• Title/Summary/Keyword: grounding resistance

Search Result 246, Processing Time 0.023 seconds

Presumption for Reduced Scale Model of Mesh Electrod (메쉬접지전극의 축척모형에 관한 추정)

  • Koh, Hee-Seog;Kim, Ju-Chan;Lee, Chung-Sik;Choi, Jong-Kyu
    • Proceedings of the KIEE Conference
    • /
    • 2002.06a
    • /
    • pp.29-33
    • /
    • 2002
  • There are a lot of errors and little accuracy when calculating the grounding resistance with the transposition methods in the equivalent surface of hemisphere electrode. Therefore we should calculate the grounding resistance by using the mesh factor, In this paper, we would estimate the grounding value of mesh electrode with water tank model & estimation method using the reduced scale ratio of mesh electrode based on the theory of model electrode & proportional factor according to the reduced scale ratio. And also we have confirmed the accuracy of the empirical formula of model electrode by using the regression analysis.

  • PDF

Effects of Soil Resistivity on the Grounding Characteristics (대지 저항률이 접지 특성에 미치는 영향)

  • Jung, Yeon-Ha;Jang, Tae-Jun;Kwak, Hee-Ro;Roh, Young-Su;Choi, Chung-Seog
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.19 no.5
    • /
    • pp.74-79
    • /
    • 2005
  • In this paper the earth structures of four cities are analysed on the basis of the measured soil resistivity and the characteristics of a grounding system is examined. As a result it is revealed that the soil resistivity has an effect on touch voltage and step voltage, which are directly related to safety, as well as ground resistance.

An Analysis of Potential Interference Effects in the Vicinity of Ground Rod Depending on Frequency of Ground Currents (접지전류의 주파수에 따른 수직 접지전극 주변에서 전위간섭 영향 분석)

  • Lee, Bok-Hee;Cho, Yong-Seung;Choi, Jong-Hyuk;Yang, Soon-Man
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.25 no.12
    • /
    • pp.88-93
    • /
    • 2011
  • When the ground current is injected into the adjacent ground electrode, the potential interference is caused between ground electrodes, the ground potential interferences have been largely studied with power frequency fault currents. Many attempts to find the frequency-dependent grounding impedance report that the high frequency grounding impedance is very different with the ground resistance. This paper presents experimental data on the frequency-dependent potential interference effects in the vicinity of ground rod. The ground potential rises around the test ground rod of 4 or 6[m] were measured and discussed. As a result, the ground potential rises and potential interference factor are decreased with decreasing the grounding impedance. It was found that the lowering of grounding impedance is critical to reduce the ground potential interference effects.

Effects of Maximum Probe Spacing of Wenner Method on Substation Grounding (변전소 접지설계를 위한 대지저항율 측정시 전극간격이 해석결과에 미치는 영향)

  • Choi, J.K.;Kee, H.C.;Jung, G.J.;Kim, B.J.
    • Proceedings of the KIEE Conference
    • /
    • 1999.07e
    • /
    • pp.2355-2357
    • /
    • 1999
  • Estimating equivalent soil model which represents an actual soil structure and its electrical characteristics, is extremely improtant for good substation grounding system design and analysis. Since the equivalent soil model is deduced based on the measured apparent soil resistivity - generally obtained from Wenner's 4-point method, reasonable and accurate measuring technique and procedure guarantee good grounding system design and analysis. The paper aims to show the importance of reasonable enough probe spacing by presenting the influence of soil modelling to estimation and measurement of grounding resistance of substation grounding grid.

  • PDF

Charicteristics of Stationary and Transient Ground Impedance of Large-Scale Grounding Piles (임펄스 전류에 대한 대규모 접지시스템의 정상상태 및 과도상태의 접지임피던스 특성)

  • Lee, B.H.;Lee, S.C.;Park, J.S.
    • Proceedings of the KIEE Conference
    • /
    • 1999.07e
    • /
    • pp.2296-2298
    • /
    • 1999
  • The stationary ground resistance and the transient ground impedance of grounding system are very important parameters in the field of lightning and surge protection. But, it is very difficult to obtain correct values of them in large-scale grounding system. In this paper, the stationary and transient ground impedances of a large-scale grounding system have been measured and analyzed under impulse currents. In order to obtain correct values of them, we have described Z-v(impedance vs ground potential rise) distributions and Z-t waveforms. The transient ground impedance of 36 [m] long three-parallel grounding piles have showed the inductive aspects and the hysterisis region under impulse currents.

