• Title/Summary/Keyword: condenser cooling system

Search Result 142, Processing Time 0.026 seconds

The Performance Characteristics of Heat Pump Using the Refrigerant Subcooling (냉매 과냉각을 이용한 열펌프 시스템의 성능 특성)

  • Roh, Geon-Sang;Son, Chan-Ghyo
    • Journal of Hydrogen and New Energy
    • /
    • v.18 no.4
    • /
    • pp.413-421
    • /
    • 2007
  • In this paper, the performance characteristics of heat pump system using a new refrigerant subcooling system designed for the study, are introduced. The new heat pump system have the ice storage tank at the outlet of condenser. The experimental apparatus is a well-instrumented water/water heat pump which consisted of working fluid loop, coolant loop, and ice storage tank. The experiment parameters of subcooling ranged as the evaporating temperature from $-5^{\circ}C$ to $8^{\circ}C$, the condensing temperature from $30^{\circ}C$ to $35^{\circ}C$. The test of the ice storage was carried out at evaporating temperature of $-10^{\circ}C$ and the ice storage mode is Ice-On-Coil type. The working fluid was R-22 and the storage materials were city-water. The test results obtained were as follows; The refrigerant mass flow rate and compressor shaft power were unchanged by the degrees of subcooling, that is, they were independent of degrees of subcooling. The cooling capacity of the new heat pump system increase as the evaporating temperature and subcooling degrees increase and is higher by $25{\sim}30%$, compared to the normal heat pump system. The COP of the new heat pump system increases as the degrees of subcooling and evaporating temperature increase and is higher by 28% than that of the normal heat pump system.

STUDY ON THE PREVENTION METHOD FOR HEAT ACCUMULATION FOR PERSONAL RAPID TRANSIT (PRT) VEHICLE UNDER BODY (PRT 차량하부 열부하 저감방안 도출 연구)

  • Kwon, S.B.;Song, J.H.;Kang, S.W.;Jeong, R.G.;Kim, H.B.;Lee, C.H.;Seo, D.K.
    • Journal of computational fluids engineering
    • /
    • v.18 no.1
    • /
    • pp.58-62
    • /
    • 2013
  • Personal Rapid Transit (PRT) is the emerging personal transport vehicle operating on the loop automatically. The PRT system utilize the electrical power from super capacity or battery, it is important to manage the power or energy. In this regards, the management of high temperature occurred by the operation of system is significantly important to prevent from serious damage of component. In this study, we studied the adequate shape of underbody which can reduce the heat accumulation by pickup coil and condenser using natural air cooling. We suggested the additional air pathway, air inlet and flow separator to decrease the temperature of the heat source components. It was found that suggested system can decrease the temperature of PRT under body by 16% during the static mode and by 10% during the running mode at 30km/h. It is expected that the findings of this study will feed into final design of newly built Korean PRT vehicle.

Development of an on-demand flooding safety system achieving long-term inexhaustible cooling of small modular reactors employing metal containment vessel

  • Jae Hyung Park;Jihun Im;Hyo Jun An;Yonghee Kim;Jeong Ik Lee;Sung Joong Kim
    • Nuclear Engineering and Technology
    • /
    • v.56 no.7
    • /
    • pp.2534-2544
    • /
    • 2024
  • This paper proposes a flooding safety system (FSS) and its operation strategy that can provide long-term safety and effective maintenance for modules of small modular reactor (SMR) and metal containment maintained at dried environment during normal operation. During hypothesized accidents, the FSS re-collects the evaporated steam into the common pool by the condenser installed above the common water pool and provides an emergency coolant for the cavities and auxiliary pools. This study suggested that the condensate re-collection strategy using the FSS can effectively delay the depletion of available water in response to the accidents. Without recollection, the achievable grace periods ranged from 44 to 1507 days for six-module and one-module accidents, respectively. However, with a full re-collection (ratio = 1.0), the time to total depletion of emergency coolant was estimated indefinite. Even with a partial re-collection ratio of 0.3, a grace period of 83.5 days could be ensured for a six-module transient. This study reported the effectiveness of condensate re-collection and the FSS as an innovative safety management strategy and system. Employing a condensate re-collection strategy with a high re-collection ratio can enhance the long-term safety and effective convenience of SMR operations and maintenance.

