Transient CFD 모사기법을 이용한 정수지 최적설계 사례연구 (Case study on Remodeling Clearwell Hydraulic Structure using Transient CFD Simulation Technique)

  • 김선진;김성수;박노석;차민환;왕창근
    • 상하수도학회지
    • /
    • 제24권4호
    • /
    • pp.425-432
    • /
    • 2010
  • From the results of tracer test for the existing clearwell in Y water treatment plant, $T_{10}$ and T10/T were calculated as 150 min and 0.24, respectively. Therefore it required the modification schemes for improving hydraulic efficiency, surrogated by $T_{10}$ and $T_{10}$/T, and disinfection performance. In this study, using transient CFD(Computational Fluid Dynamics) simulation technique, tracer tests on dynamic condition for the suggested schemes were simulated. From the results of simulation, it was revealed that 8~6 baffles are necessary to guarantee the disinfection ability in the existing clearwell. Also, installing orifice baffle in the vicinity of inlet could increase plug flow fraction within clearwell.

정수지 내 추적자 실험과 CFD(전산유체역학)의 상관관계 분석 (Case study comparisons of computational fluid dynamics modeling versus tracer test to evaluate the hydraulic efficiency of clearwell)

  • 김태균;최영준;조영만
    • 상하수도학회지
    • /
    • 제25권5호
    • /
    • pp.635-642
    • /
    • 2011
  • Hydraulic efficiency was a vital component in evaluating the disinfection capability of clearwell. Current practice evaluates these system based on the tracer test only. In this paper, CFD(Computational Fluid Dynamics) was applied on the clearwell for alternating or supplementing the tracer test. The baffle factor derived from the CFD modeling closely matched the values obtained from full scale tracer testing. And, for suggesting proper numerical model in clearwell; the turbulence model, discretization scheme, convergence criteria were investigated through separate simulation runs. The model validation was conducted by comparing the simulated data with experimental data. In the turbulence model, the realizable ${\kappa}-{\varepsilon}$ model and the standard ${\kappa}-{\varepsilon}$ model were found to be more appropriate than RNG ${\kappa}-{\varepsilon}$ model. The residuals of convergence criteria should be used as not $10^{-3}$ but $10^{-4}$ or $10^{-5}$. In discretization scheme, the difference of simulated values in 1st, 2nd, 3rd upwind scheme was found to be insignificant. Moreover, the result of this study suggest that CFD modeling can be a reliable alternative to tracer testing for evaluating the hydraulic efficiency.

정수지의 형상과 유입 유량이 T10에 미치는 영향 연구 (Effect of Shape and Flow Rate on T10 in Clearwell)

  • 신은허;김성훈;박희경;안재찬;최재호;최영준
    • 상하수도학회지
    • /
    • 제19권6호
    • /
    • pp.819-826
    • /
    • 2005
  • To guarantee the disinfection ability in clearwell, a value of CT is considered where C[mg/l] is disinfectant residual at the exit of clearwell and T[min] means $T_{10}$, the contact time when 10% of tracer is out of clearwell after introducing the tracer at the inlet. To meet a CT value required, increasing the C value is not recommended because high C value can increase potential of producing disinfection by product like THMs. Increasing the hydraulic efficiency surrogated by $T_{10}$ is thus an option widely recommended. Right now, it is widely adopted estimating $T_{10}$ considering LW ratio only due to the suggestions of previous researches. The authors think however there are other factors to consider including shape, flow rate, configuration of inlet and outlet, and the existence of intra basin. This study is initiated to closely look at the effects of two factor on hydraulic efficiency. The factors are shape and inlet flow velocity, i.e., inflow. For that, computational fluid dynamics (CFD) model is developed and pilot test is also carried out. The results show that at a L/W ratio, disinfection ability is overestimated with larger length in shape and higher inlet flow velocity. This suggests that in determining $T_{10}$, the shapes of clearwell and inlet flow velocity should also be considered as well as L/W ratio.

