Reduction of Cooling Load using Outdoor Air Cooling (외기냉방을 이용한 냉방부하 절감 연구)

  • Kim, Min-Yang;Kim, Young-Il;Chung, Kwang-Seop
    • Journal of the Korean Society for Geothermal and Hydrothermal Energy
    • /
    • v.7 no.1
    • /
    • pp.51-58
    • /
    • 2011
  • Due to enhanced sealing and insulation of buildings, extensive use of glasses for building envelopes and increased use of heat generating office equipments, energy consumption of modem buildings for cooling is steadily increasing. With outdoor air cooling(ODAC) system, cooling load can be reduced by exchanging indoor air with the cold outdoor air during spring and fall seasons. If ODAC is operated based only on temperature, total cooling load may virtually increase if the outdoor humidity is high. To overcome this problem, ODAC should be controlled based on enthalpy. In this work energy saving characteristics of enthalpy controlled ODAC is studied using dynamic simulation. The result shows that cooling load can be reduced by 27% by adopting ODAC.

A Fundamental Study on Development of a Wall Structure type Thermal Diode for Energy Saving (에너지 절약을 위한 벽체형 열다이오드 개발에 관한 기초)

  • Pak, E.T.;Chang, Y.G.;Chea, S.S.
    • Solar Energy
    • /
    • v.17 no.3
    • /
    • pp.67-73
    • /
    • 1997
  • In order to development of a new wall structure type thermal diode for energy saving, the numerical studies have been performed for natural convection across an rectangular enclosure with the various lengthes of the heat source and sink plate. The governing equations for the two-dimensional, laminar, natural convection process in an enclosure are discretized by the control volume approach which insures the conservative characteristics to be satisfied in the calculation domain, and solved by a elliptic SIMPLE algorithm. The momentum and energy equations are coupled through the buoyancy term.

  • PDF

Energy Saving Potentials of Dedicated Outdoor Air System in a High-rise Apartment Building (외기전담 시스템 기반 초고층 공동주택 중앙 환기시스템의 에너지 절감효과 분석)

  • Kim, Min-Hwi;Kim, Jin-Hyo;Kwon, Oh-Hyun;Jeong, Jae-Weon
    • 한국태양에너지학회:학술대회논문집
    • /
    • 2009.11a
    • /
    • pp.291-296
    • /
    • 2009
  • This paper investigates the energy saving potentials of a dedicated outdoor air system (DOAS) applied to a highrise apartment building. As for a typical $132-m^2$ apartment unit, two different HVAC systems; centralized DOAS-Ceiling Radiant Cooling Panel and decentralized Energy Recovery Ventilator-Packaged Air Conditioner were installed. Transient behavior and control characteristics of each system were modeled numerically using a commercial equation solver program, and annual cooling coil load and heating load reduction potentials were compared. The research shows that DOAS-Ceiling Radiant Cooling Panel system can reduce the cooling coil load over 21% annually compared with the current Energy Recovery Ventilator-Packaged Air Conditioner pair. In addition, over 40% of annual ventilation heating load can be reduced by use of DOAS.

  • PDF

A Study on the Individual Room Control of Radiant Floor Heating System in Apartment Buildings (공동주택에서 바닥복사 난방시스템의 실별 제어에 관한 연구)

  • 김오봉;이미경;김광우;여명석
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.16 no.5
    • /
    • pp.421-429
    • /
    • 2004
  • In Korea, the radiant heating system has been widely used as a residential heating method, which has been modernized to use hot water running into the tubes embedded in the floor structure. According to the recent improvement of living standard of residential buildings, the requirement of the thermal comfort and energy saving in heating system has been raised. Until now, the radiant floor heating system has been controlled by room thermostat installed in the living room, but for better thermal comfort, an individual room control method is adopted as an alternative. Therefore, it is necessary to evaluate the control performance between the current control method and the individual room control method. In this study, the control performance between the two systems is evaluated through the field experiment. And the control performances of room air temperature and energy performances are analyzed through the simulation using TRNSYS. Firstly, the simulations are performed in the various outdoor conditions and the flow rates and the simulation results are analyzed for the control performances. Also, to evaluate the energy performance, the simulations are performed under the operating conditions in which the set-point of the room air temperature is fixed or changed according to the schedule of occupancy, and the simulation results are analyzed between the two methods.

Dynamic Shutdown of Server Power Mode Control for Saving Energy in a Server Cluster Environment (서버 클러스터 환경에서 에너지 절약을 위한 서버 전원 모드 제어에서의 동적 종료)

  • Kim, Hoyeon;Ham, Chihwan;Kwak, Hukeun;Chung, Kyusik
    • KIPS Transactions on Computer and Communication Systems
    • /
    • v.2 no.7
    • /
    • pp.283-292
    • /
    • 2013
  • In order to ensure high performance, all the servers in an existing server cluster are always On regardless of number of real-time requests. They ensure QoS, but waste server power if some of them are idle. To save energy consumed by servers, the server power mode control was developed by shutdowning a server when a server is not needed. There are two types of server power mode control depending on when a server is actually turned off if the server is selected to be off: static or dynamic. In a static mode, the server power is actually turned off after a fixed time delay from the time of the server selection. In a dynamic mode, server power is actually turned off if all the services served in the server are done. This corresponds to a turn off after a variable time delay. The static mdoe has disadvantages. It takes much time to find an optimal shutdown time manually through repeated experiments. In this paper, we propose a dynamic shutdown method to overcome the disadvantages of static shutdown. The proposed method allows to guarantee user QoS with good power-saving because it automatically approaches an optimal shutdown time. We performed experiments using 30 PCs cluster. Experimental results show that the proposed dynamic shutdown method is almost same as the best static shutdown in terms of power saving, but better than the best static shutdown in terms of QoS.

