• Title/Summary/Keyword: geothermal heating and cooling

Search Result 185, Processing Time 0.022 seconds

Economic Analysis of Cooling-Heating System Using Ground Source Heat in Horticultural Greenhouse (시설원예의 지열냉·난방시스템 경제성 분석)

  • Ryoo, Yeon-Su;Joo, Hye-Jin;Kim, Jin-Wook;Park, Mi-Lan
    • Journal of the Korean Solar Energy Society
    • /
    • v.32 no.6
    • /
    • pp.60-67
    • /
    • 2012
  • Government Geothermal Cooling-Heating Projects has made efforts to reduce GHG(Greenhouse Gas) emissions and to manage cost of greenhouse farm households. This study evaluated the economic benefits of heating load rate of change by comparing Geothermal Cooling-Heating System with the existing system(greenhouse diesel heating) in the Government Geothermal Cooling-Heating Projects. Economic analysis results shows that, 1) When installing the Cooling-Heating system according to the ratio of 70% heating load in policy standards, the geothermal cooling-heating system has economic efficiency with greenhouse type or scale independent because the investment cost is recovered within 7 years. And It was more economic efficiency the ratio of 50% heating load than70% heating load. 2) When installing the Cooling-Heating system according to the glass greenhouse of the ratio of 90% heating load, pay period of investment cost is recovered within 5 years. Therefore it is necessary to apply flexible heating sharing according to greenhouse type or scale.

Heating and Cooling Effect of Portected Horticulture by Geothermal Heat Pump System with Horizontal Heat Exchanger (수평형 지열히트펌프 시스템의 시설원예 냉난방 실증 효과)

  • Ryou, Young-Sun;Kang, Youn-Ku;Kim, Young-Jung;Kang, Keun-Chun
    • 한국신재생에너지학회:학술대회논문집
    • /
    • 2008.05a
    • /
    • pp.630-633
    • /
    • 2008
  • Geothermal heat pump systems use the earth as a heat source in heating mode and a heat sink in cooling mode. These systems can be used for heating or cooling systems in farm facilities such as greenhouses for protected horticulture, cattle sheds, mushroom house and etc. A horizontal type means that a geothermal heat exchanger is laid in the trench buried in 1.2 to 1.8 m depth. Because a horizontal type has advantages of low installation, operation and maintenance costs compared to a vertical type, it is easy to be adopted to agriculture. In this study, to heat and cool farm facilities and obtain basic data for practical application of horizontal geothermal heat pump system in agriculture, a horizontal geothermal heat pump system of 10 RT was installed in greenhouse. Heating and cooling performance of this system was estimated. The horizontal geothermal heat pump used in this study had heating COP of 4.57 at soil temperature of $14^{\circ}C$ with depth of 1.75m and heating COP of 3.75 at soil temperature of $7^{\circ}C$ with the same depth. The cooling COP was 2.7 at ground temperature at 1.75m depth of $25.5^{\circ}C$ and 2.0 at the temperature of $33.5^{\circ}C$.

  • PDF

Comparative Analysis of Energy Performance of Hydrothermal, Geothermal Source and Hybrid Heat Pump System According to Internal Heat Load for Office, School and Smart Farm (건축물 용도별 내부 발열부하에 따른 수열원, 지열원 및 하이브리드 히트펌프 시스템의 에너지 성능 비교 분석)