정수지 내 유동 특성과 유공벽을 이용한 소독능 변화에 대한 수치 해석적 연구 (Numerical Analysis for Characteristics of Flow Fields and Disinfection Performances in the Clearwell with a Porous media Wall)

  • 이석원;리광훈;구자용
    • 상하수도학회지
    • /
    • 제21권6호
    • /
    • pp.755-761
    • /
    • 2007
  • Disinfection performance in clearwell is generally measured by CT, which is expressed by $C{\times}T$. C is represented by disinfection concentration, and T is represented by $T_{10}$ which means 90% contact time in clearwell. In order to improve Disinfection performance, augmentation of $T_{10}$ is required. Guide wall has been generally used to improve $T_{10}$ because $T_{10}$ changes according to flow field. In this study, porous media is proposed instead of guide wall, and disinfection performance between guide wall and porous media wall are compared. Flow field and $T_{10}$ in each clearwell are investigated as well. Improved Disinfection performance appear in case of porous media wall compare to guide wall, and best performance occur in porosity factor ${\beta}$ 1e+4.

도류벽 형태에 따른 정수지 내 유동 특성과 소독능 변화에 대한 수치 해석적 연구 (Numerical Analysis for Characteristic of Flow and Disinfection Performance with Variation of Guide Wall in Clearwell)

  • 이석원;박준정;리광훈
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2006년도 하계학술발표대회 논문집
    • /
    • pp.767-772
    • /
    • 2006
  • The SWTR(Surface Water Treatment Rule) requires achieving removal 99.9% Giardia and 99.99% Virus. To remove Giardia and Virus, disinfection process is essential process. CT is important index for Disinfection performance. CT value is expressed by CXT. C is represented by disinfection concentration and T is represented by $T_{10}$ which means 90% contact time in clearwell. To improve Disinfection performance, it is desirable to increase $T_{10}$. Primary factor affected $T_{10}$ is flow Pattern. Because guide wall change that flow pattern is uniform, we have installed guide wall to increase $T_{10}$. In this paper, we have performed numerical analysis for clearwell installed symmetric guide wall and center divided guide wall using CFD. We have analyzed flow pattern and $T_{10}$ in each clearwell. And. we compare symmetric guide wall with center divided guide wall in flow pattern and $T_{10}$.

  • PDF

정수지 내부 단락류 발생 평가 : Part B. 내부 단락류 평가 방법의 현장 적용을 통한 내부 도류벽과 정류벽을 이용한 T10/T 증가분석 (Internal Short-circuiting Estimation in Clearwell : Part B. Improving T10/T Using Intra Basin and Diffuser Wall by Applying ISEM to Field)

  • 신은허;이승재;김성훈;박희경
    • 상하수도학회지
    • /
    • 제22권1호
    • /
    • pp.113-120
    • /
    • 2008
  • A large majority of clearwell must be modified with maintaining the present baffles since they were underground built with the material like concrete. Therefore it is unreasonable to apply the previous research in clearwell modification which is studied with the assumption that distance between baffles is constant. In this study, internal short-circuiting estimation method (ISEM), which has the advantage of being applied at any condition, is applied to evaluate modification of A clearwell and modify B and C clerwell which have unusual characteristics. After analyzing the hydraulic efficiency at current state, modifications, where baffles, intra basins and diffuser walls are additionally installed, are considered and evaluate using ISEM. And the effect of intra basin and diffuser wall on $T_{10}/T$ is estimated and application feasibility of ISEM is evaluated. The improvement of intra basins is almost same with that of baffles. Also, short-circuiting in effluent zone can be reduced with the same level of channel zone if intra basin is added in effluent zone. However, effect range is restricted to the next channel zone. Diffuser wall can obtain the lower ISI than minimum ISI of cases where baffles and intra basins are installed. Therefore, additional improvement of $T_{10}/T$ value can be expected after $T_{10}/T$ value converges maximum only using baffles

정수지내 사류지역이 수리학적 효율에 미치는 영향 연구 (The Effect of Dead Zone on Hydraulic Efficiency in Clearwell)

  • 이승재;신은허;김성훈;박희경
    • 상하수도학회지
    • /
    • 제21권2호
    • /
    • pp.177-185
    • /
    • 2007
  • Hydraulic efficiency($T_{10}/T$) in clearwell is often estimated by L/W ratio. However, this estimation is not accurate because other factors which give an effect on hydraulic efficiency such as shape of basin, diffuser wall and intra-basin is ignored. Therefore, in this research, hydraulic efficiency is predicted by the quantitative analysis of dead zone using CFD simulation in a pilot scale clearwell. The results show that the reason why higher L/W ratio increase the hydraulic efficiency is to decrease the dead zone of linear region which is located between baffles. Diffuser wall or intra-basin also affects on hydraulic efficiency with this process. Also, we conclude that hydraulic efficiency can not be reached to 0.8 or higher.

