• Title/Summary/Keyword: grounding resistance

Search Result 246, Processing Time 0.036 seconds

Analysis of Deterioration Characteristics for Connection Factor according to Connection Method of Grounding System (접지시스템의 접속방식에 따른 접속요소의 열화특성 분석)

  • Gil, Hyoung-Jun;Kim, Hyang-Kon;Kim, Dong-Ook;Kim, Dong-Woo
    • Proceedings of the KIEE Conference
    • /
    • 2011.07a
    • /
    • pp.2126-2127
    • /
    • 2011
  • This paper describes the analysis of deterioration characteristics for connection factor according to connection method of grounding system. The connection method of grounding system is specified in IEC standard. In order to analyze the deterioration characteristics for connection factor, deterioration test was carried out when the connection factor was buried in salt water and underground. The test connection factors were C-type sleeve, clamp, and exothermic welding. As a consequence, most of the connection factor was corroded, and the electrical resistance decreased after deterioration. The analytical results can be used to establish the safety of grounding system.

  • PDF

The Construction of Safety Measurement Equipment of Grounding Electrode for Distribution System (배전용 접지전극의 안전성 분석 장치 구성)

  • Kang, Moon-Ho;Park, Young-Keun;Jang, Sang-Ok;Won, Yoon-Chan;Lee, Heung-Ho
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2005.05a
    • /
    • pp.218-221
    • /
    • 2005
  • Grounding electrodes as discharge paths to the earth are normally used to ensure the safety of human body and facilities from the over-voltages in distribution power system, and each grounding mode has a prescribed ground resistance value respectively which is applied by the utilities. As the various electrodes for distribution power system are recently developing to improve the performance of them and resolve the problem of space restriction, it is necessary to measure and investigate the safety of human body of developed electrodes. Therefore, in this paper, we provide briefly a technical comparison of two standards, i.e. IEEE Std 80 and the IEC 479-1, and describe the configuration of safety measurement system which can measure the step voltage and the touch voltage of grounding electrodes based on IEEE Std 80.

  • PDF

Grounding Grid Design Considering the Dangerous Voltage of Multi-layered Model in the Constrained Sites (제한된 부지 다층 대지구조에서 위험전압을 고려한 접지설계)

  • Son, Seok-Geum
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.62 no.3
    • /
    • pp.139-144
    • /
    • 2013
  • In Korea, where most of the sites are narrow in space and their earth resistivity is relatively high, the spaces between grounding conductors are likely to be designed narrow in order to lower ground resistance and dangerous voltage below to the permitted safety values. In addition, ground nets are in the shape of square or rectangle depending on the location and size of the facilities and ground contact area, and inner conductors are laid out in grids like the pattern of nets. Nevertheless, with the existing designs, the marginal voltage for safety gets higher as the area is extended further outside, in comparison with that of inner mesh grounding, thus causing much difficulty maintaining them equipotential, and there exist limits in the burial, grounding grid design considering the dangerous voltage of muti-layered model in the constrained sites, was studied.

An experimental research for Potential Interference of a Mesh electrode in Intelligent Building System (지능형빌딩의 대단위접지극의 전위간섭에 대한 실증연구)

  • Koh, Hee-Seog;Kim, Ju-Chan;Choi, Jong-Gyu;Kim, Maeng-Hyun
    • Proceedings of the KIEE Conference
    • /
    • 2005.07a
    • /
    • pp.414-416
    • /
    • 2005
  • This is for investigating the grounding resistance of grounding electrodes, the experiment was performed with model-scale of the grounding system and the scaled model grounding system was to this experiment using a water tank of a stainless steel-hemisphere shape. since mesh electrodes have been widely in the general building, we're tried to analyze that this water tank model and it's simulation as well.

  • PDF

Modeling of Impedance Characteristics of Grounding Electrode for Distribution Line Pole (배전전주의 봉상 접지전극 형태별 임피던스 특성의 모델링)

  • Shim, Keon-Bo;Kim, Kyung-Chul;Lee, Hyung-Soo;Park, Jae-Duck;Choi, Jong-Kee;Park, Sang-Man
    • Proceedings of the KIEE Conference
    • /
    • 2005.07a
    • /
    • pp.694-696
    • /
    • 2005
  • Although DC ground resistance is a good index of grounding performance for grounding electrodes, it does not reflect the grounding performance during transient state. Besides, impulse ground impedance, which is defined by a ratio of the peak value of transient ground potential rise to the peak value of impulse current, cannot be an absolute index due to its dependence on impulse current shape. In this paper, ground impedance characteristics of ground electrodes has been measured in frequency domain ranging from 1 Hz to hundreds of kHz. Equivalent circuit models and transfer function models of the ground rod have been identified from the measured values of ground impedance in frequency domain.

