R-410A 비등열전달에 미치는 미세관경의 영향 (Effect on Flow Boiling Heat Transfer of Minichannel Diameter for R-410A)

  • 최광일;;오종택;;박창용
    • 설비공학논문집
    • /
    • 제21권12호
    • /
    • pp.663-670
    • /
    • 2009
  • Two-phase flow boiling heat transfer of R-410A in horizontal small tubes was reported in the present experimental study. The local heat transfer coefficients were obtained over a heat flux range of 5 to 40 kW/$m^2$ a mass flux range of 170 to 600 kg/$m^2s$, a saturation temperature range of 3 to $10^{\circ}C$, and quality up to 1.0. The test section was made of stainless steel tubes with inner diameters of 0.5 and 3.0 mm, and lengths of 330 and 3000 mm, respectively. The test section was heated uniformly by applying a direct electric current to the tubes. The effects on heat transfer of mass flux, heat flux, inner tube diameter, and saturation temperature were presented. The experimental heat transfer coefficients are compared with six existing heat transfer coefficient correlations. A new boiling heat transfer coefficients correlation based on the superposition model for R-410A in small tubes was developed with mean deviation of 10.13%.

용접형 판형열교환기 성능측정에 관한 실험적 연구 (An Experimental Study on the Performance of Brazed Plater Heat Exchangers)

  • 박현민;박창용
    • 한국생산제조학회지
    • /
    • 제22권3_1spc호
    • /
    • pp.551-557
    • /
    • 2013
  • The heat transfer performance and pressure drop characteristics of brazed-plate heat exchangers with 20 and 30 plates were experimentally measured and analyzed in this study. The mass flow rates of the heat exchangers with 20 and 30 plates were fixed at 0.6 and 0.9 kg/s for the low temperature side, respectively. The mass flow rate for the high temperature side was controlled from 0.2 kg/s to 1.2 kg/s. The inlet temperatures for the high and low temperature sides were $10^{\circ}C$ and $7^{\circ}C$, respectively. The heat transfer characteristics were not influenced by the number of plates. The pressure drop at the heat exchanger with 30 plates was slightly higher than that with 20 plates. The values calculated from the correlations based on gasket plate heat exchangers were compared with the experimental results. It was found that the predicted Nusselt numbers for the gasket plate heat exchangers were about 5% to 20% lower than the measured Nusselt numbers for the brazed plate heat exchangers. However, a pressure drop comparison showed that the calculated pressure drops at the gasket plate heat exchangers were less than half of the measured pressure drops at the brazed plate heat exchangers.

Gas 분산 기-액 반응조에서 기포운동이 열전달에 미치는 영향

  • 손병진;이현
    • 대한설비공학회지:설비저널
    • /
    • 제8권1호
    • /
    • pp.10-13
    • /
    • 1979
  • The study for bubbling phenomena to influence heat transfer in gas - liquid contactors. The sparged contactor is gaining importance for gas-liquid chemical reactions. In this paper, correlations between Reynolds number and heat transfer coefficient were studied and experimental expressions were also obtained over broth of areas, namely, laminar area and turbulent area respectively.

  • PDF

알루미늄 다채널 평판관내 R-22 증발에 관한 실험적 연구 (An Experimental study on R-22 Evaporation in Flat Aluminum Multi-Channel Tubes)

  • 김정오;조진표;김종원;정호종;김내현
    • 대한기계학회:학술대회논문집
    • /
    • 대한기계학회 2000년도 춘계학술대회논문집B
    • /
    • pp.96-103
    • /
    • 2000
  • In this study, evaporation heat transfer tests were conducted in flat aluminum multi-channel tubes using R-22. Two internal geometries were tested ; one with smooth inner surface and the other with micro-fins. Data are presented for the following range of variables ; vapor quality $(0.1{\sim}0.9)$, mass flux$(100{\sim}600kg/m^2s)$ and heat flux$(5{\sim}15kW/m^2)$. The micro-tin tube showed higher heat transfer coefficients compared with those of the smooth tube. Results showed that, for the smooth tube, the effects of mass flux, quality and heat flux were not prominent, and existing correlations overpredicted the data. For the micro-fin tube at low quality, the heat transfer coefficient increased as heat flux increased. However, the trend was reversed at high quality Kandlikar's correlation predicted the low mass flux data, and Shah's correlation predicted the high mass flux data. The heat transfer coefficient of the micro fin tube was approximately two times larger than that of the plain tube. New correlation was developed based on present data.

