• Title/Summary/Keyword: breaker bar

Search Result 15, Processing Time 0.028 seconds

Optimization ova Mechanism for Power Transfer Breakers (전력변환차단기의 트리거 기구 최적화)

  • 조두현;김권희
    • Proceedings of the Korean Society of Precision Engineering Conference
    • /
    • 2002.05a
    • /
    • pp.735-739
    • /
    • 2002
  • PTB(Power Transfer Breaker) is a device which incorporate the functions of ACB(Air Circuit Breaker) and ATS(Automatic Transfer Switch). ACB is a circuit breaker against overload and ATS is a switching device to transfer the load between two electric power sources. An existing PTB design based upon the 5 bar & cam mechanism has been regarded to be too complex and thus a simpler 4 bar mechanism with trigger lock is proposed. Experimentation and optimization of the trigger lock is presented.

  • PDF

Measurement and Design Review of Contact Force by Garter Spring in Connection between Circuit Breaker and Bus Bar (차단기와 모선과의 연결시 가터스프링에 의한 접촉력의 측정 및 설계 고찰)

  • 조상순;안길영;박우진;오일성
    • Proceedings of the Korean Society of Precision Engineering Conference
    • /
    • 2002.10a
    • /
    • pp.942-945
    • /
    • 2002
  • A garter spring, which is a long. special, close-coiled extension spring with its ends joined to form a ring, is used in connection between vacuum circuit breaker and bus bar in switchgear. To carry short-time current and resist welding at the contact surface in the connection, the garter spring must transmits an uniform contact force to the contact surface through the contact chips arranged in the circumference of bus bar. In this paper, the system for measurement of the contact force by the garter spring is developed. Using the developed measurement system, the design of the connection structure including the garter spring is reviewed to obtain the uniform contact forces in all of contact chips.

  • PDF

Influence of SF6/N2 Gas Mixture Ratios on the Lightning Streamer Propagation Characteristics of 22 kV MV Circuit Breaker

  • Gandhi, R.;Chandrasekar, S.;Nagarajan, C.
    • Journal of Electrical Engineering and Technology
    • /
    • v.13 no.4
    • /
    • pp.1663-1672
    • /
    • 2018
  • In recent times, gas insulated medium voltage (MV) circuit breakers (CB) form a vital component in power system network, considering its advantages such as reduced size and safety margins. Gas insulation characteristics of circuit breakers are generally measured by lightning impulse (LI) test according to IEC standard 60060-1 as a factory routine test. Considering the environmental issues of $SF_6$ gas, many research works are being carried out towards the mixture of $SF_6$ gases for high voltage insulation applications. However, few reports are only available regarding the LI withstand and streamer propagation characteristics (at both positive and negative polarity of waveform) of $SF_6/N_2$ gas mixture insulated medium voltage circuit breakers. In this paper, positive and negative polarity LI tests are carried out on 22 kV medium voltage circuit breaker filled with $SF_6/N_2$ gas mixture at different gas pressures (1-5 bar) and at different gas mixture ratios. Important LI parameters such as breakdown voltage, streamer velocity, time to breakdown and acceleration voltage are evaluated with IEC standard LI ($1.2/50{\mu}s$) waveform. Weibull distribution analysis of LI breakdown voltage data is carried out and 50% probability breakdown voltage, scale parameter and shape parameter are evaluated. Results illustrate that the $25%SF_6+75%N_2$ gas filled insulation considerably enhances the LI withstand and breakdown strength of MV circuit breakers. LI breakdown voltage of circuit breaker under negative polarity shows higher value when compared with positive polarity. Results show that maintaining the gas pressure at 0.3 MPa (3 bar) with 10% $SF_6$ gas mixed with 90% $N_2$ will give optimum lighting impulse withstand performance of 22 kV MV circuit breaker.

Characteristics Analysis of the Solenoid for High-Voltage Circuit Breaker (고전압 차단기용 솔레노이드의 특성해석)

  • 윤소남;류재섭;함영복;노종호
    • Proceedings of the Korean Society of Precision Engineering Conference
    • /
    • 2003.06a
    • /
    • pp.382-385
    • /
    • 2003
  • In this paper, the solenoid for high-voltage circuit breaker which is composed of bobbin, solenoid coil, stationary core and plunger was studied. The solenoid is made of a soft magnetic iron bar with a large number of coil windings. when an electric current passes through this, this stationary core becomes the strong magnet used for hydraulic and pneumatic valve of a solenoid operated valve. For the performance evaluation of the solenoid for high-voltage circuit breaker, electromagnetic characteristics and dynamic characteristics were analyzed. And, the parameters which is related to performance improvement were investigated.

  • PDF

Preliminary Study on the Development of a Platform for the Optimization of Beach Stabilization Measures against Beach Erosion II - Centering on the Development of Physics-Based Morphology Model for the Estimation of an Erosion Rate of Nourished Beach (해역별 최적 해빈 안정화 공법 선정 Platform 개발을 위한 기초연구 II - 양빈 된 해빈 침식률 산정을 위한 물리기반 해빈 지형모형 개발을 중심으로)

