• 제목/요약/키워드: lightning surge current

검색결과 119건 처리시간 0.024초

비선형 소자 및 서지억제회로의 Pspice 시뮬레이션 (Pspice Simulation for Nonlinear Components and Surge Suppression Circuits)

  • 이복희;공영은;최원규;전덕규
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제49권8호
    • /
    • pp.477-486
    • /
    • 2000
  • This paper presents Pspice modeling methods for spark gaps and ZnO varistors and describes the application for the two-stage surge suppression circuit which was composed of the nonlinear components. The simulation modelings of nonlinear components were conducted on the basis of the voltage and current curves measured by the impulse current with the time-to-crest of $1~50 \mus$ and the impulse voltage with the rate of the time-to-crest of 10, 100 and 1000 V/\mus$. The firing voltages of the spark gap increased with increasing the rate of the time-to-crest of impulse voltage and the measured data were in good agreement with the simulated data. The I-V curves of the ZnO varistor were measured by applying the impulse currents of which time-to-crests range from 1 to $50 \mus$ and peak amplitudes from 10 A to 2 kA. The simulation modeling was based on the I-V curves replotted by taking away the inductive effects of the test circuit and leads. The meximum difference between the measured and calculated data was of the order of 3%. Also the two-stage surge suppression circuit made of the spark gap and the ZnO varistor was investigated with the impulse voltage of $10/1000\mus$$mutextrm{s}$ wave shape. The overall agreement between the theoretical and experimental results seems to be acceptable. As a consequence, it was known that the proposed simulation techniques could effectively be used to design the surge suppression circuits combined with nonlinear components.

  • PDF

전철 탑재형 피뢰기의 모듈설계 및 성능평가기술 (Module Design and Performance Evaluation of Surge Arrester for Loading In Railway Rolling Stock)

  • 조한구;김석수;한세원;이운응
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2000년도 하계학술대회 논문집 C
    • /
    • pp.2038-2040
    • /
    • 2000
  • The main objective of this paper is to design and test a new type of polymer ZnO surge arrester for AC power system of railroad vehicles. Metal oxide surge arrester for most electric power system applications, electric train and subway are now being used extensively to protect overvoltage due to lightning. Surge arresters with porcelain housing must not have explosive breakage of the housing to minimize damage to other equipment when subjected to internal high short circuit current. When breakdown of ZnO elements in a surge arrester occurs due to flashover, fault short current flows through the arrestor and internal pressure of the arrester rises. The pressure rise can usually be limited by fitting a pressure relief diaphragm and transferring the arc from the inside to the outside of the housing. However, there is possibility of porcelain fragmentation caused by the thermal shock, pressure rise. etc. Non-fragmenting of the housing is the most desired way to prevent damage to other equipment. The pressure change which is occurred by flashover become discharge energy. This discharge energy raises to damage arrester housing and arrester housing is dispersed as small fragment. Therefore, the pressure relief design is requested to obstruct housing dispersion. The main research works are focused on the structure design by finite element method, pressure relief of module, and studies of performance of surge arrester for electric railway vehicle.

  • PDF

가변주파수 및 임펄스 전류를 이용한 과도접지임피던스 분석 (An Analysis Method for the Transient Ground Impedance Using Variable Frequency and Lightning Impulse Current)

  • 엄주홍;조성철;이태형
    • 조명전기설비학회논문지
    • /
    • 제22권6호
    • /
    • pp.100-108
    • /
    • 2008
  • 접지전극의 형태, 크기, 재질 및 임펄스전류의 형상에 따라 변화하는 과도접지임피던스는 접지시스템의 성능에 중요한 영향을 미친다. 본 논문은 기존의 실효임펄스임피던스가 실제 과도접지임피던스를 얼마나 효과적으로 나타내고 있는가에 대한 분석과 보다 효과적인 과도접지임피던스 평가방법에 대하여 실험적인 결과를 제시하였다. 실험에 사용된 접지전극은 저항성분과 인덕턴스를 포함한 모의 접지전극과 1[m] 탄소접지봉, 9[m] 일반동봉 그리고 40[m] 매설지선이며, 가변주파수 전류와 임펄스전류에 의한 접지임피던스를 각각 측정하였다. 각각의 값을 비교 했을 때 기존의 실효임펄스임피던스의 값보다는 전압의 최대 값과 전류의 최대 값을 이용하여 과도접지임피던스를 구한 임피던스 값($Z_1$)이 등가주파수에 해당하는 가변주파수 전류에 의해 구해진 접지임피던스에 근접함을 확인하였다.

