• 제목/요약/키워드: gas insulation

검색결과 539건 처리시간 0.026초

$SF_6$와 액체 질소의 절연파괴특성과 정기포현상 (The Positive Bubble Effect and the Breakdown Characteristics in $SF_6$ and $LN_2$)

  • 이광식;최은혁;박광서;김종환;임창호
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제54권8호
    • /
    • pp.355-360
    • /
    • 2005
  • In this paper the experiments of breakdown characteristics by temperature change of $SF_6$ gas, $SF_6$ liquid ($LSF_6$) and $N_2$ liquid ($LN_2$) in model GIS(Gas Insulated Switchgear) were described. From the experiments results, the breakdown voltage of $SF_6$ increases with the drop of temperature and the increase of the inner pressure in model GIS. The ability of $LSF_6$ insulation is higher than high-pressurized $SF_6$ gas and $LN_2$. The breakdown characteristics of $LSF_6$ were produced by bubble formed evaporation of $LSF_6$ and bubble caused by high electric emission. It is considered in this paper that the results are fundamental data for electric insulation design of superconductor and cryogenic equipments machine교 which will be studied and developed in the future.

(-)전압 인가시 액체 $SF_6$의 전극형상에 따른 절연파괴특성 (The discharge characteristics for various electrode shapes under negative high-voltagein in Liquid $SF_6$)

  • 최은혁;박광서;김이국;이광식;도대호;김종환
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2005년도 제36회 하계학술대회 논문집 C
    • /
    • pp.2085-2087
    • /
    • 2005
  • In this paper the experiments of insulation characteristics by temperature change of $SF_6$ gas and liquid $SF_6$ in model GIS(Gas Insulated Switchgear) were described. From this results, the breakdown voltage was increased with a drop of temperature and an increase of the inner pressure in model GIS. The ability of insulation in liquid $SF_6$ was higher than that of the highly pressurized $SF_6$ gas. A liquid $SF_6$ discharge characteristics was caused by bubble formed evaporation of liquid $SF_6$ and bubble caused by high electric emission. It is considered that these result are fundamental data for electric insulation design of superconductor and cryogenic application machinery which will be studied and developed in the future.

  • PDF

유침 절연에서 전기적 및 열적 열화에 따른 유중가스분포특성 (Characterisrics of Dissolved Gas Distribution in Oil with Thermal and Electrical Degradation in Oil Imersed Paper Insulation)

  • 선종호;이상화;김광화
    • 조명전기설비학회논문지
    • /
    • 제18권6호
    • /
    • pp.136-144
    • /
    • 2004
  • 본 논문에서는 유침절연에 대한 열열화와 전기적열화 실험을 실시하여 유중가스분석법을 이용한 유침절연의 고장원인 진단에 대한 신뢰성을 향상시키는 방안에 대하여 연구하였다. 유침절연의 고장원인에 대하여 주도가스법과 탄화수소가스의 구성률, CO/$CO_2$비와 같은 진단요소를 단독으로 사용하는 것보다는 진단요소들의 상호관계를 이용하는 것이 유침절연의 고장원인을 신뢰성 있게 진단하는 것으로 나타났다.

KC-1 Membrane LNG 탱크 단열시스템의 열해석에 관한 연구 (Thermal Analysis of Insulation System for KC-1 Membrane LNG Tank)

  • 정현원;김태현;김석순;심재우
    • 한국해양공학회지
    • /
    • 제31권2호
    • /
    • pp.91-102
    • /
    • 2017
  • Recently, a new type of LNG membrane Tank called the "KC-1 membrane LNG Tank" was developed by KOGAS (Korean Gas Corporation). It is necessary to estimate the temperature distribution of the hull structure and insulation system for this new LNG tank, as well as the BOR (Boil-Off Rate) when exposed to outside temperature conditions to ensure the integrity of the tank structure and limit LNG evaporation, from a safety evaluation point of view. In this study, temperature distribution calculations for the hull structure and insulation system of the KC1 membrane tank were compared by employing four numerical approaches under the IGC condition. Approaches 1-3 studied 2D simulations and approach 4 used a 3D numerical simulation. Approach 1 was calculated by in-house Excel VBA codes and the three other approaches utilized ANSYS Fluent. The BOR of approach 4, the 3D simulation case, for the IGC condition was 0.0986%/day.

TEV 검출에 의한 가스 절연 개폐기의 절연 진단 (Insulation Diagnosis of Gas-Insulated Switchgears by TEV Detection)

  • 공정배;길경석;김성욱
    • 한국전기전자재료학회논문지
    • /
    • 제32권4호
    • /
    • pp.307-312
    • /
    • 2019
  • Transient earth voltage (TEV) signals propagate on metal surfaces when partial discharge (PD) occurs due to the deterioration of insulation performance in the operation of gas-insulated switchgears (GIS). A TEV sensor has advantages of high sensitivity and convenient installation for detecting PD defects. However, the TEV sensor depends on imports in domestic and detailed studies have not been conducted. In this study, a sensor was designed and fabricated by the TEV principle and its response characteristics were evaluated for detecting PD defects, which were simulated as protrusion on conductor (POC), protrusion on enclosure (POE), and free moving particle (FMP) defects. Finally, the PD-induced TEV signals were measured and phase-resolved partial discharge (PRPD) patterns were analyzed to identify the type of defect.

