• Title/Summary/Keyword: finned tube

Search Result 159, Processing Time 0.025 seconds

An Experimental Study on the Effects of Design Factors for the Performance of Fin-Tube Heat Exchanger Under Frosting Conditions (착상시 설계인자에 따른 핀-관 열교환기의 성능변화에 관한 실험적 연구)

  • 이관수
    • Transactions of the Korean Society of Mechanical Engineers
    • /
    • v.19 no.10
    • /
    • pp.2657-2666
    • /
    • 1995
  • In this study, the effects of design factors of finned-tube heat exchanger, such as fin spacing and fin array on the frost growth and heat exchanger performance are investigated under a frosting condition. The results show that the amount of frost, frost density and blockage ratio of air flow passage increase with decreasing fin spacing. Heat transfer rate increases momentarily at the initial stage of frosting and then decreases. After that heat transfer rate continues to increase again to reach a maximum value and then decreases dramatically. It is shown that the time required for heat transfer rate to reach a maximum value becomes shorter with decreasing fin spacing, and after a maximum value, heat transfer rate decreases very fast. The maximum allowable blockage ratio is introduced to determine the operation limit of a finned-tube heat exchanger operating under frosting condition and is obtained as a function of fin spacing. It is also shown that heat transfer rate of heat exchanger with staggered fin array increases about 17% and the amount of pressure drop of air increases about 1~2 mmH$_{2}$O, compared with those of in-line type heat exchanger under frosting condition.

A Study on the Thermal Characteristics of Finned-tube Heat Exchanger by Using the Liquid Crystal Technique (액정법을 이용한 휜-관 열교환기 휜의 열적 특성에 관한 연구)

  • 강희찬;김무환;김명수
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.12 no.4
    • /
    • pp.414-421
    • /
    • 2000
  • This study was discussed about the thermal characteristics of finned tube heat exchanger having two row used in the air-conditioning application. Pressure drop and heat transfer coefficient were measured and investigated for the 3 times models of plain fin. Also the temperature distribution and heat conduction in the fin was measured by using the liquid crystal method. The surface temperature of rear row was nearly constant, and heat conduction in the fin was stronger near the front row than the rear row.

  • PDF

VERIFICATION OF FIN EFFICIENCY THEORY FOR THE CIRCULAR FINNED-TUBE HEAT EXCHANGER BY NUMERICAL EXPERIMENT (원형휜-원형관 열교환기의 휜효율 이론에 관한 수치적 검증)

  • Kang, H.C.;Lim, B.B.;Lee, J.W.;Chang, B.C.;Ahn, S.W.
    • 한국전산유체공학회:학술대회논문집
    • /
    • 2008.03a
    • /
    • pp.137-142
    • /
    • 2008
  • The purpose of the present study is to investigate the convective heat transfer characteristics and the validity of fin efficiency of the circular finned-tube heat exchanger by using commercial CFD code. The heat transfer coefficient obtained by using the laminar model was 22% overestimated to the experimental data. The fin surface temperature compared with the experimental data measured by the liquid crystal method. The fin efficiency by the present numerical experiment, defined as normalized and averaged fin surface temperature, was greater than the theoretical fin efficiency and the difference is increased at high value of the factor m.

  • PDF

Measurement of the Thermal Characteristics of Finned-tube Heat Exchanger Fin by Using the Liquid Crystal Technique

  • Kang, Hie-Chan;Kim, Moo-Hwan
    • International Journal of Air-Conditioning and Refrigeration
    • /
    • v.9 no.2
    • /
    • pp.28-35
    • /
    • 2001
  • This study deals with the thermal characteristics of finned-tube heat exchanger having two rows used in the air-conditioning application. Pressure drop and heat transfer coefficient were measured by using the three times models of plain fin and compared with the theory. Also the temperature distribution and heat conduction in the fin was measured by using the liquid crystal method. The surface temperature of rear row was nearly constant, and heat conduction in the fin was stronger near the front row than the rear row.

  • PDF

Free Convection Correlation for the Single Circular Finned Tube Heat Exchanger (단일 원형관-원형휜 열교환기의 자연대류 열전달 실험관계식)

  • Kang, Hie-Chan;Jang, Hyun-Soon;Hong, Cha-Kun
    • Proceedings of the SAREK Conference
    • /
    • 2008.11a
    • /
    • pp.596-600
    • /
    • 2008
  • An experimental study has been conducted on the free convection heat transfer for the 7 kinds of circular finned tube heat exchangers. Empirical correlation was suggested at the range of 3,500$D_o$/$D_i$<3.0, 0.19<$P_f$/$D_i$<0.34. The 92% of experimental data agreed with the correlation within 10%.

