• Title/Summary/Keyword: fire modeling

Search Result 336, Processing Time 0.029 seconds

A Study on the Application of Fire Modeling for Multiplex Cinema Theater (복합상영관 화재에 대한 화재모델링의 적용)

  • 허준호;김종훈;노삼규;김운형
    • Fire Science and Engineering
    • /
    • v.18 no.1
    • /
    • pp.42-48
    • /
    • 2004
  • The deterministic modeling techniques like Zone model and Field model are mainly used for thermal distribution and smoke flow at fire case in multi use facilities. While Zone model analyse fire simulation by dividing spaces by 2 section, the Field model dividing many cells. However, the difficultly follows to prove efficiency between the two models when it applys. Therefore new modeling development is required which in closes to real situation by verify number algorithm and related data for fire modeling. The paper analyses the efficiency of two different fire modeling at interior spaces of multiplex cinema theater. It is found that the zone model for average distribution and the field model for detail space phenomenon are relevant to apply. Also, Filed model is useful to the result that fire analysis and position of detector and review for smoke control system.

A Study on the Fire Safety Plan for High-Rise Building Construction (초고층 건축물 건설공사 시 화재안전계획 수립에 관한 연구)

  • Ham, Eun-Gu;Jeong, Myeong-Jin;Lee, Myeong-Gu
    • Proceedings of the Safety Management and Science Conference
    • /
    • 2012.11a
    • /
    • pp.59-66
    • /
    • 2012
  • Recently buildings are constructed in larger and higher scales and becoming more complex. Every country in the world is competing to build high-rise buildings. Korea also has and is constructing high-rise buildings, like the 123story Jamsil Lotte Super Tower. However from small to large scale buildings and on construction sites there still are fire safety accidents that occur continuously. Therefore to improve fire safety plan, examining the actual fire safety management and understanding fire risk analysis Using Fire Modeling through Computer Simulation. Fire safety management plan related fire safety cases were collected an dan analyzed for the study. Also hazard analysis of High rise Buildings under fire compared with existing fire law sand regulations.

  • PDF

Extension of IFC information Modeling for Fire Safety based on WBS (작업분류체계 기반 소방 객체 IFC 정보 모델링 확장 방안 연구)

  • Won, Junghye;Kim, Taehoon;Choo, Seoungyeon
    • Journal of KIBIM
    • /
    • v.13 no.2
    • /
    • pp.37-46
    • /
    • 2023
  • The main objective of this study is to propose a method to enhance building safety using the Industry Foundation Classes (IFC) schema in Building Information Modeling (BIM). To achieve this goal, a fire object relationship diagram is created by using the Model View Definition (MVD) and Property Set (Pset) methodology, as well as the Work Breakdown Structure (WBS) based object relationship analysis. The proposed method illustrates how to represent objects and tasks related to fire prevention and human safety during a building fire, including variables that are relevant to these aspects. Furthermore, the proposed method offers the advantage of considering both the IFC object hierarchy and the project work hierarchy when creating new objects, thereby expanding the attribute information for fire safety and maintenance. However, upon confirmation via an IFC viewer after development, a problem with the accuracy of mapping between attributes and objects arises due to the issue of proxy representation of related object information and newly added object information in standard IFC. Therefore, in future research, a mapping method for fire safety objects will be developed to ensure accurate representation, and the scope of utilization of the fire safety object diagram will be expanded. Furthermore, efforts will be made to enhance the accuracy of object and task representation. This research is expected to contribute significantly to the technological development of building safety and fire facility design in the future.

A Study on the Fire Reconstruction of Exterior on High-rise Building (Focus on Fire Case Including the Woosin Golden Suite in Haeundae) (고층 건축물 외장재의 화재 재현에 관한 연구 (해운대 우신골든스위트의 화재사례를 중심으로))

  • Min, Se-Hong;Lee, Jae-Moon
    • Fire Science and Engineering
    • /
    • v.27 no.2
    • /
    • pp.25-30
    • /
    • 2013
  • 'Heaundae Woosin Building' fire was the case that a fire breaking out on the $4^{th}$ floor spread out the $38^{th}$ floor which is a top story and the penthouse was destroyed by fire. After this fire, the fire safety for high rise buildings has been on the rise and several new laws and regulations related in the buildings were created. The study is to analyze Heaundae officetel building case using FDS which is one of the CFD programs for fire. The methodology of this study is to analyze the case comparing with fire spread and route from a virtual fire simulation and related articles and a video clip of actual scene fire. This study shows that a fire spreading on top of levels spent approximately 30 minutes and, which is similar to the actual fire case. Also the pattern of spread has similarity with the case. However, even if the actual fire case shows the fire pattern was "V shape", the smoke-view presents the fire dose not spread horizontally as much as the real fire case. The result shows uncertainty of the modeling based on many grids and a limitation of putting interior finish input sources and the direction of the wind might cause the difference. Also, to analyze factors influencing on a vertical fire, another fire modeling is performed by in condition of modeling environment considering concrete interior finish between buildings and no wind. The result presents the fire spread in smoke-view does not spread vertically as much as the actual case.