단열 진공유리의 제작 및 열전달계수 측정에 관한 실험적 연구 (Experimental Study on Manufacturing of Insulation Vacuum Glazing and Measurement of the Thermal Conductance)

  • 이보화;윤일섭;곽호상;송태호
    • 대한기계학회논문집B
    • /
    • 제30권8호
    • /
    • pp.772-779
    • /
    • 2006
  • Window is a critical component in the design of energy-efficient buildings. To minimize the heat loss, insulation performance of the glazing has to be improved. Manufacturing of vacuum glazing has been motivated by the possibility of making windows of very good thermal insulation properties for such applications. It is made by maintaining vacuum in the gap between two glass panes. Pillars are placed between them to withstand the atmospheric pressure. Edge covers are applied to reduce conduction through the edge. Accurate measurements have been made of the radiative heat transfer, the pillar conduction and the gas conduction using a guarded hot plate apparatus. Vacuum glazing is found to have low thermal conductance roughly below $1W/m^2K$. Among the heat transfer modes of residual gas conduction, conduction through support pillar and the radiative heat transfer between the glass panes, the last one is the most dominant to the overall thermal conductance. Vacuum glazing using very low emittance AI-coated glass has an overall thermal conductance of about $0.7W/m^2K$.

Damping Effect of Reinforced Polyurethane Foam under Various Temperatures

  • Lee, Tak-Kee;Kim, Myung-Hyun;Rim, Chae-Whan;Chun, Min-Sung;Suh, Yong-Suk
    • International Journal of Ocean System Engineering
    • /
    • 제1권4호
    • /
    • pp.230-235
    • /
    • 2011
  • Reinforced polyurethane foam (RPUF) is one of the important materials of Mark III type insulation systems used in liquefied natural gas (LNG) cargo containment systems. However, RPUF is the most difficult material to use with regard to its safety assessment, because there is little public and reliable data on its mechanical properties, and even some public data show relatively large differences. In this study, to investigate the structural response of the system under compressive loads such as sloshing action, time-dependent characteristics of RPUF were examined. A series of compressive load tests of the insulation system including RPUF under various temperature conditions was carried out using specimens with rectangular section. As a result, the relationship between deformation of RPUF and time is linear and dependent on the loading rate, so the concept of strain rate could be applied to the analysis of the insulation system. Also, we found that the spring constant tends to converge to a value as the loading rate increases and that the convergence level is dependent on temperature.

단열재 개선을 통한 PKG-A Water Jet Room 온도저감 연구 (A Study on the Internal Temperature Reduction of PKG-A Water-jet-room by Substituting Heat Insulation Materials)

  • 정영인;최상민
    • 품질경영학회지
    • /
    • 제47권3호
    • /
    • pp.425-435
    • /
    • 2019
  • Purpose: The purpose of this study was to resolve the Naval ship's Local Operation Panel(LOP) malfunction problems which caused by overheating in summer season and dispatching to equatorial regions. Methods: Instead of using dual type heat insulation materials(consist with ceramic wool and glass wool), aerogel heat insulation materials were used for decreasing heat emissions from gas-turbine heat waste steam pipes passing water-jet- room. Experiment and Computational analysis of heat flow were conducted to analyze the internal room temperature changes. Results: The results of this study are as follows; The aerogel heat insulation materials suppress heat emission more efficiently than dual type insulation materials. The cold surface temperature of insulation was far more decreased and internal room, LOP surface temperature also showed significant results too. Conclusion: The substituted heat insulation materials appeared remarkable performance in decreasing room temperature that it could be used for suppressing the LOP overheatings and malfunctions.

선형회귀법을 이용한 절연유에 용존된 furfural과 CO, CO2 가스 함유량 간의 상관관계 분석 (Analysis for Correlation Between Furfural and CO, CO2 Gas Dissolved Inside Insulating Oil using Linear Regression Method)

  • 김재훈;박두기;한상옥
    • 전기학회논문지P
    • /
    • 제59권2호
    • /
    • pp.212-217
    • /
    • 2010
  • When paper which was applied as insulation in oil-filled transformer was aged by thermal, its electrical, mechanical and chemical characteristics were changed and deteriorated. Therefore operating temperature was more higher, damage of paper was more quicker. Insulating paper which was generally made with cellulose was degraded, polymer of long length chain was decomposed as a monomer and CO, $CO_2$ gas and/or by-product such as furfural was produced from paper at the same time. In according with detection these gas and furfural by dissolved gas analysis(DGA) and high performance liquid chromatography(HPLC), we have investigated effects of CO, $CO_2$ gas and furfural on insulation of paper. Also we have analyzed for correlation between furfural and CO, $CO_2$ gas using linear regression method that was known as useful, credible statistical analysis.