• Title/Summary/Keyword: fire scenarios

Search Result 236, Processing Time 0.025 seconds

Fire Modeling and Smoking Control Characteristic Analysis of Electric Room by Using FDS (FDS를 이용한 전기실의 화재모델링 및 연기제어 특성 분석)

  • Choi, Jeong-A;Lee, Min-Gu;Lee, Dae-Dong
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.19 no.3
    • /
    • pp.662-668
    • /
    • 2018
  • Most electric rooms are located in the underground spaces of buildings. When a fire occurs in electrical equipment, the fire expands to cable insulation material, resulting in toxic smoke and combustion products. If the smoke and combustion products quickly move vertically and horizontally, the evacuation of occupants and firefighting activities will be hindered. Therefore, it is necessary to design optimal equipment for smoke control in cases of fires in electric rooms. This study analyzes the characteristics of smoke and combustion products in fires in a cubicle-type switchboard in an electric room using PyroSim, which is based on the program Fire Dynamics Simulator (FDS). The fire modeling consists of four scenarios according to the operation mode of the mechanical ventilation equipment, the amount of air supply and exhaust, and the location of the air supply slot. The analysis shows that the mechanical ventilation equipment improves the smoke density, visibility, carbon monoxide concentration, and temperature characteristics. The visibility and temperature characteristics were improved when the air flow rate and the location of the air supply slot from fire defense regulations were applied.

A Study on the Evacuation Risk of Simultaneous Fires from Exterior (외장재에 의한 동시다발적인 화재의 피난위험성에 관한 연구)

  • Min, Se-Hong
    • Fire Science and Engineering
    • /
    • v.26 no.4
    • /
    • pp.48-54
    • /
    • 2012
  • In order to study on the evacuation risk when connate fires caused by vertical fire spread of the exterior occurs, the egress simulations based on the relevant scenarios has carried out. As a result of it, ASET (permitted evacuation time) was reached in between 550 to 650 seconds in entire floors after vertical smoke spread from fire of combustible exteriors. In particular, ASET was 358 seconds in the first floor, 490 seconds in the six floor and 473 seconds in the tenth floor. In addition, five floors of all levels, the 1st floor, the 6th floor and the 28th floor ~30th floor, show RSET (minimum evacuation time) which is bigger than ASET as evacuation risk. This result presents occupants in high rise buildings with more than 15 floors might not be able to egress of them using staircases due to huge population attempting to evacuate simultaneously. Particularly, 699 people in the upper levels by smoke from the first floor are having difficulty escaping this building since ASET on the first floor adjacent to the ignition point was 358 seconds which is relatively reached fast. Considering a prevention method of the fire and smoke spread, architects have to use non-combustible exterior in the building's facade to be required as an active fire protection system.

Mechanical behavior of 316L austenitic stainless steel bolts after fire

  • Zhengyi Kong;Bo Yang;Cuiqiang Shi;Xinjie Huang;George Vasdravellis;Quang-Viet Vu;Seung-Eock Kim
    • Steel and Composite Structures
    • /
    • v.50 no.3
    • /
    • pp.281-298
    • /
    • 2024
  • Stainless steel bolts (SSB) are increasingly utilized in bolted steel connections due to their good mechanical performance and excellent corrosion resistance. Fire accidents, which commonly occur in engineering scenarios, pose a significant threat to the safety of steel frames. The post-fire behavior of SSB has a significant influence on the structural integrity of steel frames, and neglecting the effect of temperature can lead to serious accidents in engineering. Therefore, it is important to evaluate the performance of SSB at elevated temperatures and their residual strength after a fire incident. To investigate the mechanical behavior of SSB after fire, 114 bolts with grades A4-70 and A4-80, manufactured from 316L austenitic stainless steel, were subjected to elevated temperatures ranging from 20℃ to 1200℃. Two different cooling methods commonly employed in engineering, namely cooling at ambient temperatures (air cooling) and cooling in water (water cooling), were used to cool the bolts. Tensile tests were performed to examine the influence of elevated temperatures and cooling methods on the mechanical behavior of SSB. The results indicate that the temperature does not significantly affect the Young's modulus and the ultimate strength of SSB. Up to 500℃, the yield strength increases with temperature, but this trend reverses when the temperature exceeds 500℃. In contrast, the ultimate strain shows the opposite trend. The strain hardening exponent is not significantly influenced by the temperature until it reaches 500℃. The cooling methods employed have an insignificant impact on the performance of SSB. When compared to high-strength bolts, 316L austenitic SSB demonstrate superior fire resistance. Design models for the post-fire mechanical behavior of 316L austenitic SSB, encompassing parameters such as the elasticity modulus, yield strength, ultimate strength, ultimate strain, and strain hardening exponent, are proposed, and a more precise stress-strain model is recommended to predict the mechanical behavior of 316L austenitic SSB after a fire incident.

