• Title/Summary/Keyword: j 인자

Search Result 456, Processing Time 0.024 seconds

An Experimental Study on Air-Side Performance of Fin-and-Tube Heat Exchangers Having Compound Enhanced Fins (복합 전열 촉진 핀이 적용된 핀-관 열교환기의 성능에 대한 실험적 연구)

  • Kim, Nae-Hyun
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.16 no.7
    • /
    • pp.4364-4374
    • /
    • 2015
  • In this study, heat transfer and friction characteristics of compound enhanced fin-and-tube heat exchangers were experimentally investigated. Louver-finned heat exchangers were also tested for comparison purpose. The effect of fin pitch on j and f factor was negligible. The j factor decreased as number of tube row increased. However, f factor was independent of number of tube row. Louver fin samples yielded higher j and f factors than compound enhanced fin samples. For one row, j and f factors of louver fin were 23% and 27% higher than those of compound enhanced fin. For two row, those were 11% and 8%, and for three row, those were 10% and 9%. However, heat transfer capacities at the same pressure drop of the compound enhanced fins were 6.4% for one row, 11.1% for two row and 13.6% for three row larger than those of louver fins, Existing louver fin correlation overpredicted the present j factors and underpredicted the present f factors.

Air-Side Performance of Fin-and-Tube Heat Exchangers Having Non-Symmetric Slit Fins Under Wet Condition (비대칭형 슬릿 핀이 적용된 핀-관 열교환기의 습표면 성능)

  • Kim, Nea-Hyun
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.16 no.6
    • /
    • pp.3698-3707
    • /
    • 2015
  • In this study, wet surface heat transfer and friction characteristics of non-symmetric slit-finned heat exchangers are experimentally investigated. Louver-finned heat exchangers are also tested for comparison purpose. The effect of fin pitch on j and f factor is negligible. Louver fin samples yield higher j and f factors than slit fin samples. For one row, j and f factors of louver fin are 27% and 31% higher than those of slit fin. For two row, j and f factors of louver fin are 15% and 30% higher. Both j and f factor decrease as the number of tube row increases. For one row, average j/f ratios of slit fin samples are 3.4% larger than those of louver fin samples. For two row, average j/f ratios of slit fin samples are 11.5% larger. A new correlation was developed using the present data.

An Experimental Study on Air-Side Performance of Fin-and-Tube Heat Exchangers Having Compound Enhanced Fins Under Wet Condition (복합 전열 촉진 핀이 적용된 핀-관 열교환기의 습표면 성능에 대한 실험적 연구)

  • Kim, Nae-Hyun
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.16 no.9
    • /
    • pp.5778-5788
    • /
    • 2015
  • In this study, wet surface heat transfer and friction characteristics of compound enhanced fin-and-tube heat exchangers were experimentally investigated. Louver-finned heat exchangers were also tested for comparison purpose. The effect of fin pitch on j and f factor was negligible. Both j and f factor decreased as number of tube row increased. Compound enhanced fin samples yielded higher j and f factors than louver fin samples. For one row, j and f factors of compound enhanced fin samples were 11% and 43% higher than those of louver fin samples. For two row, those were 8% and 50%, and for three row, those were 17% and 53%. Heat transfer capacities at the same pressure drop of the compound enhanced fin samples were 2.0% for one row, 3.1% for two row and 8.4% for three row larger than those of louver fin samples, Data were compared with predictions of existing louver fin correlations.

Airside Performance of Fin-and-Tube Heat Exchangers Having Round Wave Fins (둥근 웨이브 핀-관 열교환기의 공기 측 전열 성능)

  • Kim, Nae-Hyun
    • Journal of Energy Engineering
    • /
    • v.24 no.4
    • /
    • pp.105-116
    • /
    • 2015
  • In this study, airside performance of round fin-and-tube heat exchangers are compared with that of the herringbone wave fin-and-tube heat exchangers with an aim to investigate the effect of fin shape on thermal performance. Results show that j factors of the round wave fin are 1.2~22% larger than those of herringbone wave fin. The f factors of the round wave fin are -1.0~29% smaller than those of herringbone wave fin for 1 or 2 row configuration. For 3 row configuration, f factors of the round wave fin are 8.3~23% larger. The reason may be attributed to the reduced recirculation zone in the valley of the fin for round wave fin as compared with that of the herringbone wave fin. For round wave fin, the effect of fin pitch on j and f factor is not significant. In addition, j factors decrease as the number of tube row increases. On the other hand, f factors are independent of the number of tube row. A new correlation was developed based on the present data.

Numerical Analysis on the Effect of Corrugation Angle on the Performance of Humidifying Element (절곡각에 따른 가습소자의 성능에 대한 수치해석적 연구)

  • Lee, Eul-Jong;Kim, Nae-Hyun
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.16 no.5
    • /
    • pp.3051-3059
    • /
    • 2015
  • In this study, the effect of corrugation angle on thermal performance of corrugated plate is numerically investigated with an aim to develop humidifying element. Numerical analysis was conducted for a range of corrugation angle (from $0^{\circ}/0^{\circ}$ to $60^{\circ}/60^{\circ}$ for equal angle and from $15^{\circ}/0^{\circ}$ to $15^{\circ}/60^{\circ}$ for unequal angle). Results revealed that both j and f factor increased as corrugation angle increased. Especially, f factor increased significantly at high corrugation angles. j and f factors of unequal angle plates and those of equal angle (obtained by averaging unequal angles) plates were approximately the same. The largest $j/f^{1/3}$, which implies the largest heat transfer rate per consumed power, was obtained at $15^{\circ}/15^{\circ}$. Existing correlations under- or over-predicted the present numerical results.

