• 제목/요약/키워드: fault current characteristics

검색결과 608건 처리시간 0.021초

피크전류제한 기능을 갖는 초전도한류기의 전류제한 특성분석 (Analysis on Current Limiting Characteristics of a Superconducting Fault Current Limiter (SFCL) with a Peak Currnt Limiting Function)

  • 한태희;임성훈
    • 한국전기전자재료학회논문지
    • /
    • 제24권1호
    • /
    • pp.47-51
    • /
    • 2011
  • The superconducting fault current limiter (SFCL) with a peak current limiting function according to the initial fault current with the different amplitudes was suggested. The proposed SFCL, which consists of two limiting components, causes only the first superconducting element among two limiting components to be quenched in case that the initial fault current with the lower peak amplitude happens. On the other hand, the initial fault current with the higher peak amplitude makes both the superconducting elements of two limiting components to be quenched, which contributes to the peak current limiting function of the SFCL. To confirm the fault current limiting operation of the proposed SFCL, the short-circuit tests of the SFCL according to the fault angle were carried out and its effective fault current limiting operations could be discussed.

삼차권선을 이용한 이중퀜치 자속구속형 초전도한류기의 전류제한 특성 분석 (Analysis on Current Limiting Characteristics of Double Quench Flux-Lock Type SFCL Using Its Third Winding)

  • 한태희;임성훈
    • 한국전기전자재료학회논문지
    • /
    • 제29권5호
    • /
    • pp.289-293
    • /
    • 2016
  • The flux-lock type superconducting fault current limiter (SFCL) connects the two parallel windings in parallel with a ferromagnetic core. We suggest that the double quench flux-lock type SFCL should add a third winding. We analyzed characteristics of the fault current and the peak current using the quench of the high-Tc superconducting element. The proposed SFCL's inductances of a primary winding and the third winding were fixed and the amplitude of inductance of the secondary winding was changed. We found that the fault current can be more effectively controlled through the analysis of the equivalent circuit and the short-circuit tests.

전류분석을 이용한 유도 전동기의 결함분석 알고리듬 개발 (A Development of the Algorithm to Detect the Fault of the Induction Motor Using Motor Current Signature Analysis)

  • 신대철;정병훈
    • 한국소음진동공학회논문집
    • /
    • 제14권8호
    • /
    • pp.675-683
    • /
    • 2004
  • The motor current signature provides an important source of the information for the faults diagnosis of three-phase induction motor. The theoretical principles behind the generation of unique signal characteristics, which are indicative of failure mechanisms, are Presented. The fault detection techniques that can be used to diagnose mechanical Problems, stator and rotor winding failure mechanisms, and air-gap eccentricity are described. A theoretical analysis is presented which predicts the presence of unique signature patterns in the current that are only characteristics of the fault. The predictions are verified by experimental results from a special fault Producing test rig and on-site tests in a steel company. And this study have made new diagnostic algorithm for the operating induction motors with the test results. These developments are including the use of monitoring and analysis of electric current to diagnose mechanical and electrical problems and gave the precise test results automatically.

저항형 초전도 한류기에서의 퀀치 전파 (Quench propagation in resistive SFCL)

  • 김혜림;현옥배;최효상;황시돌;김상준
    • 한국전기전자재료학회논문지
    • /
    • 제13권4호
    • /
    • pp.337-342
    • /
    • 2000
  • We fabricated resistive superconducting fault current limiters based on YB $a_{2}$/C $u_{3}$/ $O_{7}$ thin films and investigated their quench propagation characteristics. The YB $a_{2}$/C $u_{3}$/ $O_{7}$ films was coated with a gold layer and patterned into 1 mm wide meander lines by photolithography. The quench was concluded to start locally and propagates until completed. The quench propagation characteristics were explained based on the heat transfer within the film as well as between the film and the surrounding liquid nitrogen. The quench completion time depended strongly on potential fault current amplitude and not significantly on fault angle which indicates that the quench propagation speed is affected more by heat dissipation rate than by fault current increase rate. The quench completion time was 1 msec at the fault current of 65 $A_{peak/{\ak}}$.

  • PDF

트리거형 초전도한류기의 접점구성에 따른 전류제한 및 회복특성 분석 (Analysis on Current Limiting and Recovery Characteristics of a Trigger Type SFCL as the Composition of the Contact)

  • 최종수;김명후;유일경;김진석;임성훈;김재철
    • 조명전기설비학회논문지
    • /
    • 제24권9호
    • /
    • pp.159-164
    • /
    • 2010
  • We experiment to analyze on current limiting and recovery characteristics of trigger type SFCL as the composition of the contact. Generally, some superconductor of SFCL is relatively largely loaded due to limit the fault current by oneself and recovery time is affected until the fault cleared. However, in the fault, the proposal trigger type SFCL transfer the fault current to current limiting reactor(CLR) using power switch so it could reduce the recovery time and load of the superconductor. However, because of applying the additional power switches, that could generate some power loss. Therefore, to solve this problem, we proposed the composition method of the double contact for a trigger type SFCL and analyzed on current limiting and recovery characteristics for ones.