임펄스전압에 대한 누전차단기의 부동작 특성 (Dead Operation Characteristics of Earth Leakage Circuit Breaker Caused by Impulse Voltages)

  • 이복희;장석훈;이승칠
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1997년도 하계학술대회 논문집 E
    • /
    • pp.1715-1717
    • /
    • 1997
  • This paper deals with the dead operation characteristics of the earth leakage circuit breaker(ELB) caused by impulse voltages. The surge protective devices for electronic circuit and AC power lines are becoming more widely used. It is possible to give rise to the malfunction of ELB due to the operation of surge protective devices, and the interruption of AC power lines brings about several disadvantages such as low reliability of electronic and informational systems, economical loss, and etc. The dead operation characteristics of the ELB from impulse voltages were measured under the conditions of KS C 4613 and the test circuit with a varistor. As a result, the peak current value of the zero-phase sequence circuit of the ELB is increased as the surge voltage and stray capacitance increase. All of the ELBs used in this work were satisfied with the lightning impulse dead operation test condition defined in KS C 4613. However one specimen only did not cause dead operation in the condition of the test circuit with a varistor. There is high possibility that a large portion of the ELBs connected with the AC power lines having the surge protective devices bring about the dead operation.

  • PDF

OF 케이블 계통에서 과도상태시 에너지 특성 검토 (A Study on Energy Characteristics in Transient States of OF Cable Systems)

  • 정채균;이종범;강지원;이동일;서재호
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제55권11호
    • /
    • pp.468-475
    • /
    • 2006
  • This paper reviews the energy characteristics of oil filled cables in transient state such as grounding fault and lightning surge. Artificial grounding fault test was firstly performed in 2003 for the analysis of arc voltage and breakdown energy according to the fault current. In this paper, energy of OF cable is variously analysed at joint box based on the actual test. Then more various conditions such as installation types, section lengths and CCPU(Cable Covering Protection Unit) connection types are applied for the simulation using EMTP when the single line to ground fault and direct lightning stroke are occurred on actual underground power cable systems and combined power cable systems, respectively. Finally, the energy by the length of crossbonded lead and grounding lead as well as fault lasting time is also calculated using EMTP simulation.

저압 AC회로의 MOV 적용방안 연구 (A Study on the Utilization of Metal Oxide Varistor for Low-Voltage AC Circuits)

  • 최효열;이원빈;강영석;이재복
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1996년도 하계학술대회 논문집 C
    • /
    • pp.1822-1824
    • /
    • 1996
  • Damage and upset of control and communication equipment due to transient overvoltages which occur due primarily to internal switching surge and external lightning surge are an important problems in electromagnetic compatibility(EMC). In this paper, we analyzed operation characteristic of metal oxide varistor widely used low voltage AC line using the electromagnetic transients program(EMTP) and compare it with experimental results and also, we modeled combination generator producing $1.2/50{\mu}s$ open circuit voltage and $8/20{\mu}s$ short circuit current as a source which is critical in calculating operation characteristic. Simulation results showed that most of Transient energy consumes at MOV located in service entrance side than load side, and it showed similar to experimental results. Therefore, entrance side MOV should be selected more energy capacity than that of load side MOV.

