• Title/Summary/Keyword: incabinet response amplification

Search Result 1, Processing Time 0.013 seconds

A Shaking Table Test for an Re-evaluation of Seismic Fragility of Electrical Cabinet in NPP (원전 전기캐비넷의 지진취약도 재평가를 위한 진동대 실험)

  • Kim, Min-Kyu;Choi, In-Kil
    • Journal of the Computational Structural Engineering Institute of Korea
    • /
    • v.24 no.3
    • /
    • pp.295-305
    • /
    • 2011
  • In this study, a seismic behavior of electrical cabinet system in Nuclear Power Plants(NPPs) was evaluated by the shaking table test. A 480V Motor Control Centers(MCCs) was selected for the shaking table test, and a real MCC cabinet for the Korea Nuclear Power Plant site was rented by manufactured company. For the shaking table tests, three kinds of seismic input motions were used, which were a US NRC Reg. guide 1.60 design spectrum, a UHS spectrum and PAB 165' floor response spectrum(FRS). Especially, the UHS input motion was selected for an evaluation of structural seismic amplification effects, three directional accelerations were measured at three points outside on the cabinet system and also that of the incabinet response amplification, accelerations were measure at two points which were mounted in electrical equipment such as relay. Seismic amplification effect is determined at the outside and inside of a cabinet as input seismic motion, and compared to the results which are calculated by analytical method based on NUREG/CR-5203.