정수지 내부 단락류 발생 평가 : Part A. 정수장 내부 단락류 분석을 통한 장폭비와 형태가 T10/T 값에 미치는 영향 연구 (Internal Short-circuiting Estimation in Clearwell : Part A. Improving T10/T Using Intra Basin and Diffuser Wall by Applying ISEM to Field)

  • 신은허;이승재;김성훈;박희경
    • 상하수도학회지
    • /
    • 제22권1호
    • /
    • pp.105-112
    • /
    • 2008
  • Disinfection is a basic and effective microorganism inactivation method and historically contributed a decrease in waterborne diseases. To guarantee the disinfection ability, improving T in CT value is important. Many indexes are used to estimate the hydraulic efficiency, however, these are black-box analysis. Therefore it is need to develope new estimation method. In this study, internal short-circuiting estimation method (ISEM) is developed using CFD and we inquire into the factor which causes increase of $T_{10}/T$ value as LW ratio increases. And the effect of shape on the relation of LW ratio and $T_{10}/T$ is analyzed. As LW ratio increases, internal short-circuiting index (ISI) of influent and effluent zone is rapidly reduced and recirculation and dead zone are reduced in channel zone. Therefore, as the $T_{10}/T$ value converges maximum value, ISI curve is changed from "V" shape to "U" shape and hydraulic efficiency is improved especially in downstream portion of clearwell. The less the shape ratio(width/length of clearwell) is the less the $T_{10}/T$ value is at a same LW ratio because the portion of turning zone increases as shape ration decreases, therefore more boundary separation is generated.

전산유체를 활용한 정수지 최적 도류벽 형태 및 경제적인 장폭비 산정 (Evaluation of Economic L/W Ratio and the Best Shape of Baffle in Clearwell by Using CFD)

  • 조영만;노재순;빈재훈;김태균;최영준
    • 대한환경공학회지
    • /
    • 제33권6호
    • /
    • pp.432-438
    • /
    • 2011
  • 현재 국내 정수지 도류벽은 형태와 장폭비에 대한 명확한 기준이 없고 장폭비가 너무 작아 소독능을 만족하지 못하거나 지나치게 큰 장폭비로 비경제적인 설계를 하는 등 많은 혼란을 겪고 있어 수리적으로 유리한 도류벽의 형태와 경제적인 장폭비를 결정하는 것이 시급한 실정이다. 본 연구는 다양한 도류벽의 형태와 장폭비에 대해 전산유체역학 기법을 활용하여 수리적으로 가장 유리한 도류벽의 형태를 제시하고 가장 경제적인 장폭비를 도출하였다. 연구결과, 정수지내 도류벽의 형태는 동일한 형태와 구조라 하더라도 수류의 방향전환 횟수가 적은 구조가 수리적으로 유리하다. 둘째, 최적 도류벽 형태는 좌우 우류식(model 2)이며 최악의 형태는 두 방향으로 분산되고 다시 모아지는 분산형(model 4) 형태이다. 좌우 우류식은 분산형보다 도류벽의 개수를 67% 정도 줄일 수 있다. 셋째, 좌우 우류식 도류벽인 경우 경제적인 장폭비는 30~50이며 50을 초과할 경우 공사비 대비 $T_{10}/T$ 값의 증가량이 미미하여 경제적이지 못하다.

소독능을 고려한 송수펌프 최적운영기법 개발 (Development of the method for optimal water supply pump operation considering disinfection performance)

  • 형진석;김기범;서지원;김태현;구자용
    • 상하수도학회지
    • /
    • 제32권5호
    • /
    • pp.421-434
    • /
    • 2018
  • Water supply/intake pumps operation use 70~80% of power costs in water treatment plants. In the water treatment plant, seasonal and hourly differential electricity rates are applied, so proper pump scheduling can yield power cost savings. Accordingly, the purpose of this study was to develop an optimal water supply pump scheduling scheme. An optimal operation method of water supply pumps by using genetic algorithm was developed. Also, a method to minimize power cost for water supply pump operation based on pump performance derived from the thermodynamic pump efficiency measurement method was proposed. Water level constraints to provide sufficient disinfection performance in a clearwell and reservoirs were calibrated. In addition, continuous operation time constraints were calibrated to prevent frequent pump switching. As a result of optimization, savings ratios during 7 days in winter and summer were 4.5% and 5.1%, respectively. In this study, the method for optimal water pump operation was developed to secure disinfection performance in the clearwell and to save power cost. It is expected that it will be used as a more advanced optimal water pump operation method through further studies such as water demand forecasting and efficiency according to pump combination.