An Availability Assessment of Protection Wall Installed in LPG Filling Station (LPG 충전소 내 설치된 방호벽의 효용성 평가)

  • Lee, Jin-Han;Jo, Young-Do;Moon, Jong-Sam;Kim, Lae Hyun
    • Journal of the Korean Institute of Gas
    • /
    • v.22 no.5
    • /
    • pp.38-45
    • /
    • 2018
  • Jet fire, pool fire, and vapor cloud explosion are major accident scenarios in LPG filling station. The protection wall would mitigate radiation effect in a jet fire. In case of a pool fire, the protection wall would restrict expanding the pool area. The protection wall might both obstruct the dispersion of released vapor and protect blast overpressure in a vapor cloud explosion scenario. In this paper, An availability assessment method of the protection wall how much reduce damage to receptors is proposed. Additionally application cases are presented for the effectiveness of protection wall in the LPG filling station. The study shows that the protection wall can effectively reduce the death probabilities of receptors located behind the wall in cases of the jet fires and the vapor cloud explosions.

Development of Impact and Fire Hazard Analysis on the Steel Roof of LNG Storage Tank (LNG 저장탱크 강재지붕의 충격 및 화재에 대한 안전성평가기법 개발)

  • Lee, Seung-Rim;Park, Jang-Sik;Lee, Young-Soon
    • Journal of the Korean Institute of Gas
    • /
    • v.13 no.1
    • /
    • pp.34-39
    • /
    • 2009
  • Traditionally all concrete roof type LNG storage tank have been constructing in Korea regardless of LNG tank types. But a steel roof LNG storage tank has merits relatively in designing larger scale tanks and construction cost so it is on the table to apply. This study was carried for the standardized development of impact and fire hazard analysis on a 200,000$k{\ell}$ steel roof LNG storage tank designed by KOGAS and for getting quantitative safety data on a steel roof LNG storage tank compared with a conventional concrete roof LNG storage tank by evaluating with this method. Hazard analysis on each four impact and fire scenarios were developed and evaluated by using finite element methods.

  • PDF

Alteration of mechanical properties of tunnel structural members after a tunnel fire accident (화재 후 터널구조물 시공재료의 역학적 특성변화)

  • Chang, Soo-Ho;Choi, Soon-Wook;Kwon, Jong-Wook;Kim, Sang-Hwan;Bae, Gyu-Jin
    • Journal of Korean Tunnelling and Underground Space Association
    • /
    • v.9 no.2
    • /
    • pp.157-169
    • /
    • 2007
  • This study aimed to quantify the deterioration of tunnel structural members such as concrete lining and shotcrete lining after a tunnel fire accident by measuring their mechanical properties between $300^{\circ}C$ and $1,000^{\circ}C$. From the experiments, it was revealed that the critical temperature where mechanical properties start to decrease linearly was approximately $300^{\circ}C$. In addition, the other critical temperature where macro-cracks are induced in specimens was around $600^{\circ}C$. From a series of regression analysis, the optimum regression function with correlation coefficients over 0.99 for mechanical properties at different temperature levels was obtained as the Boltzmann function. Finally, a schematic diagram to estimate temperature distribution inside structural members as well as their mechanical properties at corresponding temperature levels quantitatively was newly proposed for RABT and RWS fire scenarios.

  • PDF

A study on the application of improved IoT- based smoke control system to lodging facilities fires (개선된 IoT기반 제연시스템의 숙박시설 적용에 관한 연구)

  • Kim, Suyong;Lee, Sangsoo;Lee, Sung-Hwa;Kim, Jin-Tae
    • The Journal of the Institute of Internet, Broadcasting and Communication
    • /
    • v.21 no.5
    • /
    • pp.113-118
    • /
    • 2021
  • The study is to provide safety to the occupants from smoke generated by fire occurring at midnight, and to provide a method for providing evacuation safety for a certain period of time even if the occupants are not aware of the fire. The goal of this study is to occur in small accommodation (floor area less than 1,000m2)It is to design a system that can provide ASET for more than 1 hour even if the occupant does not recognize the fire in late-night fire. The basic structure of the smoke-control system applicable to accommodation facilities was designed, and the expected effect was suggested when applied to small-scale domestic accommodation facilities through evacuation scenarios in accommodation facilities to which the system was applied.