  • PDF

봉상접지극의 임펼스 전류에 대한 과도접지임피던스 특성 (Characteristics of Transient Grounding Impedances of Rod Electrodes)

  • 이복희;박종순;양정재;이승칠
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1997년도 하계학술대회 논문집 E
    • /
    • pp.1645-1647
    • /
    • 1997
  • Electronic circuits are becoming more vulnerable owing to the development of integrated circuit. Computer and info-communication facilities are very sensitive to surges caused by lightning, and they can suffer a malfunction and damage. Recent concern about damage and upset caused by transient overvoltages has focused on surge protection. The most important parameter in surge protection is the transient grounding impedance. In this paper, the transient grounding impedances of a rod electrode have been measured under impulse current waves. Z-t, Z-i and V-i characteristics of the grounding electrode in according to the length of the grounding lead wire were obtained and analyzed.

  • PDF

신호.통신회로용 과도전압 차단장치 개발에 관한 연구 (A Study on the Development of a Transient Voltage Stocking Device for Signal and Telecommunication Lines)

  • 송재용;이종혁;길경석
    • 한국정보통신학회:학술대회논문집
    • /
    • 한국해양정보통신학회 1999년도 추계종합학술대회
    • /
    • pp.490-493
    • /
    • 1999
  • Due to the miniaturization of electrical components and assembles on signal and telecommunication circuits, transient overvoltages caused by switching operation or lightning surge has become more interesting concern to the field of electrical engineering. This paper describes the development of transient voltage blocking devices (TBDs) that can protect sensitive signal and telecommunication devices from overvoltages. Two kinds of TBDs are designed and tested by using a combination surge generator which can produce the standard impulse current of 8/20${\mu}$s 2.1kA according to the IEC 1000-4-5 standard. From the simulation and experimental reults, it is confirmed that the proposed TBD has an enough protection performance in low insertion loss and tight clamping voltage.

  • PDF

뇌서지에 의한 플라이백 컨버터의 서지전류 경로 분석 (Analysis of Surge Current Path of Flyback Converter by Lightning Surge)

  • 박준우;이강희;김진호;홍성수;원재선;김종해
    • 전력전자학회:학술대회논문집
    • /
    • 전력전자학회 2012년도 전력전자학술대회 논문집
    • /
    • pp.385-386
    • /
    • 2012
  • 기존 뇌서지에 관한 논문은 정보통신 설비 및 전력계통의 대책에 관한 연구가 진행되어 왔으나, SMPS에 관한 연구는 부진하였다. 따라서, 본 논문에서는 조합파 신호발생기를 통하여 서지전압 인가에 따른 플라이백 컨버터에서의 서지전류 경로를 분석한다. 또한, 새로이 발견한 서지전류로 인하여 발생되는 주요 소자파손 원리를 제시한다. 최종적으로 서지경로 상의 실제 측정 결과를 제시하여 제안 방식의 타당성 및 유효성을 검증하였다.

  • PDF

가공배전선로의 전력설비 감시를 위한 유비쿼터스 센서 (Ubiquitous Sensors for Supervision of Power Facilities in Overhead Power Distribution Lines)

  • 길경석;박대원;김일권;최수연;박찬용
    • 조명전기설비학회논문지
    • /
    • 제21권10호
    • /
    • pp.59-65
    • /
    • 2007
  • 최근 유비쿼터스 센서네트워크 기술이 전력설비관리에 적용되어 오고 있다. 본 연구에서는 가공배전선로에서 전력용변압기와 피뢰기를 관리할 수 있는 유비쿼터스 센서의 설계 및 제작에 대해 기술하였다. 이 센서들은 8-[bit] 마이크로프로세서, IEEE 802.15.4기반 무선통신모듈과 주변 전자회로로 구성되어 있다. 변압기의 부하 및 서지전류 측정에는 1000[A]까지 포화되지 않고 선형성을 유지할 수 있도록 공심형 로고우스키 코일을 제작하여 적용하였다. 피뢰기를 흐르는 $50[{\mu}A]{\sim}1[mA]$의 미소누설전류를 측정하기 위하여 180[Hz]에서 $10^5$의 고투자율을 갖는 영상변류기를 사용하였으며, 피뢰기 감시모듈의 -3[dB] 주파수 대역은 12[Hz]에서 1.24[kHz]이다.