Applying to simulation analysis for predicting the combustion performance of Large scale fire tests (실대화재시험의 연소성능 예측을 위한 시뮬레이션 적용)

  • Kim, Woon-Hyung;Park, Kye-Won;Jeong, Jae-Gun;Im, Hong-Soon
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 2008.11a
    • /
    • pp.86-92
    • /
    • 2008
  • On this study, modeling works using Cone tools simulation method were made for the prediction of real fire test results such as small to large scale fire tests including ISO 5660-1, EN 13823 and ISO 13784-1. For those simulation prediction, three real fire tests were performed in advance. In addition, Real data from ISO 5660-1 test were applied to this simulation modeling. Finally, the comparative analysis between Real fire tests and Simulation results were made out. Also, the Classifying evaluation by EURO Class using EN 13501-1 were taken off.

  • PDF

A Study on the Fire Safety Plan for Building Construction (건축물 건설공사 시 화재안전계획 수립에 관한 연구)

  • Jeong, Myeong-Jin;Lee, Myeong-Gu;Ham, Eun-Gu
    • Journal of the Korea Safety Management & Science
    • /
    • v.14 no.4
    • /
    • pp.31-37
    • /
    • 2012
  • Recently buildings are constructed in larger and higher scales and becoming more complex. However from small to large scale buildings and on construction sites there still are fire safety accidents that occur continuously. Therefore to improve fire safety plan, examining the actual fire safety management and understanding fire risk analysis Using Fire Modeling through Computer Simulation. On this study, the permissible evacuation times were estimated for smoke fall, temperature, CO concentration, viability, etc. Fire safety management plans for fire safety were suggested.

Fast and Efficient Method for Fire Detection Using Image Processing

  • Celik, Turgay
    • ETRI Journal
    • /
    • v.32 no.6
    • /
    • pp.881-890
    • /
    • 2010
  • Conventional fire detection systems use physical sensors to detect fire. Chemical properties of particles in the air are acquired by sensors and are used by conventional fire detection systems to raise an alarm. However, this can also cause false alarms; for example, a person smoking in a room may trigger a typical fire alarm system. In order to manage false alarms of conventional fire detection systems, a computer vision-based fire detection algorithm is proposed in this paper. The proposed fire detection algorithm consists of two main parts: fire color modeling and motion detection. The algorithm can be used in parallel with conventional fire detection systems to reduce false alarms. It can also be deployed as a stand-alone system to detect fire by using video frames acquired through a video acquisition device. A novel fire color model is developed in CIE $L^*a^*b^*$ color space to identify fire pixels. The proposed fire color model is tested with ten diverse video sequences including different types of fire. The experimental results are quite encouraging in terms of correctly classifying fire pixels according to color information only. The overall fire detection system's performance is tested over a benchmark fire video database, and its performance is compared with the state-of-the-art fire detection method.

An Investigation of Quantitative Risk Assessment Methods for the Thermal Failure in Targets using Fire Modeling (화재모델링을 이용한 목표 대상물의 열적 손상에 대한 정량적 위험성 평가방법의 고찰)

  • Yang, Ho-Dong;Han, Ho-Sik;Hwang, Cheol-Hong;Kim, Sung-Chan
    • Fire Science and Engineering
    • /
    • v.30 no.5
    • /
    • pp.116-123
    • /
    • 2016
  • The quantitative risk assessment methods for thermal failure in targets were studied using fire modeling. To this end, Fire Dynamics Simulator (FDS), as a representative fire model, was used and the probabilities related to thermal damage to an electrical cable were evaluated according to the change in fire area inside a specific compartment. 'The maximum probability of exceeding the damage thresholds' adopted in a conservative point of view and 'the probability of failure' including the time to damage were compared. The probability of failure suggested in the present study could evaluate the quantitative fire risk more realistically, compared to the maximum probability of exceeding the damage thresholds with the assumption that thermal damage occurred the instant the target reached its minimum failure criteria in terms of the surface temperature and heat flux.