• Title/Summary/Keyword: flameproof

Search Result 10, Processing Time 0.024 seconds

Relationship Analysis between Relative Humidity and Explosion Pressure of Hydrogen-Air and Acetylene-Air Mixtures in Flameproof Enclosure (내압방폭구조에서 수소-공기와 아세틸렌-공기 혼합가스의 폭발압력과 상대습도의 상관관계 분석)

  • Yong-Tae, Kim;Kihyo, Jung
    • Journal of the Korea Safety Management & Science
    • /
    • v.24 no.4
    • /
    • pp.101-107
    • /
    • 2022
  • To test a flameproof enclosure for the safety certificate, a reference pressure of explosion needs to be determined. However, the explosion pressure may be changed according to relative humidity of explosive gases. Therefore, the guideline on relative humidity should be recommended for measuring the explosion pressure for accurate and reproducible testings. This study examined the relationship of explosion pressure with relative humidity of hydrogen (31 vol %)-air and acetylene (14 vol %)-air mixture gases. The explosion pressures were measured by increasing the relative humidity of the gases by 10 % from dry state to 80 % in a cylindrical explosion enclosure of 2.3 L. on ambient temperature and atmospheric pressure (1 atm). The maximum explosive pressures were remained almost constant until the relative humidity reached 10 % for the hydrogen-air mixture and 20 % for the acetylene-air mixture. However, the maximum explosive pressures linearly decreased as the relative humidity increased. Based on the results of the study, it would be recommended to use 10 % relative humidity for the hydrogen-air mixture and 20 % for the acetylene-air mixture as the critical value in testing a flameproof enclosure.

Effect of Relative Humidity on Explosion Pressure for Gas Group IIB, IIA, and I (상대습도에 따른 가스 그룹 IIB, IIA, I의 폭발압력 분석)

  • Yongtae Kim;Kihyo Jung
    • Journal of the Korea Safety Management & Science
    • /
    • v.25 no.1
    • /
    • pp.51-58
    • /
    • 2023
  • Determination of explosion reference pressure is important in designing and testing flameproof enclosures (Ex d). Although relative humidity affects to explosion pressure, its effect is not well investigated for the gas group IIB, IIA, and I. This study tested explosion pressure for Ethylene (8 vol.%), Propane (4.6 vol.%), and Methane (9.8 vol.%), which are the representative gas of the gas group IIB, IIA, and I, at ambient temperature and atmospheric pressure (1 atm) under different relative humidity (0% ~ 80%). Ethylene- and Propane-air mixed gases generally tended to decrease as the relative humidity increased; however, explosion pressure was largely dropped at 20% of relative humidity compared to 0% and 10% of relative humidity. On the other hand, Methane-air mixture gas showed similar pressures at 0% and 10% of relative humidity; but no explosion occurred at more than 20%. The results of this study can be used in setting a testing protocol of explosion reference pressure for designing and testing a flameproof enclosure.

A Study on the MESG of Flammable Ternary Gas Mixtures (3성분계 인화성 혼합가스의 MESG에 관한 연구)

  • Hwang, Kyungyong;Byeon, Junghwan;Rhee, Kyunam;Lee, Taeck-Kie
    • Journal of the Korean Institute of Gas
    • /
    • v.20 no.3
    • /
    • pp.30-37
    • /
    • 2016
  • Electrical apparatuses for use in the presence of flammable gas atmospheres have to be specially designed to prevent them from igniting the explosive gas. Flameproof design implies that electrical components producing electrical sparks are contained in enclosures and withstand the maximum pressure of internal gas or vapours. In addition, any gaps in the enclosure wall have to designed in such a way that they will not transmit a gas explosion inside the enclosure to an explosive gas or vapours atmosphere outside it. In this study, we explained some of the most important physical mechanism of MESG(Maximum Experimental Safe Gap) that the jet of combustion products ejected through the flame gap to the external surroundings do not have an energy and temperature large enough to initiate an ignition of external gas or vapours. We measured the MESG and maximum explosion pressure of ternary gas mixtures(propane-acetylene-air) by the test method and procedure of IEC 60079-20-1:2010. As a result, the composition of propane gas that has lower explosive power than acetylene gas in the ternary gas mixtures makes greater effects on MESG and explosion pressure.