  • Park, Sihun;Min, Joonki
    • Journal of the Korean Society for Geothermal and Hydrothermal Energy
    • /
    • v.18 no.3
    • /
    • pp.19-30
    • /
    • 2022
  • In this study, comparative analysis of energy performance in Taebaek city, a test area, by applying hydrothermal, geothermal source and hybrid heat pump system to office, school and smart farms with different internal heat loads. The conclusion is as follows. In the load characteristics by use of buildings, it was found that office had a large cooling load compared to heating load, school had a large heating load compared to cooling load, and smart farm had only cooling load year-round. Performance analysis of the heat pump system in office shows that the cooling COP of the hydrothermal source is 5.12% and the heating COP is 3.22% lower based on the geothermal source, the cooling COP of the hybrid is 0.41% higher, and the heating COP is the difference in performance appeared sparsely. The performance analysis of the heat pump system in school showed that the cooling COP of the hydrothermal source was 10.44% and the heating COP 3.22% lower based on the geothermal source, and the performance difference between the hybrid cooling and heating COP was insignificant. Heat pump system performance analysis in smart farm only occurred with cooling load. Based on geothermal sources, the cooling COP of the hydrothermal source was 46% and the cooling COP of the hybrid was 19.65%, respectively.

A method for Application of Hybrid Geothermal Cooling-Heating System in Multi Family Apartment (공동주택용 하이브리드 지열 냉난방 시스템의 적용추진 전략)

  • Park, Yong-Boo;Park, Jong-Bae;Kim, Gil-Tae
    • Proceedings of the Korean Geotechical Society Conference
    • /
    • 2009.09a
    • /
    • pp.1447-1454
    • /
    • 2009
  • Currently, geothermal heat pump systems are being installed in new official and commercial building, welfare facilities, and school but there are a few cases for the housing heat sink in Korea. The reason is that there are no progressive taxes for the household electrical use, no actual output for the application of geothermal technology, high initial investment. For the overall use in multi family apartment such as the Green Home etc, technology development and building of the relevant research team need to be done through preliminary study. Core subjects for overall use include cooling heating load estimation for the multi family apartment, economical efficiency of the geothermal cooling and heating system, design and construction technology of the geothermal cooling and heating system for the multi family apartment, commercialization plan, and state of the art analysis. Selection of the detailed subjects with respect to core subject, driving schedule and commercialization plan, driving system, presentation of the utilization plan.

  • PDF

Performance Prediction of Geothermal Heat Pump System by Line-Source and Modified DST(TRNVDSTP) Models (선형열원 모델과 수정 DST(TRNVDSTP) 모델에 의한 지열 히트펌프 시스템 성능 예측)

  • Sohn, Byong-Hu
    • Journal of the Korean Society for Geothermal and Hydrothermal Energy
    • /
    • v.8 no.2
    • /
    • pp.61-69
    • /
    • 2012
  • Geothermal heat pump(GHP) systems have been shown to be an environmentally-friendly, efficient alternative to traditional cooling and heating systems in both residential and commercial applications. Although some experimental work related to performance evaluation of GHP systems with vertical borehole ground heat exchangers for commercial buildings has been done, relatively little has been reported on the performance simulation of these systems. The aim of this study is to evaluate the cooling and heating performance of the GHP system with 30 borehole ground heat exchangers applied to an commercial building($1,210m^2$) in Seoul. For this purpose, a typical design procedure was involved with a combination of design parameters such as building loads, heat pump capacity, circulating pump, borehole diameter, and ground effective thermal properties, etc. The cooling and heating performance prediction of the system was conducted with different prediction methods and then each result is compared.

An Experimental Study on the Effects of Operating Variables on the Cooling and Heating Performance of Geothermal Heat Pump (지열 히트펌프에서 운전변수가 냉난방 성능에 미치는 영향에 대한 실험연구)

  • Chang, Keun-Sun;Kang, Hee-Jeong
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.23 no.8
    • /
    • pp.562-570
    • /
    • 2011
  • In this research, an experimental study is performed to investigate the effects of system operating variables on the cooling and heating characteristics of heat pump system using geothermal heat source and carbon dioxide as a refrigerant. System variables analyzed include compressor frequency, electronic expansion valve opening, refrigerant charge, secondary fluid temperature and flow rate. Results show that optimum refrigerant charge and electronic expansion valve opening position exist at the maximum point of COP curve, and both cooling and heating capacity increase but COPs decrease with the increase of compressor frequency. The change of a secondary fluid temperature leads to variation of overheat area and enthalpy difference in the evaporator and gas cooler. which again results in considerable variations of cooling and heating capacity and COP. In the case of effects of secondary water fluid flow rate, both cooling capacity and COP increase with the increase of secondary flow in evaporator or gas cooler, whereas heating capacity and COP decrease with the increase of flow rate in gas cooler.

