• Title/Summary/Keyword: grounding system

Search Result 467, Processing Time 0.028 seconds

Study on Measurement Error Reduction Technique when Measuring Touch and Step Voltage of Grounding System (접지시스템의 접촉전압 및 보폭전압 측정오차 감소 기법에 관한 연구)

  • Kim, Dong-Woo;Lim, Young-Bea;Lee, Sang-Ick;Choi, Myeong-Il;Moon, Hyun-Wook
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.64 no.1
    • /
    • pp.188-195
    • /
    • 2015
  • This paper presents measurement error reduction technique of touch and step voltage of grounding system based on numerical analysis. When measuring touch and step voltage of grounding system, auxiliary current probes should be located at suitable places. However, the auxiliary probes can not be located at suitable places in such cases as there are buildings and pavements. Therefore, in this paper, we provided measurement error reduction technique of touch and step voltage of grounding system according to the positions of auxiliary probes and angle between auxiliary probes. Also, measurement error analyses of touch and step voltage of grounding system have been conducted using more than one current probe. Based on these analyses, recommended positions of auxiliary probes within allowable measurement errors were presented.

Calculation Method of Transient Potential Rises of Horizontal Ground Electrodes Depending on Injection Point of the Ground Current (접지전류의 입사점에 따른 정보통신설비용 수평접지전극의 과도전위상승 계산 방법)

  • Ahn, Chang-Hwan
    • Journal of the Institute of Electronics and Information Engineers
    • /
    • v.51 no.12
    • /
    • pp.197-203
    • /
    • 2014
  • When the lightning current is injected to the ground system of information and communication facilities, analysis of the transient potential rise in the ground system is one of main factors to effectively design the ground system. The performance of grounding systems is normally estimated with the grounding impedance and the transient potential rise which represents the electrical characteristics of the grounding system. The method for calculating the grounding impedance depending on the injection point of the lightning current was proposed. The delta-gap source model was proposed to calculate the grounding impedance in the case that the lightning current is injected to the center of the horizontal ground electrode. A new program which is possible to apply the frequency-dependent soil parameters using the Debye model was developed, because a commercial program for analyzing the performance of the grounding system can not apply to the frequency-dependent soil parameters. The experiment was carried out to confirm the availability of the simulation results with the same condition. Finally, the transient potential rises of a horizontal ground electrode depending on the lightning current waveforms were analyzed by using the results of the grounding impedance which is associated with the frequency-dependent soil parameters.

Recent Trend of International Standards on the Safety Criteria for Electric Shock Protection (인체감전 안전기준에 관한 최근 국제규격의 동향)

  • Lee, Jong-Chul;Kim, Han-Soo;Lee, Ju-Chul;Kang, Sung-Man
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2007.11a
    • /
    • pp.189-193
    • /
    • 2007
  • The grounding of an electrical system is one of the essential elements for public safety. Domestic practice of grounding system design has been to get grounding resistance values which are classified by facilities or equipment in the regulations. But the concept of grounding system design of IEC is, as a main factor of safety index, to consider touch voltage and step voltage instead of the resistance value itself. Recently IEC actively develops or revises safety related standards which are essential for the grounding system performance. In this paper, we present the recent trend of the international standards on the safety criteria for Electric Shock Protection.

  • PDF

Voltage Quality Analysis in Power Distribution System with Superconducting Fault Current Limiter at Grounding Line (초전도 한류기를 주변압기 접지선에 설치시 배전계통의 순간전압품질 분석)

  • Moon, Jong-Fil
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.62 no.4
    • /
    • pp.159-163
    • /
    • 2013
  • In this paper, voltage quality improvement is analyzed in case of Superconducting Fault Current Limiter (SFCL) installed in grounding line of main transformer in power distribution system. First, a resistive-type SFCL model is used. Next, Korean power distribution system is modeled. Finally, when SFCL is installed in the starting point of feeder and grounding line of main transformer, voltage qualities are evaluated according to various fault locations and resistance values of SFCL using PSCAD/EMTDC. The voltage quality results in case of grounding line are compared with the voltage in case of feeder.

Analysis for the conventional impedance of counterpoise using EMTP (EMTP를 이용한 매설지선의 규약접지임피던스 해석)

  • Kim, Jong-Ho;Joe, Jeong-Hyeon;Beak, Young-Hwan;Lee, Gang-Su;Lee, Bok-Hee
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2009.10a
    • /
    • pp.47-50
    • /
    • 2009
  • When the lightning currents flow through the ground electrode, the grounding system should be evaluated by the grounding impedance rather than the ground resistance because a grounding system shows the transient impedance characteristic by the inductance of the ground electrode and the capacitance of the soil. The ratio of the peak values of electric potential and currents is the conventional impedance that shows the transient characteristic about impulse currents of the grounding system in a roundabout way. The grounding system having low conventional impedance is a fine grounding system with low electric potential when the lightning currents flow. In this paper the conventional impedance of the counterpoise is calculated by using the distributed parameter circuit model and embodied the distributed parameter circuit model by using the EMTP program The adequacy of the distributed parameter model is examined by comparing the simulated and the measured results. The conventional impedance of the counterpoise is analyzed for first short stroke and subsequent short stroke currents.

