• Title/Summary/Keyword: cable impedance

Search Result 132, Processing Time 0.02 seconds

Numerical Simulation of Electro-Mechanical Impedance Response in Cable-Anchor Connection Interlace

  • Nguyen, Khac-Duy;Kim, Jeong-Tae
    • Journal of the Korean Society for Nondestructive Testing
    • /
    • v.31 no.1
    • /
    • pp.11-23
    • /
    • 2011
  • In this study, a finite element(FE) analysis on electro-mechanical impedance response of cable-anchor connection interface under various anchor force is presented. In order to achieve the objective, the following approaches are implemented. Firstly, an interface washer coupled with piezoelectric(PZT) material is designed for monitoring cable-force loss. The interface washer is a small aluminum plate on which a PZT patch is surface-bonded. Cable-force loss could be monitored by installing the interface washer between the anchor plate and the anchorage of cable-anchor connection and examining the changes of impedance of the interface washer. Secondly, a FE model for cable-anchor connection is established to examine the effect of cable-force on impedance response of interface washer. Also, the effects of geometrical and material properties of the interface washer on impedance responses under various cable-forces are investigated. Finally, validation of the FE analysis is experimentally evaluated by a lab-scale cable-anchor connection.

Investigation on the inductive and resistive fault current limiting HTS power cable

  • Lee, Sangyoon;Choi, Jongho;Kim, Dongmin;Kwon, Yonghyun;Kim, Seokho;Sim, Kideok;Cho, Jeonwook
    • Progress in Superconductivity and Cryogenics
    • /
    • v.16 no.2
    • /
    • pp.59-63
    • /
    • 2014
  • HTS power cable bypass the fault current through the former to protect superconducting tapes. On the other hand, the fault current limiting (FCL) power cable can be considered to mitigate the fault current using its increased inductance and resistance. Using the increased resistance of the cable is similar to the conventional resistive fault current limiter. In case of HTS power cable, the magnetic field of HTS power cable is mostly shielded by the induced current on the shield layer during normal operation. However, quench occurs at the shield layer and its current is kept below its critical current at the fault condition. Consequently, the magnetic field starts to spread out and it generates additional inductive impedance of the cable. The inductive impedance can be enhanced more by installing materials of high magnetic susceptibility around the HTS power cable. It is a concept of SFCL power cable. In this paper, a sample SFCL power cable is suggested and experimental results are presented to investigate the effect of iron cover on the impedance generation. The tests results are analyzed to verify the generation of the inductive and resistive impedance. The analysis results suggest the possible applications of the SFCL power cable to reduce the fault current in a real grid.

Increased impedance by quench at a shield layer of HTS power cable for fault current limiting function

  • Choi, Youngjun;Kim, Dongmin;Cho, Jeonwook;Sim, Kideok;Kim, Sungkyu;Kim, Seokho
    • Progress in Superconductivity and Cryogenics
    • /
    • v.21 no.4
    • /
    • pp.59-63
    • /
    • 2019
  • To reduce the fault current below the current capacity of a circuit breaker, researches on HTS (High Temperature Superconductor) power cables with fault current limiting (FCL) function are increasing. An FCL HTS power cable transports current with low a impedance during normal operation. Yet, it limits the fault current by an increased inductive or resistive impedance of conducting layer when quench occurs at the FCL HTS power cable by the large fault current. An inductive type FCL HTS power cable uses increased inductive impendence caused by leakage magnetic flux outside the cable core when the quench occurs at a shield layer losing the magnetic shielding effect. Therefore, it has an advantage of less resistive heating than resistive type FCL HTS power cable and temperature increase is suppressed. This paper describes an ideal circuit model for the FCL HTS power cable to investigate the effectiveness of increased inductive impedance when quench occurs at the shield layer. Then, FEM analysis is presented with a simplified model cable composed of various iron yokes to investigate the effect of the shape of yoke on the generation of the inductive impedance.

