• Title/Summary/Keyword: heat transfer correlations

Search Result 364, Processing Time 0.025 seconds

Evaluation of Condensation Heat Transfer Correlations for Microfin Tubes

  • Han, Dong-Hyouck;Lee, Kyu-Jung
    • International Journal of Air-Conditioning and Refrigeration
    • /
    • v.15 no.4
    • /
    • pp.163-168
    • /
    • 2007
  • The feature of six existing condensation heat transfer correlations for microfin tubes were evaluated with the consideration of vapor quality, mass flux, geometries, and various refrigerants. The Kosky and Staub [15] and the Jaster and Kosky [16] correlations for smooth tube were used for the evaluation of the heat transfer enhancement factor (EF). For the prediction of zeotropic mixtures, most correlations show discrepancy with previous measurements. The Yu and Koyama [4] and the Shikazono et al. [8] correlations do not consider spiral angle effect. The Han and Lee [10] correlation shows fin height growth deteriorates heat transfer. Experimental verification to develop reliable condensation heat transfer correlation for microfin tubes is still needed with the consideration of geometrical effects and working conditions.

EXPERIMENTAL INVESTIGATION OF CONVECTIVE HEAT TRANSFER IN A NARROW RECTANGULAR CHANNEL FOR UPWARD AND DOWNWARD FLOWS

  • Jo, Daeseong;Al-Yahia, Omar S.;Altamimi, Raga'i M.;Park, Jonghark;Chae, Heetaek
    • Nuclear Engineering and Technology
    • /
    • v.46 no.2
    • /
    • pp.195-206
    • /
    • 2014
  • Heat transfer characteristics in a narrow rectangular channel are experimentally investigated for upward and downward flows. The experimental data obtained are compared with existing data and predictions by many correlations. Based on the observations, there are differences from others: (1) there are no different heat transfer characteristics between upward and downward flows, (2) most of the existing correlations under-estimate heat transfer characteristics, and (3) existing correlations do not predict the high heat transfer in the entrance region for a wide range of Re. In addition, there are a few heat transfer correlations applicable to narrow rectangular channels. Therefore, a new set of correlations is proposed with and without consideration of the entrance region. Without consideration of the entrance region, heat transfer characteristics are expressed as a function of Re and Pr for turbulent flows, and as a function of Gz for laminar flows. The correlation proposed for turbulent and laminar flows has errors of ${\pm}18.25$ and ${\pm}13.62%$, respectively. With consideration of the entrance region, the heat transfer characteristics are expressed as a function of Re, Pr, and $z^*$ for both laminar and turbulent flows. The correlation for turbulent and laminar flows has errors of ${\pm}19.5$ and ${\pm}22.0%$, respectively.

Improved Convective Heat Transfer Correlations for Two-Phase Two-Component Pipe Flow

  • Kim, Dongwoo
    • Journal of Mechanical Science and Technology
    • /
    • v.16 no.3
    • /
    • pp.403-422
    • /
    • 2002
  • In this study, six two-phase nonboiling heat transfer correlations obtained from the recommendations of our previous work were assessed. These correlations were modified using seven extensive sets of two-phase flow experimental data available from the literature, for vertical and horizontal tubes and different flow patterns and fluids. A total of 524 data points from five available experimental studies (which included the seven sets of data) were used for improvement of the six identified correlations. Based on the tabulated and graphical results of the comparisons between the predictions of the modified heat transfer correlations and the available experimental data, appropriate improved correlations for different flow patterns, tube orientations, and liquid-gas combinations were recommended.

An Experimental Study on Heat Transfer Characteristics Just Before Critical Heat Flux in Uniformly Heated Vertical Annulus Under a Wide Range of Pressures

  • Chun, Se-Young;Moon, Sang-Ki;Chung, Heung-June;Chung, Moon-Ki
    • Nuclear Engineering and Technology
    • /
    • v.34 no.4
    • /
    • pp.269-285
    • /
    • 2002
  • Water heat transfer experiments were carried out in a uniformly heated annulus with a wide range of pressure conditions. The local heat transfer coefficients for saturated water (low boiling have been measured just before the occurrence of the critical heat flux (CHF) along the length of the heated section. The trends of the measured heat transfer coefficients were quite different from the conventional understanding for the heat transfer of saturated flow boiling. This discrepancy was explained from the nucleate boiling in the liquid film of annular flow under high heat flux conditions. The well-known correlations were compared with the measured heat transfer coefficients. The Shah and Kandlikar correlations gave better prediction than the Chen correlation. However, the modified Chen correlation proposed in the present work showed the best agreement with the present data among correlations examined .

Experiments on Single Phase Cooling Heat Transfer and Pressure Drop Characteristics in Microfin Tubes (마이크로휜관 내 단상 냉각 유동 열전달 및 압력 강하 특성에 관한 실험적 연구)

  • 이규정;한동혁
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.14 no.3
    • /
    • pp.231-239
    • /
    • 2002
  • Experiments on the single phase cooling heat transfer and pressure drop with microfin tubes were performed using water as a test fluid. Experimental data were obtained in the range of Reynolds number 3000 ~40000 and Prandtl number 4-6. The data of microfin tubes presented the characteristics of rough surface tube in pressure drop and heat transfer Experimental data were compared with the heat transfer and friction factor correlations of smooth tubes. Heat transfer enhancements of microfin tubes were lower than pressure drop penalty factors. The helix angle is more significant parameter in both of the pressure drop and heat transfer than the relative roughness. The correlations of Nusselt number and friction factor were suggested for the tested microfin tubes. Maximum deviations between correlations and experimental data were within $\pm15$% for Nusselt number and $\pm10$% for friction factor.