Effect analysis of geothermal cooling and heating system (지열(수온차)냉난방 시스템 효과 분석)

  • Chung, Hoon;Ma, Bum-Gu
    • 한국신재생에너지학회:학술대회논문집
    • /
    • 2008.10a
    • /
    • pp.365-368
    • /
    • 2008
  • This experiment is significant because we can provide information by measuring effect of energy saving for whom plan to install a geothermal heat & cooling system. The result shows geothemal system can save about 50% of energy(heating : 35%, cooling : 60%) and we verified that when using curtain can help saving $4{\sim}12%$ of energy additionally

  • PDF

Analysis on the Performance Evaluation Trends of Heat Pumps and the Test Standards of a Geothermal Heat Pump in Korea (히트펌프 성능 평가 동향과 국내 지열원 히트펌프 성능 평가 규격 및 제도 분석)

  • Kang, Shin-Hyung;Choi, Jong Min
    • Journal of the Korean Society for Geothermal and Hydrothermal Energy
    • /
    • v.13 no.4
    • /
    • pp.31-38
    • /
    • 2017
  • The heating and cooling air conditioning field has been increasing the problems of energy consumption and global warming in the world. A geothermal heat pump has been known as one of the highest efficient heating and cooling system. In this study, the analysis about the test standards of the geothermal heat pump of the Republic of Korea was executed. From the research, the following results were given. It is needed to address the domestic test standard for direct heat exchange geothermal heat pump. Water to air multi geothermal heat pump test standard was only developed in Korea. The test standard to calculate a seasonal energy efficiency ratio for cooling period and heat seasonal performance factor for heating period should be newly developed to estimate actual annual energy consumption and $CO_2$ emission.

An Experimental Study on the Load Delivery Characteristics of Hybrid Energy System with Geothermal and Solar Heat Sources (지열-태양열원 복합시스템의 부하추종특성에 관한 실험 연구)

  • Hwang, In-Ju;Woo, Nam-Sub
    • Journal of the Korean Society for Geothermal and Hydrothermal Energy
    • /
    • v.2 no.2
    • /
    • pp.1-8
    • /
    • 2006
  • The objective of the present study is to investigate the load delivery characteristics of a hybrid-renewable energy system with geothermal and solar heat sources for hot water, heating and cooling of a residential house in Korea. The hybrid energy system consists of ground source heat pump of 2 RT for cooling with a 150 m vertical U-bend ground heat exchanger, solar collectors of 4.8 m2 and gas fired backup boiler. The averaged coefficient of performance of geothermal module during cooling and heating seasons are evaluated as about 4.5 and 3.8, respectively.

  • PDF

Performance for Geothermal Heating & Cooling System by Heatpump in Office Building (사무용건물에서 지열히트펌프냉난방시스템의 운전성능 평가)

  • An, Hyung-Jun;Baek, Sung-Kwon;Cho, Chung-Sik;Sohn, Byung-Hu
    • Journal of the Korean Society for Geothermal and Hydrothermal Energy
    • /
    • v.3 no.1
    • /
    • pp.23-29
    • /
    • 2007
  • For the perfomance test of geothermal system, a large pilot of capacity of 50RT is built and operated in office building. This system is planed hybrid system with cooling tower as asisstance heat sink. From October, 2004 to September, 2005, this system is operated andmonitored. As the result, COP of heating periods is about 3.46 and COP of cooling periods is about 4.1. Therefore, geothermal system is useful and suitable in Korea.

  • PDF