Measurement and Analysis of Line Impedance in Underground Cables (지중케이블 선로 임피던스 실측 및 분석)

  • Ha, C.W.;Kim, J.N.
    • Proceedings of the KIEE Conference
    • /
    • 2003.07a
    • /
    • pp.205-207
    • /
    • 2003
  • The line impedance is important data that is applied in all analysis fields of electric power system like power flow, fault current, stability and relay calculation etc. Usually, impedance can be accurately calculated in case of overhead line. However, in case of power cables or combined transmission lines, impedance can not be accurately calculated because cable systems have the sheath, grounding wires, and earth resistance. Therefore, if there is a fault in cable system, these terms will severely be caused much error to calculation of impedance. Therefore, the line impedance were measured for this study in an actual power system of underground cables, and were analyzed by a generalized circuit analysis program EMTP for comparison with the measured value. These analysis result is considered to become foundation of impedance calculation for underground cable.

  • PDF

The line impedance calculation and measurement of the underground transmission cable (지중 송전 케이블 선로임피던스 계산 및 실측)

  • Kim, Nam-Yul;Kim, Joung-Yun;Heo, Hoi-Deok;Lee, Su-Kil
    • Proceedings of the KIEE Conference
    • /
    • 2006.11a
    • /
    • pp.405-407
    • /
    • 2006
  • The power system analysis based on the accurate impedance of the individual underground cable, which is the inter connected to a large power system, is required. A study on calculation method of impedance allowable current for underground cables. furthermore, various methods of bonding and earthing the sheath have been used for the purpose of eliminating or reducing the sheath losses. the effectes of bonding and earthing must be includied in impedances. therefore, the subject of predicting thermal performance of soil and cable systems has been received increasing attension. for these problems, this paper describes a general formulation of impedance that is based on the effect of crossbonding and earthing of the sheath on the 66kV, 132kV and 220kV underground cable systems. also the work is presented, for calculating the temperature rise of power cable and soil.

  • PDF

Multi-Impedance Change Localization of the On-Voltage Power Cable Using Wavelet Transform Based Time-Frequency Domain Reflectometry (웨이블릿 변환 기반 시간-주파수 영역 반사파 계측법을 이용한 활선 상태 전력 케이블의 중복 임피던스 변화 지점 추정)

  • Lee, Sin Ho;Choi, Yoon Ho;Park, Jin Bae
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.62 no.5
    • /
    • pp.667-672
    • /
    • 2013
  • In this paper, we propose a multi-impedance changes localization method of on-voltage underground power cable using the wavelet transform based time-frequency domain reflectometry (WTFDR). To localize the impedance change in on-voltage power cable, the TFDR is the most suitable among reflectometries because the inductive coupler is used to inject the reference signal to the live cable. At this time, the actual on-voltage power cable has multi-impedance changes such as the automatic section switches and the auto load transfer switches. However, when the multi-impedance changes are generated in the close range, the conventional TFDR has the cross term interference problem because of the nonlinear characteristics of the Wigner-Ville distribution. To solve the problem, the wavelet transform (WT) is used because it has the linearity. That is, using WTFDR, the cross term interference is not generated in multi-impedance changes due to the linearity of the WT. To confirm the effectiveness and accuracy of the proposed method, the actual experiments are carried out for the on-voltage underground power cable.

Finite Element Analysis on Impedance Parameters of Anchor Plate of Structural Cables Under Cable Force Changes (구조용 케이블의 장력 변화에 따른 정착부의 임피던스 특성에 대한 유한요소해석)

  • Nguyen, Khac-Duy;Park, Jae-Hyung;Hong, Dong-Soo;Lee, Ju-Won;Kim, Jeong-Tae;Na, Won-Bae
    • Proceedings of the Computational Structural Engineering Institute Conference
    • /
    • 2010.04a
    • /
    • pp.783-786
    • /
    • 2010
  • This paper presents a finite element analysis on impedance parameters of anchor plates of structural cables under the change in cable forces. To achieve the objective, four approaches are implemented as follows: Firstly, theoretical background of electro-mechanical impedance is described. Secondly, anchor plates of structural cables are selected to experimentally examine the relationship between impedance parameters and cable force changes. Thirdly, finite element analysis is performed to verify the experimental results. Fourthly, a comparison between the experimental and numerical analysis on impedance parameters of anchor plate of structural cables under cable force changes is carried out.