A Study on the Correlation of MESG and Explosion Pressure (최대실험안전틈새(MESG)와 폭발압력의 상관관계에 대한 연구)

  • Hwang, Kyungyong;Shin, Woonchul;Lee, Taeck-Kie
    • Journal of the Korean Institute of Gas
    • /
    • v.20 no.1
    • /
    • pp.29-39
    • /
    • 2016
  • Electrical apparatuses for use in the presence of explosive gas atmospheres have to be special designed to prevent them from igniting the explosive gas. Flameproof design implies that electrical components producing electrical sparks are contained in enclosures and withstand the maximum pressure of internal gas or vapours. In addition, any gaps in the enclosure wall have to designed in such a way that they will not transmit a gas explosion inside the enclosure to an explosive gas or vapours atmosphere outside it. In this study, we explained some of the most important physical mechanism of Maximum Experimental Safe Gap(MESG) that the jet of combustion products ejected through the flame gap to the external surroundings do not have an energy and temperature large enough to initiate an ignition of external gas or vapours. We measured the MESG and maximum explosion pressure of propane and acetylene by the test method and procedure of IEC 60079-20-1:2010.When the minimum MESG is measured, the concentration of propane, acetylene in the air is higher than the stoichiometric point and their explosion pressure is the highest value.

Electrical Machines and Drives for Potentially Explosive Atmospheres

  • Grantham, Colin
    • Journal of international Conference on Electrical Machines and Systems
    • /
    • v.1 no.1
    • /
    • pp.128-134
    • /
    • 2012
  • This paper gives an overview of the requirements for electrical equipment in potentially explosive atmospheres and describes how these are applied to electrical machines and drives in hazardous areas. The method by which equipment can be shown to be safe in a whole range of gases, by testing in a single test gas, is covered. It is shown how the more recently introduced methods of protection for hazardous areas, increased safety and nonsparking, are ideally suited to AC machines and drives. A novel method of measuring the fullload temperature rise of electrical machines for hazardous, and other areas, without the need to connect a mechanical load to the machine's drive shaft is explained.

Effect of Electrode Material on the Minimum Ignition Energy in Low-Voltage Spark Discharge (저압방전 불꽃에서 전극재질이 점화에너지에 미치는 영향)

  • Choi, Sang-Won;Lee, Gwan-Hyung;Moon, Jung-Gi
    • Proceedings of the KIEE Conference
    • /
    • 1995.07c
    • /
    • pp.1394-1397
    • /
    • 1995
  • In the hazardous areas where explosive gases, vapor or mists exist, electrical apparatus and installations must be of explosion-proof construction to prevent or limit the danger of the ignition of potentially explosive atmosphere. In Korea, nine types of protection have been specified in the government regulations at present: flameproof enclosure, pressurization, oil immersion, increased safety, intrinsic safety, non-incendive, sand filling, encapsulation, and special types. Among these types, the intrinsic safety has the construction which limit or by-pass igniting the electric energy using electronic devices. This type has lots of merits but at the same time requires a high-degree of technology. In this paper, we investigated several dominating factors which affect the minimum ignition energy: this energy plays a very important role in design and evaluation of the intrinsic safety type electrical apparatus. Eletrode material, which is one of the most important factors, was intensively studied for the five sorts of material(Al, Cd, Mg, Sn, and Zn) with performing experiment in a low-voltage inductive circuit using IEC-type spark apparatus. The experimental results show that the minimum ignition energy of electrode material is varied: highest in Cd and lowest in Sn. We also confirmed the effect of eletrode make-and-break speed and magnetic field magnitude.

