• Title/Summary/Keyword: breakdown strength

Search Result 523, Processing Time 0.03 seconds

The Effect of Conducting Particles on Breakdown Phenomena in GIS (GIS내에서 금속이물이 절연파괴에 미치는 영향)

  • Kim, Min-Kyu;Moon, In-Wook;Kim, Youn-Taeg;Kim, Ik-Soo;Lee, Hyeong-Ho
    • Proceedings of the KIEE Conference
    • /
    • 1994.07b
    • /
    • pp.1574-1576
    • /
    • 1994
  • $SF_6$ gas has become an important insulation medium in modern electric power apparatus, because of its high insulation withstand levels and good arc quenching capability. For the application of $SF_6$ gas in GIS the estimation of insulation properties is a fundamental point. Moreover the reduction of withstand levels in case of inhomogeneous fields caused by particles or fixed protrusions is of special interest. It is known that the presence of free conducting particles in GIS can significantly lower the insulating level of $SF_6$ gas at elevated pressure and also it has been recently shown that dielectric strength is greatly reduced by fast transients such as disconnector surges where metallic particles are involved. In this paper, we have disigned the particle test chamber rated 362kV for the purpose of investigating the discharge characteristics in SF6 gas where inhomogenius fields are caused by metallic particles.

  • PDF

Effect of Electrical Stimulation and Delayed Chilling on the Physicochemical Characteristics of Hanwoo Beef (한우 도체에 대한 전기자극 및 지연냉각이 쇠고기의 이화학적 특성에 미치는 영향)

  • 김대곤;안동현;김수민;성삼경
    • Journal of the Korean Society of Food Science and Nutrition
    • /
    • v.27 no.2
    • /
    • pp.207-213
    • /
    • 1998
  • These experiments were carried out to investigate the effects of electrical stimulation(ES) and delayed chilling (DC) on the quality characteristics of Hanwoo beef. The left half carcass was treated with ES(550V, 90sec)within postmortem 30min. The electrical stimulated half carcass was subjected to chilling at 16$^{\circ}C$ for 24hr, and then stored at 2$\pm$2$^{\circ}C$ for 15days (ESDC). The right half carcass was stored at 2$\pm$2$^{\circ}C$ for 15 days (NES). ESDC showed a rapid pH fall and tended to reach to pH5.54 at postmortem 2 hrs. But, there was no consistent effect of electrical stimulation and delayed chilling on meat color, cooking loss and water holding capacity. Myofibril fragmentation index was higher than that of NES during storage. ESDC showed lower shear force value and strength consistently than NES. SDS-PAGE band patterns of myofibrils showed the rapid breakdown of troponin T and troponin I band in ESDC, compared with NES, and revealed the specific band below myosin light chain-2 pattern in ESDC.

  • PDF

Flame Retardancy and Electrical Characteristics of LDPE/EVA Blend Involving Mg(OH)2 and Zinc-borate

  • Ryu, Boo-Hyung;Kim, Gyu-Baek;Jung, Sang-Ho;Cho, Young-Suk
    • Transactions on Electrical and Electronic Materials
    • /
    • v.7 no.6
    • /
    • pp.309-312
    • /
    • 2006
  • This study shows to blend ethylene vinyl acetate(EVA) and a flame retardant agent, $Mg(OH)_{2}$, and synergists, zinc borate for improving flame retardancy of low density polyethylene(LDPE). And it studied the property of flame retardancy of LDPE/EVA blend by the amount of addition through LOI and TGA, estimated the electrical characteristics such as volume resistivity and breakdown strength. The flame retardancy of LDPE/EVA blend was much improved in case of adding zinc borate with 6phr degree, and the electrical characteristics were more or less decreased depending on increasing the amount of addition. Zinc borate used for improving the flame retardancy of LDPE/EVA blend let the added amount of a flame retardant agent, $Mg(OH)_{2}$ limited, and the electrical characteristics decreased extremely by adding a good deal of $Mg(OH)_{2}$.

Development and Test results of the Dielectric Evaluation System for a Helium Gas Cooled HTS Cable (헬륨가스 냉각 고온초전도 케이블의 절연특성 평가 시스템 개발 및 성능평가)

  • Kwag, Dong-Soon;Rodrigo, Horatio
    • Progress in Superconductivity and Cryogenics
    • /
    • v.14 no.1
    • /
    • pp.25-29
    • /
    • 2012
  • The novel type of cable under consideration is cooled by gaseous Helium at elevated pressure. Helium is known for having poor electric breakdown strength; therefore the dielectric capabilities of this type of cable must be tested under conditions similar to the envisaged operation. In order to study the dielectric performance we have designed and built a novel high pressure cryostat rated at 2.17 MPa which has been used for testing model cables of lengths of up to 1 m. The cryostat is an open system where the gas is not re-circulated. This allows maintaining a high purity of the gas. The target temperature range is between 40 K and 70 K. This substantially increases the critical current density of the HTS compared to 77 K, which is the typical temperature of cables cooled by liquid nitrogen. The cryostat presented allows for adjusting the temperature and keeping it constant for the time necessary to run a complete dielectric characterization test. We give a detailed description of the cryostat. Measurements of partial discharge inception voltages as well as the temperature distribution along the model cables as a function of time are presented.