Effects of geometric conditions of blade on Performance of Axial Pan (익형의 기하학적 조건에 따른 축류팬의 성능에 관한 연구)

  • Ahn E. Y.;Kim J. W.;Jeongng E. J.
    • 한국전산유체공학회:학술대회논문집
    • /
    • 2005.04a
    • /
    • pp.25-29
    • /
    • 2005
  • Axial fan is used for the supplement of large amount of flows. Axial blowers show relatively high efficiency of the system. The present model of axial fan is for cooling a condenser in an air-conditioning unit that exhibits tendency toward compact size. In order to realize the compact model, the width of an axial blade should be cut down in axial distance. Main interest lies on the performance of the axial blowing system with blades having shorter chord length. One of the important design parameters for axial fan is the shape of the blades of it. Design of blades includes the cross-sectional shape and its dimension, including the chord length. We consider two types of blades; one is NACA airfoil with normal chord length and the other is with shortening chord length by $10\%$ of normal airfoil. Axial blower with the modified blades is essential for the compact model of an air-conditioner. The other design parameters are same in the two cases. Using a wind tunnel follows ASHRAE standards carries out evaluation of performance of the system. Detail of flows around the blades is prepared by velocity measurements using PIV. According to performance estimation, the axial blower with short chord blade show quite close to the performance results, including flow rate and pressure rise, of the standard one. The reason of the two similar results is that the flowpatterns depend on Reynolds number based on the chord length of a blade. In this investigation, the critical chord length is found, in which the flows near the airfoil are so unstable and the performance of the system is decreased. A series of figures is for the detail information on the flow.

  • PDF

Greenhouse Gas Mitigation Effect Analysis by Establishing Additional Heat Storage System for Combined Heat and Power Plant (열병합발전소에서의 축열조 증설에 의한 온실가스 감축 효과 분석)

  • Kim, Shang Mork;Yoon, Joong Hwan;Lim, Kyoung Mi
    • Journal of Climate Change Research
    • /
    • v.2 no.3
    • /
    • pp.175-189
    • /
    • 2011
  • In this research, we describe the methodology and the quantification about GHG reduction effects, expected by optimization of operation mode according to establishing additional heat storage system of Bundang Combined Cycle Power Plant. As an intermediate form of General Combined Cycle Power Plant and Heat supply only district heating plant, Bundang Combined Cycle Power Plant(and Ilsan, Anyang, Bucheon) is possible to satisfy demand for the electrical load and thermal load capacity at the same time through changes to the operation mode itself. Therefore, through the operating transition of high-efficiency mode that the condenser cooling water is recovered and supplied to district heat and cooling, establishing additional heat storage system have flexible supply ability at the power and heat market. In this research, We calculated using the operating performance for the last three years(2008~2010) and efficiency of each mode-specific values. As a result, GHG reduction effects were calculated as $97.95kg_{-}CO_2/Gcal$ per heat energy 1 Gcal supplied at the heat storage system and we expected emmision reduction effect about $13,500Ton_{-}CO_2/yr$.