  • PDF

Measurement of Transfer Impedance on Shielded Multiconductor Telecommunication Cables using IEC 96-1 Line Injection Method (IEC 96-1 Line Injection Method를 이용한 다 도체 통신케이블 차폐층의 전달임피던스 측정)

  • 이현영;오호석;박동철
    • The Journal of Korean Institute of Electromagnetic Engineering and Science
    • /
    • v.14 no.4
    • /
    • pp.377-383
    • /
    • 2003
  • As the high-speed data communications such as xDSL using the existing copper cable come into wide use, the electromagnetic coupling characteristics of telecommunication cables become more significant. In order to describe the screening performance of telecommunication cable, the transfer impedance of cable shield is required. This paper describes the transfer impedance for two types of telecommunication cables using the line injection method of IEC 96-1. Results are analyzed to show how the materials of cable shields, the positioning of the injection line and of the inner conductor of the CUT(Cable Under Test) affect the value of transfer impedance. We then propose the transfer impedance model of telecommunication cable based on the measurements.

A Study on the Sequence Impedance Modeling of Underground Transmission Systems (지중송전선로의 대칭분 임피던스 모델링에 관한 연구)

  • Hwang, Young-Rok;Kim, Kyung-Chul
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.28 no.6
    • /
    • pp.60-67
    • /
    • 2014
  • Power system fault analysis is commonly based on well-known symmetrical component method, which describes power system elements by positive, negative and zero sequence impedance. The majority of fault in transmission lines is unbalanced fault, such as line-to-ground faults, so that both positive and zero sequence impedance is required for fault analysis. When unbalanced fault occurs, zero sequence current flows through earth and ground wires in overhead transmission systems and through cable sheaths and earth in underground transmission systems. Since zero sequence current distribution between cable sheath and earth is dependent on both sheath bondings and grounding configurations, care must be taken to calculate zero sequence impedance of underground cable transmission lines. In this paper, EMTP-based sequence impedance calculation method was described and applied to 345kV cable transmission systems. Calculation results showed that detailed circuit analysis is desirable to avoid possible errors of sequence impedance calculation resulted from various configuration of cable sheath bonding and grounding in underground cable transmission systems.

Improvement of Digital Distance Relaying Algorithm Using Wavelet Transform in Combined Transmission Line (웨이브렛을 이용한 혼합송전선로에서의 거리계전 알고리즘 개선)

  • 정채균;김경호;하체웅;이종범;윤양웅
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.52 no.10
    • /
    • pp.593-601
    • /
    • 2003
  • Distance realy is tripped by the line impedance calculated at the relay point. Accordingly the accurate operation depends on the precise calculation of line impedance. Impedance can be accurately calculated in case of overhead line. However, in case of power cables or combined transmission lines, impedance can not be accurately calculated because cable systems have the sheath, grounding resistance, and sheath voltage limiters(SVLs). There are also several grounding systems in cable systems. Therefore, if there is a fault in cable systems, these terms will severely be caused much error to calculation of impedance. Accordingly the proper compensation should be developed for the correct operation of the distance relay. This paper presents the distance calculating algorithm in combined transmission line with power cable using wavelet transform. In order to achieve such purpose, judgement method to discriminate the fault section in both sections was proposed using D1 coefficient summation in db4. And also, error compensation value was proposed for correct calculation of impedance in power cables section.