A Study on the Design of Microcomputer Processor Algorithm for Electrical Fire Prediction (전기화재 예측을 위한 마이컴 프로세서 알고리즘 설계에 관한 연구)

  • Kwak, Dong-kurl;Choi, Jung-Kyu;Lee, Bong-Seob;Choi, Shin-Hyeong
    • Proceedings of the KIPE Conference
    • /
    • 2015.07a
    • /
    • pp.11-12
    • /
    • 2015
  • This study has looked into ways to cut the power supply by predicting electrical fire that may occur in low-voltage cable, which is most frequently used in industrial settings and households. In addition, we have designed a system that cuts off electricity to prevent the fire upon occurrence of events that may cause electrical fire, including short circuit, tracking and contact failure. A lot of previous researches have designed arc suppressors built in analog circuit, which left much to be desired such as difficulty in remote control and inability to identify the location of arc suppressor when it is activated. To address these issues, the study seeks to develop an arc suppressor using micom and to verify its performance through simulations designed to detect arc faults.

  • PDF

The Effects of Optical Cable Fault on Customer Complaints (광케이블 고장이 고객 불만에 미치는 영향 연구)

  • Jung, So-Ki;Cha, Kyoung Cheon
    • The Journal of Korean Institute of Communications and Information Sciences
    • /
    • v.40 no.2
    • /
    • pp.325-333
    • /
    • 2015
  • In this paper, we are aim to analysis the effects of optical cable fault on customer complaints. We considered several causes: the elapse time to allow repair from the optical cable fault, whether working day or not, seasonality and human error, external construction, optical cable cutting or core banding that is controllable causes and natural disasters, vehicle crash, fire that is uncontrollable causes. The results of analysis are as follows: First, customer complaints increase through indifferencial relationship when using the production function for the number of expected victims and elapsed time due to the optical cable fault. Second, not only the elapsed time but also controllable variables, human error, external construction, the core cut occurs, increased customer complaints due to optical cable faults.

Characteristics of Fire-induced Thermal-Flowfields in an Underground Utility Tunnel with Ventilation (화재 발생시 환기방식에 따른 지하공동구내 열유동 특성 연구)

  • Kim, Hong-Sik;Hwang, In-Ju;Kim, Yun-Je
    • Proceedings of the KSME Conference
    • /
    • 2003.04a
    • /
    • pp.1845-1850
    • /
    • 2003
  • The underground utility tunnels are important facility as a mainstay of country because of communication developments. The communication and electrical duct banks as well as various utility lines for urban life are installed in the underground utility tunnel systems. If a fire breaks out in this life-line tunnel, the function of the city will be discontinued and the huge damages are occurred. In order to improve the safety of life-line tunnel systems and the fire detection, the behaviors of the fire-induced smoke flow and temperature distribution are investigated. In this study we assumed that the fire is occurred at the contact or connection points of cable. Numerical calculations are carried out using different velocity of ventilation in utility tunnel. The fire source is modeled as a volumetric heat source. Three-dimensional flow and thermal characteristics in the underground tunnel are solved by means of FVM (Finite Volume Method) using SIMPLE algorithm and standard ${\kappa}-{\varepsilon}$ model for Reynolds stress terms. The numerical results of the fire-induced flow characteristics in an underground utility tunnel with different velocity of ventilation are graphically prepared and discussed.

  • PDF

Development of Loaded Stream Fire Extinguishing Systems for Underground Transmission Cables (지중송전선로 접속부용 미분무 강화액 소화설비의 개발연구)

  • Lee, Sung-Mo
    • Fire Science and Engineering
    • /
    • v.22 no.1
    • /
    • pp.93-98
    • /
    • 2008
  • Full-scale fire extinguishment tests were conducted to develop loaded stream fire extinguishing systems for protecting underground transmission cables. The dimension of test mock-up was 5.5m height${\times}3m$ width ${\times}6m$ length, and six 154kV OF cables were piled up. Gasoline was used to ignite cates. Linear heat detection cables were installed on top of 154 kV OF cable and discharge nozzles were installed on the top and sidewalls, respectively. As a result, both surface fires and deap-seated fires were extinguished successfully within the specified 3 minutes by discharging loaded stream agent.

Failure Analysis of Underground Transmission Cable Systems (국내 지중 케이블 고장현황 분석)

  • Kang, Y.W.;Cho, S.B.;Kwak, B.M.;Lim, H.E.;Yoon, H.H.
    • Proceedings of the KIEE Conference
    • /
    • 1999.07e
    • /
    • pp.2377-2379
    • /
    • 1999
  • In order to analyze failure rates of underground transmission power cable systems in Korea, the survey has been performed for the failure cases of cables, joints, and terminations in CV, OF and POF cable systems which occurred from 1983 to 1998. During 16 years, the failure cases due to trips of the systems were 47 among the total 108 cases, These 47 cases could be divided into internal reasons(manufacture/installation, corrosion and degradation) of 16 cases and external reasons (external mechanical damages, lightning, fire. etc.) of 31 cases. For the 154 kV cable systems during 12 years from 1987 to 1998, total failure rate was 0.0057 [case/100C-km/year] and internal reason failure rate was 0.0020 [case/100C-km/Year], which is similar to those of foreign countries. Also, the many cases of internal reason failures occurred in the early stage after the operations due to incorrect installations. This implies that the installation process is very important and some diagnostic tests such as PD measurement are needed besides after laying test.