Performance Analysis of New Working Solution for Absorption Refrigeration Machine using Treated Sewage (하수처리수이용 신용액 흡수식 냉동기의 성능해석)

  • 권오경;유선일;윤정인
    • Journal of Energy Engineering
    • /
    • v.7 no.2
    • /
    • pp.231-240
    • /
    • 1998
  • The global environmental problems such as CFC, energy losses in heat recovery system as well as summer peak time power demands, the development of high efficiency absorption refrigeration systems is one of the most promising method in this problems. The absorption refrigeration system to utilize treated sewage is available for environmental protection and energy conservation. Simulation analysis on the double-effect absorption refrigeration cucles with parallel or series flow type has been performed. LiBr+LiI+LiCl+LiNO$_3$ solution was selected as the new working fluid. The main purpose of this study is evaluating the possibilities of effective utilization of treated sewage as a cooling water for the absorber and condenser. The other purpose of the present study is to determine the optimum designs and operating conditions based on the operating constraints and the coefficient of performance in the parallel or series flow type. In this study, we found out the characteristic of new working solution through the cycle simulation and compared LiBr solution to evaluate. The absorption refrigeration machine using the new working fluid was obtained better results COP rise and compactness of system by comparison with LiBr solution.

  • PDF

Cooling Performance of Horizontal Type Geothermal Heat Pump System for Protected Horticulture (시설원예를 위한 수평형 지열 히트펌프의 냉방성능 해석)

  • Ryou, Young-Sun;Kang, Youn-Ku;Kang, Geum-Chun;Kim, Young-Joong;Paek, Yee
    • Journal of Bio-Environment Control
    • /
    • v.17 no.2
    • /
    • pp.90-95
    • /
    • 2008
  • It has become a big matter of concerns that the skill and measures against reduction of energy and cost for heating a protected horticultural greenhouse were prepared. But in these days necessity of cooling a protected horticultural greenhouse is on the rise from partial high value added farm products. In this study, therefore, a horizontal type geothermal heat pump system with 10 RT scale to heat and cool a protected horticultural greenhouse and be considered to be cheaper than a vertical type geothermal heat pump system was installed in greenhouse with area of $240\;m^2$. And cooling performances of this system were analysed. As condenser outlet temperature of heat transfer medium fluid rose from $40^{\circ}C$ to $58^{\circ}C$, power consumption of the heat pump was an upturn from 11.5 kW to 15 kW and high pressure rose from 1,617 kPa to 2,450 kPa. Cooling COP had the trend that the higher the ground temperature at 1.75 m went, the lower the COP went. The COP was 2.7 at ground temperature at 1.75 m depth of $25.5^{\circ}C$ and 2.0 at the temperature of $33.5^{\circ}C$ and the heat extraction rate from the greenhouse were 28.8 kW, 26.5 kW respectively at the same ground temperature range. 8 hours after the heat pump was operated, the temperature of ground at 60 cm and 150 cm depth buried a geothermal heat exchanger rose $14.3^{\circ}C$, $15.3^{\circ}C$ respectively, but the temperature of ground at the same depth not buried rose $2.4^{\circ}C$, $4.3^{\circ}C$ respectively. The temperature of heat transfer medium fluid fell $7.5^{\circ}C$ after the fluid passed through geothermal heat exchanger and the fluid rejected average 46 kW to the 1.5 m depth ground. It analyzed the geothermal heat exchanger rejected average 36.8 W/m of the geothermal heat exchanger. Fan coil units in the greenhouse extracted average 28.2 kW from the greenhouse air and the temperature of heat transfer medium fluid rose $4.2^{\circ}C$after the fluid passing through fan coil units. It was analyzed the accumulation energy of thermal storage thank was 321 MJ in 3 hours and the rejection energy of the tank was 313 MJ in 4 hours.