Thermal Performance of a Finned-tube Heat Exchanger used in Condensing Gas Boiler

  • Kang, Hie-Chan;Lim, Bok-Bin;Lee, Jung-Man;Kim, Moo-Han
    • International Journal of Air-Conditioning and Refrigeration
    • /
    • v.17 no.2
    • /
    • pp.61-67
    • /
    • 2009
  • In the present study, an experiment was conducted to investigate the heat and mass transfer performance of heat exchangers used in the condensing gas boiler. Two types of spiral circular fin-tube heat exchangers and a plain tube were tested in the flue gas of propane and dry air. Heat and mass transfer coefficients were measured and compared with the previous correlations. The experimental data for the sensible heat transfer of the plain tube reasonably agreed with the previous correlations for dry air and flue gas. However, the mass transfer coefficient of the plain tube was greater than the previous correlations. The pH, $NO_x$, and $SO_x$ data of condensate were provided.

Characteristics of Evaporative Heat Transfer and Pressure Drop of Carbon Dioxide and Correlation Development near the Critical Point (임계점 부근에서 이산화탄소의 증발열전달 및 압력강하 특성 연구와 상관식 개발)

  • 윤석호;조은석;김민수
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.16 no.6
    • /
    • pp.530-537
    • /
    • 2004
  • In recent years, carbon dioxide among natural refrigerants has gained consider-able attention as an alternative refrigerant due to its excellent thermophysical properties. However, few investigations have been performed to develop useful correlations of heat trans-fer coefficients and pressure drop during evaporation of carbon dioxide. This study is aiming at providing the characteristics of heat transfer and pressure drop during the evaporation process of carbon dioxide. Heat is provided by a direct heating method to the test section, which was made of a seamless stainless steel tube with an inner diameter of 7.53 mm, and a length of 5.0 m. Experiments were conducted at saturation temperatures of -4 to 2$0^{\circ}C$, heat fluxes of 12 to 20 ㎾/$m^2$ and mass fluxes of 200 to 530 kg/$m^2$s. A comparison of different heat transfer correlations applicable to evaporation of carbon dioxide has been made. Based on the experiments for evaporation heat transfer and pressure drop, new correlations were developed. The newly developed empirical correlations for the heat transfer and pressure drop show average absolute deviations of 15.3% and 16.2%, respectively.

Heat Transfer Correlations for Air-Water Two-Phase Flow of Different Flow Patterns In a Horizontal Pipe

  • Kim, Dongwoo
    • Journal of Mechanical Science and Technology
    • /
    • v.15 no.12
    • /
    • pp.1711-1727
    • /
    • 2001
  • Heat transfer coefficient were measured and new correlations were developed for two-phase heat transfer in a horizontal pipe for different patterns. Flow patterns were observed in a transparent circular pipe (2.54 cm I. D. and L/D=96) using an air/water mixture. Visual identification of the flow patterns was supplemented with photographic data and the results were plotted on the flow regime map proposed by Taitel and Dukler and agreed quite well with each other. A two-phase heat transfer experimental setup was built for this study and a total of 150 two-phase heat transfer data with different flow patterns were obtained under a uniform wall heat flux boundary condition. For these data, the superficial Reynolds number ranged from 640 to 35,500 for the liquid and from 540 to 21,200 for the gas. Our previously developed robust two-phase heat transfer correlation for a vertical pipe with modified constants predicted the horizontal pipe air-water heat transfer experimental data with good accuracy. Overall the proposed correlations predicted the data with a mean deviation of 1.0% and an rms deviation of 12%.

  • PDF

Experimental Study on Heat Transfer and Pressure Drop Characteristics for Single-Phase Flow in Plate and Shell Heat Exchangers. (Plate and Shell 열교환기의 단상유동 열전달 및 압력강하 특성에 관한 실험적 연구)

  • 서무교;김영수
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.12 no.4
    • /
    • pp.422-429
    • /
    • 2000
  • Plate and shell heat exchanger(P&SHE) is widely applied as evaporators or condensers in the refrigeration and air conditioning systems for their high efficiency and compactness. In order to set up the database for the design of the P&SHE, heat transfer and pressure drop characteristics for single phase flow of water in a plate & shell heat exchanger are experimentally investigated in this study. Single phase heat transfer coefficients were measured for turbulent water flow in a plate and shell heat exchangers by Wilson plot method. The shell side heat transfer resistance was varied and the overall heat transfer coefficients were measured. The single-phase heat transfer coefficients in a plate side were obtained by Wilson plot method. Single-phase heat transfer correlations based on projected heat transfer area and friction factor correlations have been proposed for single phase flow in a plate and shell heat exchanger.

  • PDF

Study on Characteristics of Flow Boiling Heat Transfer in Multi channels (수평 다채널 관에서의 유동 비등 열전달 특성에 관한 연구)

  • CHOI, Yong-Seok;LIM, Tae-Woo
    • Journal of Fisheries and Marine Sciences Education
    • /
    • v.27 no.5
    • /
    • pp.1310-1317
    • /
    • 2015
  • Two-phase flow boiling heat transfer in micro-channels was experimently investigated. The test section consisted of 15 rectangular micro-channels with a depth of 0.45mm, width of 0.20mm. The experiments were performed for heat fluxes ranging from 5.6 to 46.1kW/m2 and mass fluxes from 150 to 450kg/m2s using FC-72 as the working fluid. According to the results, at the low heat flux region, heat transfer coefficient strongly depends on the heat flux, while heat transfer coefficient at the high heat flux region was independent on the heat flux. Four correlations were used to predict the heat transfer coefficient. The measured heat transfer coefficient was compared with four correlations. It was found that Kaew-On and Wongwises's correlation well predicted the measured data, within the MAE of 40.3%.