  • PDF

Constructional Properties and Evaluation Methods of the Non-Incendive Type of Explosion-Proof Electrical Apparatus (비점화(非點火)(Non-Incendive)형(型) 방폭(防爆) 전기기기(電氣機器)의 구조특성(構造特性) 및 평가방법(評價方法))

  • Choi, Sang-Won;Lee, Gwan-Hyung;Moon, Jung-Gi
    • Proceedings of the KIEE Conference
    • /
    • 1994.07a
    • /
    • pp.110-113
    • /
    • 1994
  • In the hazardous areas where explosive substances in the form of gases, vapor or mists exist, electrical apparatus and installations must be of explosion-proof construction to prevent or limit the danger of the ignition of potentially explosive atmosphere. In Korea, six types of protection have been specified in the government regulations at present: flameproof enclosure, pressurization, oil immersion, increased safety, intrinsic safety, and special types. If electrical apparatus are made of explosion-proof construction in a way other than five above-mentioned types, and their performance is tested and approved by the reponsible authorities, they may be categorized as special type apparatus. In this paper, we introduced a special type of explosion-proof electrical apparatus, called non-incendive type, and presented its constructional requirements. We also investigated evaluation methods of non-incendive type apparatus to assure the explosion-proof performance, and proposed a new classification method of hazardous areas using probabilistic concept.

  • PDF

Research of Novel Water Cooling Jacket for Explosion-proof Motor

  • Wang, Yu;He, Huiming;Bai, Baodong
    • Journal of international Conference on Electrical Machines and Systems
    • /
    • v.3 no.1
    • /
    • pp.67-71
    • /
    • 2014
  • The well tightness of the coal mining water-cooling explosion-proof motor results in difficult heat dissipation, high hydraulic pressure is needed to increase the cooling effect. However, high hydraulic pressure may lead motor shell to deform, which makes it difficult to change the motor and maintain the motor unit. The method of adding keyhole caulk weld spots on the outer cooling water jacket was proposed to solve the problem. Based on the elasticity mechanics equations and the principle of finite element method the stresses and the deformations of the traditional and novel outer cooling water jacket were calculated separately. A hydraulic pressure experiment of the both cooling water jackets was constructed. Obviously, the stress and the deformation of the novel cooling water jacket are lower. The experimental result is consistent with the simulation results. It is effective to reduce the stress and the deformation of the cooling water jacket by adding the keyhole caulk weld spots.

An Experimental Study on the Minimum Ignition Energy in Low Voltage Spark Discharge by Electrode Material (방전전극 재질과 최소점화에너지에 관한 실험 연구)

  • Choi, Sang-Won
    • Journal of the Korean Society of Safety
    • /
    • v.27 no.3
    • /
    • pp.63-70
    • /
    • 2012
  • In the hazardous areas where explosive gases, vapor or mists exist, electrical apparatus and installations must be the explosion-proof construction to prevent or limit the danger of the ignition of potentially explosive atmosphere. In Korea, nine types of protection have been specified in the government regulations at present: flameproof enclosure, pressurization, oil immersion, increased safety, intrinsic safety, non-incendive, powder filling, encapsulation, and special types. Among these types, the intrinsic safety has the construction which limit or by-pass igniting the electric energy using electronic devices. This type has lots of merits but at the same time requires a high-degree of technology. In this paper, we investigated several dominating factors which affect the minimum ignition energy; this energy plays a very important role in design and evaluation of the intrinsic safety type electrical apparatus. Electrode material, which is one of the most important factors, was intensively studied for the five sorts of material(Al, Cd, Mg, Sn, and Zn) with performing experiment in a low-voltage inductive circuit using IEC-type(International Electro-technical Commission) spark apparatus. The experimental results show that the minimum ignition energy of electrode material is varied: highest in Cd and lowest in Sn. We also confirmed the effect of electrode make-and-break speed.