  • PDF

경사각이 PF 열교환기의 열전달 및 압력 손실에 미치는 영향 (Effect of Inclination Angle on the Heat Transfer and Pressure Drop Characteristics of Parallel Flow Heat Exchanger)

  • 김도영;함정호;김내현;박내현;황준현
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2007년도 동계학술발표대회 논문집
    • /
    • pp.222-228
    • /
    • 2007
  • The effect of inclination angle on the heat transfer and pressure drop characteristics of brazed aluminum heat exchangers is experimentally investigated. Three samples having different fin pitches (1.25, 1.5 and 2.0 mm) were tested. Results show that heat transfer coefficient is not affected by the inclination angle. However, the friction factor increases as the inclination angle increases with negligible difference between the forward and backward inclination. Both the heat transfer coefficient and the friction factor are the smallest at $P_f$=1.5mm, followed by $P_f$=2.0mm and 1.25mm. Possible explanation is provided considering the louver layout. Comparison with existing correlations is also mad.

  • PDF

병렬 마이크로 채널에서 FC-72의 비등 열전달 특성 (Boiling heat transfer characteristics of FC-72 in parallel micro-channels)

  • 최용석;임태우;유삼상;김환성;최형식
    • Journal of Advanced Marine Engineering and Technology
    • /
    • 제38권9호
    • /
    • pp.1032-1038
    • /
    • 2014
  • 본 연구에서는 병렬 마이크로 채널에서 FC-72의 비등 열전달 특성을 파악하기 위한 실험적 연구를 수행하였다. 병렬 마이크로 채널은 깊이 0.2 mm, 폭 0.45 mm, 길이 60 mm의 15개의 마이크로 채널로 구성되었으며, 실험은 열유속 $16.4kW/m^2$$25.6kW/m^2$의 조건에서 수행되었으며, 이때 질량유속 300, 400 그리고 $500kg/m^2s$의 범위에서 이루어졌다. 실험을 통해 측정된 열전달 계수는 낮은 건도에서는 건도가 증가함에 따라 급격하게 감소하며, 일정 건도 이상에서는 일정하게 유지되었다. 본 연구를 통해 마이크로 채널에서 FC-72의 비등 열전달 메커니즘을 확인하였으며, 실험에서 얻어진 열전달 계수는 열전달 계수를 예측하기 위한 기존의 상관식들과 비교 분석하였다.

나선형 튜브내의 난류 열전달에 대한 수치적 연구 (Numerical Study of Turbulent Heat Transfer in Helically Coiled Tubes)

  • 윤동혁;박주엽;설광원
    • 대한기계학회논문집B
    • /
    • 제36권8호
    • /
    • pp.783-789
    • /
    • 2012
  • 본 연구에서는 나선형 튜브내의 난류 열전달 및 하중 특성을 수치해석 방법을 이용하여 파악하였다. 열교환기와 같은 공학적 설비에서 관내 열전달을 향상시키기 위해 튜브의 형상을 나선형으로 설계한다. 이에 나선형 튜브내의 열전달 및 난류 특성에 대한 많은 실험적 연구가 이루어 졌으나, 대부분의 연구가 압력 강하 및 열전달 상관관계에 초점이 맞추어 진행되었다. 나선형 튜브내의 유동은 원심력에 의해 튜브 바깥쪽에서는 상대적으로 높은 열전달 및 전단응력이 발생하지만, 안쪽에서는 낮은 열전달 및 전단응력이 발생하게 된다. 따라서 본 연구에서는 튜브의 원주방향으로 발생하는 전단 응력 및 Nusselt 수의 변화를 Reynolds 수와 나선 코일의 지름을 변경하며 정량적으로 살펴보았다. 나선 코일 안쪽에서 국부적인 전단응력과 열전달율이 크게 낮게 특정되었으며, 이는 튜브 재질의 안정성에 영향을 미칠 것으로 판단되었다. 또한 본 연구에서는 마찰계수와 Nusselt 수에 대한 기존 상관관계식을 검증하였으며, 직관에서의 마찰계수와 Nusselt 수의 상관관계식이 나선형 튜브의 형상에도 적용될 수 있음을 관측하였다. 본 연구의 결과는 열교환기나 증기발생기의 안전성 평가를 위해 중요한 데이터로 활용될 수 있을 것이다.