고온초전도 전류제한기의 초기사고전류 제한시점 분석 (Analysis of the Initial Fault Current Limiting Point of the SFCLs)

  • 박충렬;두호익;두승규;김용진;김민주;조용선;최효상;한병성
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2008년도 하계학술대회 논문집 Vol.9
    • /
    • pp.292-292
    • /
    • 2008
  • The superconducting fault current limiter(SFCL) can be used to limit fault current level in electrical transmission line and power system. Up to now, there are several kinds of SFCL that have proposed and it is expects that they will be applied to appropriated position considering their own properties; initial fault current limiting instant and the current limiting characteristics. In this paper, we investigated the initial fault current limiting instant and the amplitude of initial fault current in the resistive type, the flux-lock type, the flux-coupling type and the transformer type SFCL. Experiment results show that the initial fault current limiting instant and the amplitude of initial fault current of the SFCLs are dependant on the ratio of inductance of primary and secondary coils.

  • PDF

1선 지락 사고 시 3 권선 변압기에 적용된 초전도 한류기의 동작 특성 분석 (Analysis of Transient Characteristics of a SFCL Applied Into Third-winding Transformer in a Single Line-to-ground Fault)

  • 최혜원;최효상;정병익
    • 전기학회논문지
    • /
    • 제62권7호
    • /
    • pp.1033-1037
    • /
    • 2013
  • Coercion transformer is commonly used in the electrical grid which in three phase of distribution system. The accident of the electrical grid is divided into a single, a double, a third line-to-ground faults and a double, a third line-to-line faults. A single line-to-ground fault accounts for nearly 75[%] among them. In this research, when a Superconducting Fault Current Limiters (SFCL) was applied to the three phase power system, operation in a single line-to-ground fault and limiting characteristics of fault current according to turns ratio of third winding were analyzed. When a single line-to-ground fault happened, secondary winding's circuit was open. Then third winding's circuit with a SFCL was closed. So fault current was limited by diverted circuit. At this time, we could find out that size of the limited fault current could be changed according to third winding rate. We confirmed that limiting operation of the fault current was carried out within one-period. These results will be utilized in adjusting the size of the SFCL.

변압기형 초전도전류제한기의 히스테리시스 특성 분석 (Analysis on Hysteresis Characteristics of a Transformer Type Superconducting Fault Current Limiter)

  • 임성훈
    • 한국전기전자재료학회논문지
    • /
    • 제23권2호
    • /
    • pp.164-168
    • /
    • 2010
  • The transformer is expected to be an essential component of a superconducting fault current limiter (SFCL) for both the increase of its voltage ratings and the simultaneous quench due to different critical current between high-$T_C$ superconducting (HTSC) elements comprising the SFCL. However, in order to perform the effective current limiting operation of the SFCL, the design for the SFCL considering the hysteresis characteristics of the iron core is required. In this paper, the influence of the hysteresis characteristics of the iron core comprising the transformer type SFCL on its current limiting characteristics was investigated. Through the comparative analysis on the hysteresis curves due to the ratio of the turn number between the 1st and the 2nd windings of the transformer, the proper design condition for the ratio of the turn number to achieve the effective current limiting operation of the transformer type SFCL could be obtained.

반주기 이후 동작 하이브리드 초전도 전류제한기와 보호기기 협조 분석 (Analysis on the Protective Coordination with Hybrid Superconducting Fault Current Limiter)

  • 김진석;임성훈;김재철;최종수
    • 전기학회논문지
    • /
    • 제60권10호
    • /
    • pp.1832-1837
    • /
    • 2011
  • The fault current has increased due to the large power demand in power distribution system and network distribution system. To protect the power system effectively from the increased fault current, the superconducting fault current limiter (SFCL) has been notified. However, the conventional SFCL has some problems such as cost, operation, recovery, loss. To solve some problems, the hybrid superconducting fault current limiter using the fast switch was proposed. However, hybrid SFCL also has a problem that is protection coordination in power distribution system with hybrid SFCL. In this paper, the fault current limiting characteristics of hybrid SFCL with first half cycle non-limiting operation according to the fault angle, the resistance of superconducting element, and the magnitude of Current Limit Resistor (CLR) which are the components of hybrid SFCL were analyzed through the experiments.

초전도(신)전력계통 고장전류 분석 및 병렬한류시스템 (A fault current analysis and parallel FCL scheme on superconducting new power system)

  • 윤재영;이승렬;김종율
    • 한국초전도ㆍ저온공학회논문지
    • /
    • 제8권1호
    • /
    • pp.49-53
    • /
    • 2006
  • This paper specifies the new power supply paradigm converting 154kV voltage level into 22.9kV class with equivalent capacity using superconducting rower facilities and analyze the fault current characteristics with and without HTS-FCL (High Temperature Superconducting-Fault Current Limiter). Superconducting new power system is the power system to which applies the 22.9kV HTS cable in parallel to HTS transformer and HTS-FCL with low-voltage and mass-capacity characteristics replacing 154kV conventional cable and transformer. The fault current of superconducting new power system will increase greatly because of the mass capacity and low impedance of HTS transformer and cable. This means that the HTS-FCL is necessary to reduce the fault current below the breaking current of circuit breaker. This paper analyze the fault current and suggests the parallel HTS-FCL scheme complementing the inherent problem of HTS-FCL, that is recovery after quenching is impossible within shorter than a few seconds.