Numerical Study of the Heat Removal Performance for a Passive Containment Cooling System using MARS-KS with a New Empirical Correlation of Steam Condensation (새로운 응축열전달계수 상관식이 적용된 MARS-KS를 활용한 원자로건물 피동냉각계통 열제거 성능의 수치적 연구)

  • Jang, Yeong-Jun;Lee, Yeon-Gun;Kim, Sin;Lim, Sang-Gyu
    • Journal of Energy Engineering
    • /
    • v.27 no.4
    • /
    • pp.27-35
    • /
    • 2018
  • The passive containment cooling system (PCCS) has been designed to remove the released decay heat during the accident by means of the condensation heat transfer phenomenon to guarantee the safety of the nuclear power plant. The heat removal performance of the PCCS is mainly governed by the condensation heat transfer of the steam-air mixture. In this study, the heat removal performance of the PCCS was evaluated by using the MARS-KS code with a new empirical correlation for steam condensation in the presence of a noncondensable gas. A new empirical correlation implemented into the MARS-KS code was developed as a function of parameters that affect the condensation heat transfer coefficient, such as the pressure, the wall subcooling, the noncondensable gas mass fraction and the aspect ratio of the condenser tube. The empirical correlation was applied to the MARS-KS code to replace the default Colburn-Hougen model. The various thermal-hydraulic parameters during the operation of the PCCS follonwing a large-break loss-of-coolant-accident were analyzed. The transient pressure behavior inside the containment from the MARS-KS with the empirical correlation was compared with calculated with the Colburn-Hougen model.

Performance of R1234yf and R1234yf/R134a Mixture under Mobile Air-conditioner Operating Conditions (R1234yf와 R1234yf/R134a의 자동차 에어컨 작동 조건에서의 성능 평가)

  • Park, Ki-Jung;Lee, Yo-Han;Choe, Dae-Seong;Jung, Dong-Soo
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.22 no.12
    • /
    • pp.837-844
    • /
    • 2010
  • In this study, performance of R1234yf and R1234yf/R134a mixture is measured on a heat pump bench tester in an attempt to substitute R134a used widely in mobile air conditioners (MACs). The bench tester is equipped with a open type compressor providing a nominal capacity of 3.5 kW. All tests are conducted under the summer cooling and winter heating conditions of 7/4 $5^{\circ}C$ and $-7/41^{\circ}C$ in the evaporator and condenser, respectively. For R1234yf/R134a mixture, measurements are made at 5%, 10%, and 15% of R134a by mass. Test results show that the coefficient of performance (COP) and capacity of R1234yf are up to 2.7% and 4.0% lower than those of R134a, respectively. For R1234yf/R134a mixture, the COP and capacity are up to 3.9% lower and 3.6% higher than those of R134a. For R1234yf and R1234yf/R134a mixture, the compressor discharge temperature is $4.1{\sim}6.7^{\circ}C$ lower than that of R134a while the amount of charge is reduced up to 11% as compared to R134a. 90%R1234yf/10%R134a is a better refrigerant than pure R1234yf in that it is less flammable and more compatible with existing R134a system. Based upon the results, it is concluded that R1234yf and R1234yf/R134a mixture are long term environmentally friendly solutions to mobile air-conditioners due to their excellent environmental properties with acceptable performance.

A comparative study on the simulation of single-stage and multi-stage refrigeration cycle using propane as a refrigerant (프로판 냉매를 활용한 단일 및 다단 냉동 사이클의 전산모사 비교 연구)

  • Noh, Sanggyun
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.15 no.5
    • /
    • pp.3327-3335
    • /
    • 2014
  • In this study, comparison works have been performed for single-stage and multi-stage refrigeration cycle using propane as a refrigerant in order to cool down the natural gas stream. A comparative analysis has been performed for a single, two, three and four stage refrigeration cycle using propane as a refrigerant for cooling the natural gas stream. For the simulation, natural gas feedstock properties supplied by KOGAS were utilized and Peng-Robinson equation of state model was used. As the number of compression stages increase, the condenser heat duty is decreased. The refrigeration heat duty for a four-stage refrigeration cycle is decreased by 20.36% compared to that for a single-stage refrigeration cycle. Moreover, the total refrigerant circulation rate for a four-stage refrigeration system is was reduced by 14.53% compared to the single stage refrigeration cycle. The total compression power for a four-stage compression was reduced by 41.61% compared to the single stage compression.