  • PDF

A Study on the Grounding Impedance Effects and Its Characteristics (접지 임피던스의 영향분석에 관한 연구)

  • Chang, Myong-Soo;Park, Keon-Woo;Kim, Chul-Hwan
    • Proceedings of the KIEE Conference
    • /
    • 2007.07a
    • /
    • pp.1948-1949
    • /
    • 2007
  • This paper presents the characteristics and effects of grounding resistor and impedance. In grounding system, Grounding resistor is governed neutral currents and voltage. It seems that, grounding resistor has 0 value, then circuit has no faults. While if grounding resistor has large value, then neutral current has large value of fault current and it is made a damage to the utility. In order to analyze the grounding impedance characteristic, EMTP simulation has been used. The grounding impedance characteristic has been analyzed and tested for various grounding arrangements and electrode circuit shapes.

  • PDF

Optimization of protection System on the Railway High Voltage power System (철도 고압배전계통의 보호시스템 최적화 방안 연구)

  • 조웅기;창상훈;한성호;김왕곤
    • Proceedings of the KSR Conference
    • /
    • 2002.10b
    • /
    • pp.989-994
    • /
    • 2002
  • In case the fault occurs in railway high voltage power supply network, protective relaying system must selectively detect 1 wire ground fault of grounding or non-grounding system. And this study presents railway high voltage power supply system model using PSCAD/EMTDC Vet 3.08 for circuit analysis and fault studies. In this paper, we propose protection method of non-grounding system of railway high voltage power supply system. The result shows its usefulness.

  • PDF

Analysis of Human Safety and System Effect according to Grounding Scheme in LVDC Distribution System (LVDC 배전계통의 접지방식에 따른 인체안전 및 계통영향 분석)

  • Oh, Yun-Sik;Han, Joon;Gwon, Gi-Hyeon;Kim, Doo-Ung;Noh, Chul-Ho;Jung, Tack-Hyun;Kim, Chul-Hwan
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.63 no.5
    • /
    • pp.608-614
    • /
    • 2014
  • Recent developments and trends in the electric power consumption clearly indicate an increasing use of DC in end-user equipment. According to the trends, new DC power distribution systems have been researched and developed although we presently enjoy a predominantly AC power distribution system. We can use various grounding schemes in DC distribution system as well as in AC distribution system to protect human body and equipments. However, we need to evaluate carefully which grounding scheme is appropriate for a specific system before applying those schemes. In this paper, we analyze the human safety and system effect according to various grounding schemes in Low Voltage DC (LVDC) distribution system. Some components in LVDC distribution system are modeled and computer simulations are conducted by using ElectroMagnetic Transient Program (EMTP).

Frequency-dependent grounding impedance of the counterpoise based on the dispersed currents

  • Choi, Jong-Hyuk;Lee, Bok-Hee;Paek, Seung-Kwon
    • Journal of Electrical Engineering and Technology
    • /
    • v.7 no.4
    • /
    • pp.589-595
    • /
    • 2012
  • When surges and electromagnetic pulses from lightning or power conversion devices are considered, it is desirable to evaluate grounding system performance as grounding impedance. In the case of large-sized grounding electrodes or long counterpoises, the grounding impedance is increased with increasing the frequency of injected current. The grounding impedance is increased by the inductance of grounding electrodes. This paper presents the measured results of frequency-dependent grounding impedance and impedance phase as a function of the length of counterpoises. In order to analyze the frequency-dependent grounding impedance of the counterpoises, the frequency-dependent current dissipation rates were measured and simulated by the distributed parameter circuit model reflecting the frequency-dependent relative resistivity and permittivity of soil. As a result, the ground current dissipation rate is proportional to the soil resistivity near the counterpoises in a low frequency. On the other hand, the ground current dissipation near the injection point is increased as the frequency of injected current increases. Since the high frequency ground current cannot reach the far end of long counterpoise, the grounding impedance of long counterpoise approaches that of the short one in the high frequency. The results obtained from this work could be applied in design of grounding systems.

Transient Grounding Impedance Characteristic Analysis of a Copper Rod-type Grounding Electrode Used for Electric Distribution Systems Using MATLAB Program (MATLAB 프로그램을 이용한 배전계통에 사용되는 동봉 접지전극의 과도 접지임피던스 특성 분석)

  • Kim, Kyung-Chul;Oh, Kyung-Hoon;Lee, Kyu-Jin;Shim, Keun-Bo;Choi, Jong-Kee
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.23 no.9
    • /
    • pp.40-46
    • /
    • 2009
  • Although a ground resistance is a good index of grounding performance for grounding electrodes, it does not reflect the grounding performance during transient state. A copper rod electrode is the most commonly used grounding electrode in electric distribution systems. In this paper, the grounding impedance of copper rods has been measured in frequency raging from 60[Hz] up to 100[kHz] and an equivalent model of the grounding impedance is identified from the measured values. The grounding impedance under study when a typical lightning surge is injected into the grounding system was simulated numerically and graphically through the use of the MATLAB software program.