Implementation of Dynamic Context-Awareness Platform for Internet of Things(IoT) Loading Waste Fire-Prevention based on Universal Middleware (유니버설미들웨어기반의 IoT 적재폐기물 화재예방 동적 상황인지 플랫폼 구축)

  • Lee, Hae-Jun;Hwang, Chi-Gon;Yoon, Chang-Pyo
    • Journal of the Korea Institute of Information and Communication Engineering
    • /
    • v.26 no.8
    • /
    • pp.1231-1237
    • /
    • 2022
  • It is necessary to dynamic recognition system with real time loading height and pressure of the loading waste, the drying of wood, batteries, and plastic wastes, which are representative compositional wastes, and the carbonization changes on the surface. The dynamic context awareness service constituted a platform based on Universal Middleware system using BCN convergence communication service as a Ambient SDK model. A context awareness system should be constructed to determine the cause of the fire based on the analysis data of fermentation heat point with natural ignition from the load waste. Furthermore, a real-time dynamic service platform that could be apply to the configuration of scenarios for each type from early warning fire should be built using Universal Middleware. Thus, this issue for Internet of Things realize recognition platform for analyzing low temperature fired fire possibility data should be dynamically configured and presented.

Projecting forest fire potential in the Baekdudaegan of the Chungcheong region under the SSP scenario climate change using KBDI Drought Index (KBDI 가뭄지수를 이용한 SSP 기후변화 시나리오하의 충청지역 백두대간 산불 잠재력 전망)

  • Choi, Jaeyong;Kim, Su-Jin;Jung, Huicheul;Kim, Sung-Yeol;Moon, Geon-Soo
    • Journal of the Korean Society of Environmental Restoration Technology
    • /
    • v.25 no.6
    • /
    • pp.1-11
    • /
    • 2022
  • Recently, climate change has been regarded as a major cause of large-scale forest fires worldwide, and there is concern that more frequent and severe forest fires will occur due to the level of greenhouse gas emissions. In this study, the daily Keetch and Byram Drought Index (KBDI) of the Baekdudaegan in Chungcheong region including Sobaeksan, Songnisan, and Woraksan National Parks were calculated to assess effect of climate change on the forest fire potential- severity of annual maximum KBDI and frequency of high KBDI days. The present (2000~2019) and future KBDI(2021~2040, 2041~2060, 2081~2090) were calculated based on the meteorological observation and the ensemble regional climate model of the SSP1-2.6 and SSP5-8.5 scenarios with a spatial resolution of 1-km provided by Korea Meteorological Administration(KMA). Under the SSP5-8.5 scenario, 6.5℃ increase and 14% precipitation increase are expected at the end of the 21st century. The severity of maximum daily KBDI increases by 48% (+50mm), and the frequency of high KBDI days (> 100 KBDI) increases more than 100 days, which means the high potential for serious forest fires. The analysis results showed that Songnisan National Park has the highest potential for forest fire risk and will continue to be high in intensity and frequency in the future. It is expected that the forest vulnerability of the Baekdudaegan in the Chungcheong region will greatly increase and the difficulty in preventing and suppressing forest fires will increase as the abundance of combustible materials increases along with climate changes.

A Study on the Architectural Planning of the Refuge Areas in Geriatric Hospitals Considering Horizontal Evacuation of the Elderly (노인요양병원에서 고령자의 수평 피난을 고려한 대피공간의 건축계획에 관한 연구)

  • Kim, Mijung;Kweon, Jihoon
    • Journal of The Korea Institute of Healthcare Architecture
    • /
    • v.29 no.3
    • /
    • pp.7-15
    • /
    • 2023
  • Purpose: This study was conducted with the aim of presenting spatial planning directions for evacuation spaces based on an analysis of the performance of horizontal evacuation during the early stages of fire incidents in a geriatric hospital. Methods: Based on a review of previous studies, the research model was designed by establishing occupancy conditions, evacuation, and fire scenarios. The analysis model was developed by considering vulnerable areas in terms of evacuation movement and analyzing the results of evacuation performance. Furthermore, the study analyzed the improvement in evacuation performance by arranging refuge areas. Results: The results of the study are as follows. Firstly, vulnerability spots were identified in terms of evacuation performance by schematizing Required Safe Egress Time, Available Safe Egress Time, and their differences. Secondly, the Required Safe Egress Time in the adjacent public spaces along the escape routes of occupants was found to be higher compared to the Available Safe Egress Time. Thirdly, the results of the correlation analysis between the difference in Available Safe Egress Time and Required Safe Egress Time during the early stages of a fire, as well as their constituent factors, demonstrated that user congestion is a more significant factor in compromising evacuation safety than the physical changes in the fire condition. Fourthly, the analysis of evacuation time was conducted by designating refuge areas where occupants can evacuate within a sufficient timeframe. This led to a decrease in the Required Safe Egress Time. Implications: This study is expected to be used as data on the direction of evacuation space planning to improve the evacuation performance of Geriatric Hospital.