  • PDF

Construction of Lightning Protection System for Railway Signaling Equipments (철도신호설비용 낙뢰방호장치의 건설)

  • Choi Kyu-Hyoung;Seo Seok-Chul;Choi Se-Wan
    • Proceedings of the KSR Conference
    • /
    • 2004.10a
    • /
    • pp.1193-1198
    • /
    • 2004
  • This paper describes the lightning protection system for railway signaling equipments installed at subway car depots in Seoul metropolitan Rapid Transit Cooperation. Several measures for improving lightning protection performance are adopted; newly organized grounding system for neutral line of power system, rolling method to minimize damages induced by direct lightning strike, new measures to reduce voltage differences between the signaling equipments and the ground, and improvement of grounding system. The proposed system has greatly reduced the grounding resistance and also the voltage difference between the signaling equipments and the ground, and has prevented the accident related with lightning surges since it was installed. The proposed approach can be viewed as a useful alternative of dealing with lightning protection for railway signaling equipments.

  • PDF

The Effects of Soil Model in the Grounding System Design (침상 접지전극봉의 접지효과 분석)

  • Lee, Hyung-Soo;Shim, Keon-Bo;Ahn, Chung-Hoon;Kim, Kyu-Sam
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2004.05a
    • /
    • pp.451-455
    • /
    • 2004
  • Although DC ground resistance is a good index of performance for a grounding system, it does not reflect the grounding performance during the transient states. Besides, impulse ground impedance, which is defined by a ratio of the peak value of transient ground potential rise to the peak value of impulse current, cannot be an absolute performance index due to its dependence on impulse current shape. In this paper, a grounding performance of needle-typed ground rod has been compared with simple ground rod.

  • PDF

Characteristic of organic/inorganic composite formed grounding resistance lowering agents (유/무기 복합재료형 접지저감제의 특성)

  • Kim, Jang-Wook;Chung, Chul-Hee;Cho, Dae-Hoon
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2004.05a
    • /
    • pp.74-80
    • /
    • 2004
  • Among inorganic materials, it is grounding resistance lower agent of new form that use being strata style clay and makes using water soluble polymer by main material to organic substance. Water soluble polymer chains are dispertion in water because water soluble polymer reacts with water if is done and these discrete polymer chains are inserted to floor of being strata style clay with water. This material that moisture content is very excellent and rate of expansion, electrical conductivity that measure after supplies water of 300wt % as well as is excellent. Can prevent corrosion or electrolytic corrosion of grounding bar securing very environmentally, chemically and pollution of soil. When applied to general grounding rod worker $7{\sim}8$ times ground resistance reduction effect of not application.

  • PDF

Characteristics of Transient Grounding Impedances of Counterpoises Relevant to the Injected Point of Impulse Currents (임펄스전류의 인가위치에 따른 매설지선의 과도접지임피던스 특성)

  • Li, Feng;Jung, Dong-Chul;Kim, Jong-Ho;Yoo, Jae-Duk;Kim, Dong-Kyu;Lee, Bok-Hee
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.24 no.5
    • /
    • pp.62-69
    • /
    • 2010
  • This paper presents the dependances of transient grounding impedances of counterpoises on the soil structures and the injected point of impulse currents. The transient and conventional grounding impedances of the 25 and 50[m] counterpoises buried in the soil with different resistivity were measured and analyzed as a function of the rise time of impulse currents. As a result, the transient grounding impedances give an inductive behavior, and the trend of the conventional grounding impedances is similar to that of the transient grounding impedances. The ground resistance of counterpoises is irrespective to the injected of impulse current, but the transient and conventional grounding impedances in a short time range especially depend on the soil resistivity and position of the injected point of impulse currents.

Research for the Substitutional Grounding Electrode in the Foundation of the House (주택기초의 대용 접지극에 관한 연구)

  • Kim, Sung-Sam;Lee, Chung-Sik;Choi, Jong-Kyu;Kim, Ju-Chan;Koh, Hee-Seog
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2005.05a
    • /
    • pp.355-358
    • /
    • 2005
  • The electrical characteristics for applying the foundation of the house to the substitutional earth electrode was reviewed fundamentally. In order to measure the earth resistance in the foundation of the house, it was performed to investigate the effect of the electrode arrangements and configurations concerning to grounding methods, and tried to the adequate simulation for comparing those experimental data. The number of steel rods and the ground resistivity were affected to change the earth resistance, but the latter caused the large variation in its resistance compared to the former in this experiment. Since the large surface area in the foundation of the house have contacted the ground usually, it is possible to use the earth electrode substitutionally.

  • PDF