thermal power plant. This system can be remotely accessed via a modem to build database, analyze status and interpret the pattern of PD activity. A personnel computer is generally connected to ten motors to continuous measurement of the PD activity. The test data can be easily interpreted by a maintenance staff. For assessing the condition of stator winding in motors, this system ensures a reliable measurement and accurate estimation. Capacitive couplers used for on-line PD measurement have been 80pF. The maximum PD magnitude(Qmax), PD pattern and normalized quantity number(NQN) were performed by this system.

  • PDF

UHF센서를 이용한 가스절연송전선로 절연파괴 위치 추정에 관한 연구 (A Study on Estimation of Breakdown Location using UHF Sensors for Gas Insulated Transmission Lines)

  • 박흥석;한상옥
    • 전기학회논문지
    • /
    • 제60권4호
    • /
    • pp.805-810
    • /
    • 2011
  • This paper deals with the method and algorithm used to find fault locations in gas insulated transmission line. The method uses UHF sensors and digital oscilloscope to detect discharge signals emitted to the outside through insulating spacer in the event of breakdown inside GIL. UHF sensors are the external type and installed at outside of insulating spacers of GIL. And we used wavelet signal processing to analyze the discharge signals and confirm the exact fault location findings in the GIL test line. This method can overcome demerit of TDR(Time Domain Reflectometer) method having been applied to detect fault location for conventional underground transmission lines, and Ground Fault Sensors used in conventional GIS systems. TDR method requires high level of specialty and experience in analyzing the measured signals. Ground fault sensors are installed inside GIL and can be destroyed by high transient voltage. This paper's method can simplify the fault location process and minimize the damage of sensors. In addition, this method can estimate the fault location only by the time difference when discharge signals are arrived to detecting sensors at the ends of GIL sections without reasons of breakdown. To test the performance of our method, we installed sensors at the ends of test line of GIL(84m) and sensed discharge signals occurred in GIL, energized with AC voltage generator up to 700kV.

고전압회전기 고정자권선 운전중 부분방전진단시스템의 현장적용사례 연구 (A Case Study of On-line PD Measuring System on the Stator Winding for High Voltage Rotating Machine)

  • 오봉근;강동식;임기조
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2010년도 하계학술대회 논문집
    • /
    • pp.109-109
    • /
    • 2010
  • On-line partial discharge(PD) diagnostic system is the most prominent systems to diagnose insulation condition for the high voltage rotating machines. Partial discharge measuring system(PDMS) series with ceramic coupler(PD detecting sensor) installed hydro generator and high voltage motor have been measured the PD data for many years. The trend of PD magnitude in the on-line PD system increased for some machines. These machines showed a same result in the conventional off-line PD test and PD magnitude decreased after stator winding insulation cleaning. This case study show that PDMS has been proved to be good results by comparing PD magnitude with on-line and off-line PD test and it is important to plan the maintenance project for the hydro generator stator winding because PD value was decreased after insulation cleaning.

  • PDF

수력 발전기의 운전중 부분방전 측정기법에 대한 신뢰성 평가 (Evaluation of On-Line Partial Discharge Measurement Techniques on Hydro-Generator)

  • 황돈하;김진봉;김용주;박명수;김택수
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1994년도 하계학술대회 논문집 C
    • /
    • pp.1526-1529
    • /
    • 1994
  • In hydro-generator, a groundwall insulation of stator windings gradually deteriorates due to mechanical, thermal, electrical and environmental stresses. These stresses combine to result in loose windings, delamination of the stator insulation and/or electrical tracking of the end winding, all of which can lead to stator insulation failures. Conventionally, off-line tests such as partial discharge measurement, DC/AC current test and ${\Delta}tan{\delta}$ test has been used for estimation of winding condition. However, off-line test requires large power supply and generator outage. In addition, major cause of insulation problems such as loose wedges and slot discharges may not be found with off-line diagnoses. This paper describes the on-line partial discharge measurement techniques in the generator stator windings. The experimental results from the UIAM #1 hydro-generator confirms a optimistic application of on-line generator diagnosis method as a reliable tool for evaluation of winding condition.

  • PDF

Implementation of an Inductively Coupled EM Probe System for PD Diagnosis

  • Kim, Hee-Dong;Park, Noh-Joon;Park, Dae-Hee
    • Journal of Electrical Engineering and Technology
    • /
    • 제6권1호
    • /
    • pp.111-118
    • /
    • 2011
  • In recent years, various types of partial discharge (PD) methods such as capacitive, inductive, electromagnetic, and acoustic coupling techniques have been developed for diagnosing rotating machines. An electromagnetic (EM) probe, which is an inductively coupled type of sensor, is required for detecting corona and internal discharges during off-line tests. In this study, a new technique for enhancing the measurement sensitivities for corona and internal discharge based on an EM inductive position sensor is proposed. An EM probe that winds wires around horseshoe-shaped and cylindershaped ferrites as helices is designed and optimized for the implementation of off-line PD monitoring of the stator winding of a rotating machine. The measurement system based on this design is implemented, and it is verified from the results of the experiment performed in this study that the probe provides similar performance as existing commercial products.

운전 중인 전력기기의 부분방전 측정장치 개발에 관하여 (Development of On-Line Patial Discharge Detector for Power)

  • 김광화;선종호;김우성;이종구;이준모;강창원
    • 한국철도학회:학술대회논문집
    • /
    • 한국철도학회 2000년도 추계학술대회 논문집
    • /
    • pp.733-739
    • /
    • 2000
  • This paper is described the development of on-line partial discharge detector for high voltage apparatus. This detector consists of acoustic and high frequency current sensors, amplifier part, A/D converter part, data communication part and computer. The contents of paper are characteristics of units and digital signal processing for reducing noise in partial discharge detection. We seek methods to do good digital signal processing for detection of partial discharge. We apply digital filtering methods to the elect Tic signal and a cross con-elation to the acoustic signal. This paper shows the characteristics of these filtering method and cross con-elation in partial discharge detection.

  • PDF