  • PDF

Characteristics of the Air-side Particulate Fouling Materials in Finned-Tube Heat Exchangers of Air Conditioners (공기조화기용 열교환기의 공기측 파울링 입자 분석 연구)

  • 안영철;신희수;황유진;이창건;이재근;이현욱;안승표;윤덕현;하삼철
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.15 no.7
    • /
    • pp.611-617
    • /
    • 2003
  • The air-side particulate fouling in the heat exchangers of HVAC applications degrades the performance of cooling capacity, pressure drop across a heat exchanger, and indoor air quality. Indoor and outdoor air contaminants foul heat exchangers. The purpose of this study is to investigate the characteristics of the air-side particulate fouling materials in finned-tube heat exchangers of air conditioners. Air conditioners being used in the field such as inns, restaurants, and offices are collected in chronological order in use. Typical fouling materials on the heat exchangers include fibers and dusts ranged from 6.6 to 20.9 ${\mu}{\textrm}{m}$ in mass median diameter.

Heat Transfer and Pressure Drop Characteristics of Plain Finned Heat Exchangers Having 5.0 mm Tubes

  • Kim, Nae-Hyun;Cho, Jin-Pyo;Oh, Wang-Ku;Choi, Yong-Hwa;Gaku, Hayase
    • International Journal of Air-Conditioning and Refrigeration
    • /
    • v.16 no.1
    • /
    • pp.9-14
    • /
    • 2008
  • In this study, pressure drop and heat transfer characteristics of plain finned heat exchangers having 5.0 mm diameter (fin collar 5.3 mm) tubes were investigated. Six samples having different fin pitches (1.1 to 1.3 mm) and tube rows (1 and 2 row) were tested. The fin pitch had a negligible effect on j and f factors. Both j and f factors decreased as the number of tube row increased, although the difference was not significant for the f factor. When compared with the j and f factors of the samples having 7.3 mm diameter tubes, the present j and f factors yielded lower values. However, the j/f ratio was larger at low Reynolds numbers. Possible reasoning is provided from the flow pattern consideration. Comparison with existing correlations were made.

Development of Hybrid Expander Unit for Fin Tube Heat Exchanger (핀튜브 열교환기용 전관확관 유닛 개발)

  • Roh, Geonsang;Kim, Jongnam
    • Journal of the Korean Society of Mechanical Technology
    • /
    • v.13 no.4
    • /
    • pp.165-168
    • /
    • 2011
  • In this paper, the hybrid tube expander unit for fin and tube type heat exchanger are developed by means of enlarging and inserting the smooth tube with a small diameter to a finned tube having larger diameter. In other word, the tube expander tool that is easy to attach and remove from tube is developed. The hybrid tube expander unit developed in this study can move easily and enlarge the tube without fixing at tube sheet. Also, this unit has a function removing scales inside tube by replacing a tube expander ball.

Prediction of Characteristics for the Air-side Particulate Fouling in Finned-Tube Heat Exchangers of Air Conditioners used in the Field (실공간 사용 공기조화기용 열교환기의 공기측 파울링 특성 예측)

  • Ahn, Young-Chull;Jung, Sung-Hak;Hwang, Yu-Jin;Lee, Chang-Gun;Kim, Doo-Hyun;Jung, Seong-Ir;Lee, Jae-Keun
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.19 no.8
    • /
    • pp.563-568
    • /
    • 2007
  • The air-side particulate fouling in the heat exchangers of HVAC applications degrades the performances of cooling capacity, pressure drop across a heat exchanger, and indoor air quality. Indoor and outdoor air contaminants foul heat exchangers. An empirical modeling equation has been derived from the experimental results using accelerated tests and it showed good predictions of the fouling characteristics of the slitted finned tube heat exchangers. However the modeling equation predicts only the fouling characteristics of new heat exchangers and it can not predicts fouling characteristics obtained from actual field data which contains the effect of hydrophilicity deterioration. Therefore an modified modeling equation is proposed and it shows good predictions of the actual fouling characteristics of finned-tube heat exchangers.

Experimental Study on Thermal Characteristics of Heat Exchanger Modules for Multi Burner Boiler (멀티버너 보일러용 열교환기 모듈 특성 시험 - 모듈 순서에 따른 특성결과 -)

  • Kang, Sae-Byul;Kim, Jong-Jin;Ahn, Joon
    • Proceedings of the KSME Conference
    • /
    • 2008.11b
    • /
    • pp.3053-3058
    • /
    • 2008
  • We develop a heat exchanger modules for a multi-burner boiler. The heat exchanger module is kind of a heat recovery steam generator (HRSG). This heat recovery system has 4 heat exchanger modules. The 1st module consists of 27 bare tubes due to high temperature exhaust gas and the others consist of 27 finned tubes. The maximum steam pressure of each module is 1 MPa and tested steam pressure is 0.7 MPa. In order to test these heat exchanger modules, we make a 0.5t/h flue tube boiler (LNG, $40\;Nm^3/h$). We tested the heat exchanger module with changing the position of each heat exchanger module. We measured the inlet and outlet temperature of each heat exchanger module and calculated the heat exchange rate. The results show that if module C is placed at second stage (the 1st stage is always module O, bare tube module), there is no need to attach an additional heat exchanger module. In this case the exit temperature of module C is low enough to enter an economizer which is more effective in heat recovery than a heat exchanger module.

  • PDF