Air-side Heat Transfer and Pressure Drop of a Fin-and-Tube Heat Exchanger Under Low Temperature Condition (저온 조건에서 핀-관 열교환기의 공기측 열전달 및 압력손실)

  • Kim, Nae-Hyun
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.18 no.4
    • /
    • pp.15-20
    • /
    • 2017
  • Currently, residential air conditioners operate as a heat pump during winter. In this case, the outdoor heat exchanger acts as an evaporator obtaining heat from cold air. On the other hand, it acts as a condenser during summer transferring heat to hot air. The outdoor temperature changes significantly from high to low. Generally, the air-side j and f factors are obtained at a standard outdoor temperature. Therefore, the applicability of the j and f factors under different outdoor conditions needs to be checked. In this study, tests were conducted for a two-row louver finned heat exchanger changing the outdoor temperature to subzero. The effects of the tube-side brine flow rate were also checked. The results showed that air-side j and f factors were essentially constant and independent of the outdoor temperature, suggesting that an extension of j and f factors obtained under standard conditions to a low outdoor temperature is acceptable. All j and f factors agreed within 9% and 3%, respectively. Tests were also conducted by changing the coolant flow rate. Both the j and f factors did not change according to the flow rate, suggesting that the tube-side heat transfer correlation is acceptable.

Thermo-Flow Analysis of Offset-Strip Fins according to Prandtl Number (Prandtl 수에 따른 옵셋 스트립 핀에서의 열 및 유동 분석)

  • Joo, Youn-Sik;Kong, Dong-Hyun;Lee, Kwan-Soo
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.21 no.6
    • /
    • pp.340-346
    • /
    • 2009
  • This paper numerically investigates thermo-flow characteristics of offset strip fins to obtain a correlation between heat transfer and pressure drop. The flow was divided into three regimes, i.e. laminar, transition and turbulent. The predicted j and f values from the SST k-$\omega$ turbulence model agreed with previous correlations with the error less than 20% in transition and turbulent regimes. Heat transfer and pressure drop were predicted by varying Prandtl number from 0.5 to 40. The Prandtl number showed little effects on pressure drop but had great effect on the heat transfer characteristics. An overall correlation to predict j was suggested by incorporating the effect of Pr and a new j correlation was suggested for each Pr.

Thermo-Flow Analysis of Offset-strip fins according to Prandtl Number (Plandtl 수에 따른 옵셋 스트립핀에서의 열 및 유동 분석)

  • Joo, Youn-Sik;Kim, Min-Soo;Lee, Kwan-Soo
    • Proceedings of the SAREK Conference
    • /
    • 2008.11a
    • /
    • pp.233-238
    • /
    • 2008
  • This paper numerically investigates thermo-flow characteristics of offset strip fins to obtain a correlation between heat transfer and pressure drop. The flow was divided into three regimes, i.e. laminar, transition and turbulent. The predicted j and f values from the SST k-$\omega$ turbulence model agreed with previous correlations with the error less than 20% in transition and turbulent regimes. Heat transfer and pressure drop were predicted by varying Prandtl number from 0.5 to 40. The Prandtl number showed little effects on pressure drop but had great effect on the heat transfer characteristics. An overall correlation to predict j was suggested by incorporating the effect of Pr and a new j correlation was suggested for each Pr.

  • PDF

Optimum Design of Offset-Strip Fins (옵셋 스트립 휜 최적 설계)

  • Kim, Min-Soo;Lee, Kwan-Soo
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.34 no.5
    • /
    • pp.531-537
    • /
    • 2010
  • This paper optimized the design parameters of the offset strip fin in a heat exchanger. To decrease the pressure drop and increase heat transfer, the performance factors such as j/f, $j/f^{1/3}$, and JF, which could be used to estimate the pressure drop and heat transfer simultaneously, were employed as the criteria for optimization. In the present study, STDQAO, PQRSM, and MGA were used for solving the constrained nonlinear optimization problem. The JF factor and heat transfer performance of the optimized offset-strip fin were greater than those of the reference offset-strip fin by 36% and 280%, respectively.

Uniform WKB Wavefunctions and Franck-Condon Factors (Uniform WKB 파동함수와 Franck-Condon 인수)

  • Cho Ung-In;Eu Byung Chan
    • Journal of the Korean Chemical Society
    • /
    • v.18 no.5
    • /
    • pp.307-319
    • /
    • 1974
  • The accuracy of the uniform WKB solution for a two-turning point problem is examined in comparison with the corresponding numerical solution. It is found that the uniform WKB solution is extremely accurate. Various Franck-Condon factors for a model system are calculated as an example of applications of such approximate wavefunction. The accuracy of the factors thus calculated is very good. By using the uniform WKB wavefunctions, we have examined the asymptotic limit of the Frank-Condon factors and derived the condition for the frequencies of the transitions, $E'_{n'J'}-U'_{eff}(r_s)=E"_{n"J"}-U"_{eff}(r_s),$, which was obtained by Mulliken using physical arguments.

  • PDF