  • Cho, Yong Jun
    • Journal of Korean Society of Coastal and Ocean Engineers
    • /
    • v.31 no.5
    • /
    • pp.320-333
    • /
    • 2019
  • In this study, a physics-based 3D morphology model for the estimation of an erosion rate of nourished beach is newly proposed. As a hydrodynamic module, IHFOAM toolbox having its roots on the OpenFoam is used. On the other hand, the morphology model comprised a transport equation for suspended sediment, and Exner type equation derived from the viewpoint of sediment budget with the bed load being taken to accounted. In doing so, the incipient motion of sediment is determined based on the Shields Diagram, while the bottom suspended sediment concentration, the bed load transport rate is figured out using the bottom shearing stress directly calculated from the numerically simulated flow field rather than the conventional quadratic law and frictional coefficient. In order to verify the proposed morphology model, we numerically simulate the nonlinear shoaling, breaking over the uniform beach of 1/m slope, and its ensuing morphology change. Numerical results show that the partially skewed, and asymmetric bottom shearing stresses can be successfully simulated. It was shown that sediments suspended and eroded at the foreshore by wave breaking are gradually drifted toward a shore and accumulated in the process of up-rush, which eventually leads to the formation of swash bar. It is also worth mentioning that the breaker bar formed by the sediments dragged by the back-wash flow which commences at the pinnacle of up-rush as the back-wash flow gets weakened due to the increased depth was successfully duplicated in the numerical simulation.

The Analysis of Temperature and Electric Field due to Contact Failure in Power Substation (수변전설비에서 접점 불량에 따른 열 및 전계 분포 해석)

  • Kim, Ki-Joon
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.29 no.5
    • /
    • pp.307-311
    • /
    • 2016
  • Although there are existing Residual Current Protective Device (RCD) including detect electric leakage and elements such as short circuit and surge, the occurrence of incidents caused by electric faults, including fire, are still constant. The purpose of this study is to analyze the causes of accidents through the electric field distribution in the interpretation of the fault contact breaker. Simulation results by the arc fault has shown the convergence of temperature and electric field to the defect. Through their simulation results, the main cause of erosion phenomena in circuit breaker bar is the electric arc by concentration of electric field not due to dissolve by temperature.

Dynamic Characteristics Analysis of Electric Actuator (EMFA) for Air Circuit Breaker (ACB) with Three-bar Linkage structure (3링크를 적용한 기중차단기용 전자석 조작기(EMFA) 해석)

  • Lee, Seung-Min;Kang, Jong-Ho;Kwak, Sang-Yup;Jung, Hyun-Kyo
    • Proceedings of the KIEE Conference
    • /
    • 2009.04b
    • /
    • pp.97-99
    • /
    • 2009
  • In this paper, a new type of electromagnetic actuator, an electro magnetic force driving actuator (EMFA) is developed and analyzed, applicable to air circuit breaker (ACB). Transient analysis is performed in order to obtain the dynamic characteristics of the EMFA. The distribution of static magnetic flux is obtained using the finite element method (FEM). The coupled problems of electrics and mechanics governing equations are solved using the time difference method (TDM). Also according to interception rate of each contactor, investigation about load condition of contactor spring is conducted, applied it to three-link system. And comparison about dynamic characteristics of three-link simulation and experiment data are performed.

  • PDF

Design Review of Tulip Contactor by Garter Spring (가터스프링에 의한 튤립접촉자의 설계 고찰)

  • Cho, S.S.;Park, W.J.;Ahn, K.Y.;Oh, I.S.
    • Proceedings of the KIEE Conference
    • /
    • 2003.10a
    • /
    • pp.242-245
    • /
    • 2003
  • A garter spring, which is a long, special, close-coiled extension spring with its ends joined to form a ring, is used in tulip contactor between vacuum circuit breaker and bus bar in switchgear. To carry short-time current and resist welding at the contact surface in the tulip contactor, the garter spring must transmits an uniform contact force to the contact surface through the contact chips arranged in the circumference of bus bar. In this paper, the system for measurement of the contact force by the garter spring is developed. Using the developed measurement system, the design of the connection structure including the garter spring is reviewed to obtain the uniform contact forces in all of contact chips.

  • PDF

A Study on the Prevention of Crack Generated in Interface Cu and Epoxy with Painting of Carbon (카본 도포에 따른 Cu-Epoxy 접촉면에서 발생하는 크랙방지에 관한 연구)

  • 송재주;김성훈;황종선;박종광;한병성
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.14 no.7
    • /
    • pp.578-583
    • /
    • 2001
  • The bushing for high voltage and large and power should endure weight of itself and force of pushing from contact with circuit breaker. Like this, epoxy mold bushing has to be strong without fault. However, the external circumstances and internal factors was caused by partial discharge, flashover and dielectric breakdown. Therefore, to remove external factor of defect and to prevent the internal cracks and cavity generated from the contraction on interface of Cu-Epoxy, we should form semi-conductive layer on Cu bar by carbon. Then, the PD properties and the insulation qualities of epoxy mold type bushing was able to improved by roles of cushions for the direction of diameter and by effects fo natural sliding like as separated from conductor for the direction of length. So, in this work, we could prove the method of semi-conductive layer in making the long conductor.

  • PDF

Impact Analysis of Spiral type Electrodes in Vacuum Circuit Breaker (진공회로차단기용 횡자계방식 접점의 충격해석)

  • Park, W.J.;Ahn, K.Y.;Oh, I.S.;Huh, H.
    • Proceedings of the KSME Conference
    • /
    • 2001.06a
    • /
    • pp.895-900
    • /
    • 2001
  • It is very important for impact analysis to reflect the dynamic characteristics of materials as well as the static characteristics. As the dynamic behavior of a material is different from the static(or quasi-static) one due to the inertia effect and the stress wave propagation, an adequate experimental technique has to be developed to obtain the dynamic responses for the corresponding level of the strain rate. To determine the dynamic characteristics of materials, the Hopkinson bar (compression type) experiment is carried out. For using dynamic material properties, Johnson-Cook model is applied in impact analysis with explicit finite element method

  • PDF