Electric Power Energy Saving and Efficient Measures in Buildings using the Smart-Meter (스마트미터를 활용한 건축물의 전력에너지 절감 및 효율화 방안)

  • Hwang, Hyun Bae;Jung, Byeong Soo
    • Journal of Digital Convergence
    • /
    • v.12 no.11
    • /
    • pp.365-372
    • /
    • 2014
  • In this paper, We implement a power-saving and efficient measures in buildings using the smart-meter. In order to save electric power energy, We propose an improved automatic power-factor controller(APFC) and demand control measures. This is achieved by controlling directly circuit breakers and the capacitor bank feeders in real time via a two-way smart-meter's ICT skills. Improved APFC is minimizing installation costs by series-parallel connecting heterologous capacitors to form a more diverse capacitor banking and controlling using the smart-meter. In order to suppress the demand power, We have designed a smart-meter with communication functions using Atmel's AVR465 and tested an operated lodging building for 24-hours. As a result, We made sure to always retained more than 95% power factor and did not occur over compensation.

A Study on the Improvement of Indoor Thermal Performance of Floor Radiant Heating System Considering Valve Operation Characteristics (바닥복사 난방시스템의 밸브구동 특성을 고려한 실내 열환경 성능 개선 연구)

  • Song, Jae-Yeob;Ahn, Byung-Cheon
    • Journal of the Korean Society for Geothermal and Hydrothermal Energy
    • /
    • v.17 no.4
    • /
    • pp.36-45
    • /
    • 2021
  • In this study, to improve the indoor thermal environment of the radiant floor heating system, a study was conducted on the temperature change characteristics and energy consumption according to the change of the indoor air set temperature, the supply hot water temperature and the outdoor temperature. As for the control method, the on/off control and the thermal difference proportional control method proposed through previous studies were applied. In addition, in consideration of field applicability, numerical analysis was performed for the case where the indoor air temperature sensor was affected by the wall temperature. As a result, it was found that the temperature difference proportional control method is more effective for thermal comfort and energy saving than on/off control.

Development of Pneumatic Servo Actuator for the Energy saving system (에너지 절약 시스템 공압 서보 액추에이터 개발)

  • Bae, Sung-Woo;Kim, Dong-Soo;Kim, Myoung-Sub
    • Proceedings of the KSME Conference
    • /
    • 2007.05a
    • /
    • pp.1428-1432
    • /
    • 2007
  • The object of this paper is development of pneumatic servo actuator technique for energy saving type. In this paper, consist of pneumatic servo actuator technique is pneumatic servo valve, pneumatic motor and cylinder. This technique applied a automobile, aerospace engineering, a ship, defence industry and industrial machine because it have high response, high speed, high precision control, low friction etc., compare with previously technique. But it depend on import the whole quantity. So this study, suggest that through the development of servo actuator applicable the use of industrial field.

  • PDF

Characteristics of Street Lamp Controller with Earth Leakage Contactor (가로등 전용 누전 개폐기의 차단효과에 대한 고찰)

  • Lee, Seong-Jae;Shin, Jae-Sik
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2010.06a
    • /
    • pp.283-283
    • /
    • 2010
  • Smart street light controller is a product with advance micro controller base for energy saving in conventional street lighting systems. Intelligent Street light controller are specially developed for automation and energy saving in conventional street light systems and lighting systems. It is so designed that it operates on sunrise & sun set timings according to longitude of particular location with facilitate to set month wise civil twilight timings to cope up with all seasons. Dimming (Power down) mode selection switch on/off at fixed times with relay or contactor. Night dimming, staggering and intelligent control reduces burn hours and increases the lifetime of lamps with about 30% and low annual operating cost type base are among the most inexpensive wireless technologies available. Low initial costs As PLC wireless, there is no need to establish cable connection.

  • PDF

LED array design for optimal combination of plant grown (식물재배를 위한 최적LED 배열조합설계)

  • Lee, Sungwon;Park, Sekwang
    • Journal of Plant Biotechnology
    • /
    • v.41 no.3
    • /
    • pp.123-126
    • /
    • 2014
  • This paper is suitable for household plant factory by design and using both energy-saving LED and solar technology. Conventional household plant factory only depending on natural sunlight is sensitive for the change of external environment. Another a big problem of conventional common household plant factory is large power consumption. Recently interest in wellbeing food such as chemical-free is increased abruptly. To solve these two problems, this paper describes hybrid type of household plant. In particular, reducing the power photosynthesis photon flux density (PPFD) is kept uniform to enhance the growth of the plant. Ambient light sensor is adopted for the control of proper combination of sunlight and LED to keep PPFD constant.