  • PDF

Diagnosis of Poor Contact Fault in the Power Cable Using SSTDR (SSTDR을 이용한 케이블의 접촉 불량 고장 진단)

  • Kim, Taek-Hee;Jeon, Jeong-Chay
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.65 no.8
    • /
    • pp.1442-1449
    • /
    • 2016
  • This paper proposes a diagnosis to detecting poor contact fault and fault location. Electrical fire by poor contact fault of power cable occupied a large proportion in the total electrical installations. The proposed method has an object to prevent electrical fault in advance. But detecting poor contact fault is difficult to detect fault type and fault location by using conventional reflectometry due to faults generated intermittently and repeatedly on the time change. Therefore, in this paper poor contact fault and fault conditions were defined. System generating poor contact fault produced for the experimental setup. SSTDR and algorithm of reference signal elimination heighten performance detecting poor contact fault on live power cable. The diagnosis methods of signal process and analysis of reflected signal was proposed for detecting poor contact fault and fault location. The poor contact fault and location had been detected through proposed diagnosis methods. The fault location and error rate of detection were verified detecting accuracy by experiment results.

Structural Safety Evaluation of Cable Stayed Bridge based on Cable Damage Scenarios (사장교 케이블 손상 사나리오에 따른 구조 안전 수준 평가)

  • Kim, Ga Young;Seo, Dong-Woo
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.19 no.7
    • /
    • pp.105-111
    • /
    • 2018
  • This study aims to evaluate the safety for cable stayed bridge due to damages on the cable system. Many cable supported bridges, including cable stayed bridge and suspension bridge, have been built in the Korean peninsula. This requires efficient maintenance and management since this structure has complex structural components and system. This large structure also often faces risks either from manmade or natural phenomenon. In 2015 one cable-stayed bridge in South Korea had been struck by a bolt of lightning on the cables. This event had led to fire on cables. These cables had been damaged and putting the bridge at risk. This bridge was back in used after a few weeks of investigations and replacements of the cables. However, enormous social and economic expense were paid for recovery. After this event risk based management for infra structures is required by public demands. Therefore, this study was initiated and aimed to evaluate risks on the cable system due to potential damages. In this paper one cable-stayed bridge in South Korea was selected and investigated its safety based on the damage scenarios of cable system for efficient and prompt management, and for supporting decision making. FEM analysis was conducted to evaluate the safety of the bridges due to damages on the cable system.

A Study on Validation Methodology of Fire Retardant Performance for Cables in Nuclear Power Plants (원자력발전소 케이블 난연성능 검증 방법론 개선을 위한 연구)

  • Lee, Sang Kyu;Moon, Young Seob;Yoo, Seong Yeon
    • Journal of the Korean Society of Safety
    • /
    • v.32 no.1
    • /
    • pp.140-144
    • /
    • 2017
  • Fire protection for nuclear power plants should be designed according to the concept of "Defense in Depth" to achieve the reactor safety shutdown. This concept focuses on fire prevention, fire suppression and safe shutdown. Fire prevention is the first line of "Defense in Depth" and the licensee should establish administrative measures to minimize the potential for fire to occur. Administrative measures should include procedures to control handling and use of combustibles. Electrical cables is the major contributor of fire loads in nuclear power plants, therefore electrical cables should be fire retardant. Electrical cables installed in nuclear power plants should pass the flame test in IEEE-383 standard in accordance with NUREG-0800, "Standard Review Plan for the Review of Safety Analysis Reports for Nuclear Power Plants". To assure the fire retardant of electrical cables during design life, both aged and unaged cable specimens should be tested in accordance with IEEE-383. It can be generally thought that the flammability of electrical cables has been increased by wearing as time passed, however the results from fire retardant tests performed in U.S.A and Korea indicate the inconsistent tendency of aging and consequential decrease in flammability. In this study, it is expected that the effective methodology for validation of fire retardant performance would be identified through the review of the results from fire retardant tests.

A Study on the Comparison between an Optical Fiber and a Thermal Sensor Cable for Temperature Monitoring (온도 모니터링을 위한 광섬유 센서와 온도센서 배열 케이블의 비교 연구)

  • Kim, Jung-Yul;Kim, Yoo-Sung;Song, Yoon-Ho
    • Proceedings of the Korean Geotechical Society Conference
    • /
    • 2006.03a
    • /
    • pp.1100-1109
    • /
    • 2006
  • In this study, two different technologies which can measure temperature simultaneously at many points are introduced. One is to use a thermal sensor cable that is comprised of addressable thermal sensors connected in parallel within a single cable. The other is to use an optic fiber with Distributed Temperature Sensing (DTS) system. The difference between two technologies can be summarized as follows. A thermal sensor cable has a concept of 'point sensing' that can measure temperature at accurate position of a thermal sensor. So the accuracy and resolution of temperature measurement are up to the ability of the thermal sensor. Whereas optic fiber sensor has a concept of 'distributed sensing' because temperature is measured by ratio of Stokes and anti-Stokes component intensities of Raman backscatter that is generated when laser pulse travels along an optic fiber. It's resolution is determined by measuring distance, measuring time and spatial resolution. The purpose of this study is that application targets of two temperature measurement techniques are checked in technical and economical phases by examining the strength and weakness of them. Considering the functions and characteristics of two techniques, the thermal sensor cable will be suitable to apply to the assessment of groundwater flow, geothermal distribution and grouting efficiency within 300m distance. It is expected that the optic fiber sensor can be widely utilized at various fields (for example: pipe line inspection, tunnel fire detection, power line monitoring etc.) which need an information of temperature distribution over relatively long distance.