맥동관 내부의 열전달에 관한 실험적 연구 (Experimental study on the transfer in pulse tube)

  • 김민규;남관우;정상권;장호일;정은수
    • 한국초전도ㆍ저온공학회논문지
    • /
    • 제2권1호
    • /
    • pp.45-50
    • /
    • 2000
  • The present study has been conducted to observe the heat transfer under pulsating pressure and oscillating flow. The experimental apparatus was fabricated to measure the gas temperature, the wall temperature. the pressure and the instantaneous heat flux inside the pulse tube. The measured gas temperature and heat flux must be calibarated to compensate their finite time constant in the oscillating flow conditious. The experiment was performed from 1 Hz to 5 Hz. The phase difference between the instantaneous heat flux and the gas-wall temperature difference was clearly observed. The experimental heat fluxes were compared to the theroretical correlations such as Complex Nusselt Number Model(CNNM) and Variable Coefficient Model(CVM). The heat flux predisted by CNNM was always greater than that of VCM. The experiment confirmed the valisity of the VCM for the instantaneous heat flux under the pulsating pressure and oscillating flow in the warm end of the pulse tube.

  • PDF

평활관 및 미세휜관 내에서의 물을 이용한 열전달 및 압력강하 특성에 관한 실험 (Experimental study of heat transfer and pressure drop characteristics for flow of water inside circular smooth and micro-fin tubes)

  • 박혁범;유승문;윤백;유국철
    • 설비공학논문집
    • /
    • 제9권4호
    • /
    • pp.454-461
    • /
    • 1997
  • Heat transfer and pressure drop for single phase flow of water in circular smooth and micro-fin tubes are measured. Copper tubes of 9.52 and 7mm outer diameter were used. The internal roughness in micro-fin tubes was formed by spiral grooves having $25^{\circ}$ helx angle, 0. 12mm fin height and 0.454mm pitch in 9.52mm tubes; $18^{\circ}$ helix angle, 0.15mm fin height and 0.322mm pitch in 7mm tubes. The measured friction factor and heat transfer coefficient are compared with relevant previous works, and the correlations for micro-fin tube are developed.

  • PDF

이산화탄소용 핀-관 증발기의 성능해석 (Performance Analysis of Fin-tube Evaporator for Carbon Dioxide)

  • 이민규;김영일;장영수;김용찬
    • 설비공학논문집
    • /
    • 제16권7호
    • /
    • pp.645-651
    • /
    • 2004
  • Fin-tube evaporator for carbon dioxide has been investigated both by experiment and simulation. Inside refrigerant heat transfer and outside heat and mass transfer of a wet surface heat exchanger were modeled using appropriate correlations. The results estimated by the calculation were in good agreement with the experimental results. The simulation errors were less than 7.9% for estimating capacity, 0.6$^{\circ}C$ for air exit temperature, 1.2% for air exit humidity and 17% for $CO_2$ exit pressure. The simulation program was used to study the effect of air flow direction, number of rows and refrigerant circuits. For a 2-row evaporator, parallel flow showed better performance for low air velocity but for high air velocity, counter-flow was better. Refrigerant circuits, however, showed insignificant effect on the performance.