  • PDF

Analysis of Lightning Overvoltage with Earth of Overhead Grounding Wire and Installation Types of Arrester in Double Circuits Distribution Systems (2회선 배전계통에서 가공지선 접지 및 피뢰기 설치환경에 따른 뇌과전압 해석)

  • Jung, Chae-Kyun;Kim, Sang-Kuk;Lee, Jong-Beom;Jeong, Yeong-Ho
    • Proceedings of the KIEE Conference
    • /
    • 2003.07a
    • /
    • pp.497-499
    • /
    • 2003
  • This paper analyses the lightning overvoltage with earth of grounding wire and installation types of arresters in double circuits distribution systems. First, the model for analysis is selected severer case between upper line and lower line when the direct lightning surge strikes on the overhead grounding wire. The lightning overvoltage is variously calculated with earth distance between overhead grounding wires. This paper also analyses the effect of the installation distance between arrestors and the earth resistance of overhead grounding wire. From these results, authors examine the rationality of BIL that is applied in distribution system.

  • PDF

Simulated Analysis for the Transient Impedance Behaviors of Counterpoises Subjected to the Impulsive Currents (임펄스전류에 의한 매설지선의 과도임피던스특성에 대한 모의해석)

  • Joe, Jeong-Hyeon;Lee, Bok-Hee
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.58 no.10
    • /
    • pp.1861-1868
    • /
    • 2009
  • A ground electrode subjected to lightning surge current shows the transient impedance behaviors. The ground electrode for protection against lightning should be evaluated in view of the transient grounding impedance and conventional grounding impedance, not ground resistance. The transient impedance characteristics of ground electrodes are influenced by the shape of ground electrode and the soil characteristics, as well as the waveform of lightning surge current. In order to propose a simulation method of analyzing the transient impedance characteristics of the grounding system in practical use, this paper suggests a theoretical analysis method of distributed parameter circuit model to simulate the transient impedance characteristics of counterpoise subjected to lightning surge current. EMTP and Matlab programs were employed to compute the transient grounding impedances of three counterpoises with different lengths. As a consequence, the simulated results using the proposed distributed parameter circuit model are in good agreement with the measured results.

Measurement and Analysis of Frequency Characteristics of Grounding Systems (접지시스템 주파수 특성의 측정과 해석)

  • 최종기;안용호;구선근;박기준;윤진열;정길조;류보혁;김정훈
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.53 no.5
    • /
    • pp.248-252
    • /
    • 2004
  • Since DC ground resistance, which is a good index of the performance of a grounding system in low frequency. does not show the performance in transient state. We measured ground impedances in frequency domain ranging from 0.1 Hz to 900 KHz maximum to quantify the transient grounding performance of 4 types of grounding system. Transfer function was derived from the measured frequency-dependant ground impedance of a grounding grid. A simulation has been performed to verify the transfer function using EMTP (Electro-Magnetic Transient Program).

Voltage Quality Analysis in Power Distribution System with Superconducting Fault Current Limiter at Grounding Line (초전도 한류기를 주변압기 접지선에 설치시 배전계통의 순간전압품질 분석)

  • Moon, Jong-Fil
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.62 no.4
    • /
    • pp.159-163
    • /
    • 2013
  • In this paper, voltage quality improvement is analyzed in case of Superconducting Fault Current Limiter (SFCL) installed in grounding line of main transformer in power distribution system. First, a resistive-type SFCL model is used. Next, Korean power distribution system is modeled. Finally, when SFCL is installed in the starting point of feeder and grounding line of main transformer, voltage qualities are evaluated according to various fault locations and resistance values of SFCL using PSCAD/EMTDC. The voltage quality results in case of grounding line are compared with the voltage in case of feeder.

Study on the Between the Grounding Resistance and Grounding Electrode using Mesh Grounding Electrodes and a Shielding Panel (메쉬접지전극과 차폐패넬을 이용한 접지저항 및 접지전극간의 영향에 관한 연구)

  • Leeg, Chung-sik;Cho, Moon-taek;Na, Seung-kwon
    • Journal of Advanced Navigation Technology
    • /
    • v.19 no.3
    • /
    • pp.230-236
    • /
    • 2015
  • In this paper, the electric potential of electrode surface is investigated by assuming them as two dimensional sets of point current sources. And, the simulated water tank is manufactured as a reduced scale of the earth. Henceforth, the adequate model electrode for test is decided to decrease experimental errors relevant to the limitation of the size of the water tank. The one of important things of this work, the deduction method of the potential interference factor is proposed, which used as the criterion of the potential interference according to the shape of conductors and the laying conditions, when multiple grounding conductors are situated at the same resistance grounding area. Also, the validity of this theory is verified from a numerical simulation of the grounding electrode to be used in experiments, and this study is realized by the verified theory and the simulated experiments.