Insulation of Winding and Current Lead of the High-Tc Superconducting Magnets for DC Reactor Type SFCL (DC 리액터형 고온초전도한류기용 고온초전도자석의 권선 및 전류리드의 절연)

  • 양성은;배덕권;전우용;김영식;김상현;고태국
    • Proceedings of the Korea Institute of Applied Superconductivity and Cryogenics Conference
    • /
    • 2003.10a
    • /
    • pp.226-229
    • /
    • 2003
  • Following the successful development of practical high temperature superconducting (HTS) wires, there has been renewed activity in the development of superconducting power equipments. HTS equipments must be operated in the coolant, such as liquid nitrogen (L$N_2$) or cooled by cooler, such as GM-cryocooler to maintain the temperature below critical temperature. In this paper, dielectric strength of some insulating materials, such as epoxy, teflon, and glass fiber reinforced plastic (GFRP) in L$N_2$was measured. Surface breakdown voltage of GFRP which is basic property in design of HTS solenoid coil was measured. Epoxy is a goof insulating material but it is fragile at cryogenic temperature. The multi-layer insulating method of current lead is suggested to compensate this fragile property. It consists of teflon tape layer and epoxy layer fixed with texture. Based on these measurements, the 6.6㎸ class HTS magnet for DC reactor type high-T$_{c}$ superconducting fault current limiter (SFCL) was successfully fabricated and tested.d.

  • PDF

Effect of nanofillers on the dielectric properties of epoxy nanocomposites

  • Wang, Q.;Chen, G.
    • Advances in materials Research
    • /
    • v.1 no.1
    • /
    • pp.93-107
    • /
    • 2012
  • Epoxy resin is widely used in high voltage apparatus as insulation. Fillers are often added to epoxy resin to enhance its mechanical, thermal and chemical properties. The addition of fillers can deteriorate electrical performance. With the new development in nanotechnology, it has been widely anticipated that the combination of nanoparticles with traditional resin systems may create nanocomposite materials with enhanced electrical, thermal and mechanical properties. In the present paper we have carried out a comparative study on dielectric properties, space charge and dielectric breakdown behavior of epoxy resin/nanocomposites with nano-fillers of $SiO_2$ and $Al_2O_3$. The epoxy resin (LY556), commonly used in power apparatus was used to investigate the dielectric behavior of epoxy resin/nanocomposites with different filler concentrations. The epoxy resin/nanocomposite thin film samples were prepared and tests were carried out to measure their dielectric permittivity and tan delta value in a frequency range of 1 Hz - 1 MHz. The space charge behaviors were also observed by using the pulse electroacoustic (PEA) technique. In addition, traditional epoxy resin/microcomposites were also prepared and tested and the test results were compared with those obtained from epoxy resin/nanocomposites.

Study on the Electron Transport Coefficient in Mixtures of $CF_4$ and Ar ($CF_4-Ar$ 혼합기체의 전자수송계수에 관한 연구)

  • Kim, Sang-Nam
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.56 no.1
    • /
    • pp.1-5
    • /
    • 2007
  • Study on the electron transport coefficient in mixtures of CF4 and Ar, have been analyzed over a range of the reduced electric field strength between 0.1 and 350[Td] by the two-term approximation of the Boltzmann equation (BEq.) method and the Monte Carlo simulation (MCS). The calculations of electron swarm parameters require the knowledge of several collision cross-sections of electron beam. Thus, published momentum transfer, ionization, vibration, attachment, electronic excitation, and dissociation cross-sections of electrons for $CF_4$ and Ar, were used. The differences of the transport coefficients of electrons in $CF_4$ mixtures of Ar, have been explained by the deduced energy distribution functions for electrons and the complete collision cross-sections for electrons. The results of the Boltzmann equation and the Monte Carlo simulation have been compared with the data presented by several workers. The deduced transport coefficients for electrons agree reasonably well with the experimental and simulation data obtained by Nakamura and Hayashi. The energy distribution function of electrons in $CF_4-Ar$ mixtures shows the Maxwellian distribution for energy. That is, $f({\varepsilon})$ has the symmetrical shape whose axis of symmetry is a most probably energy. The proposed theoretical simulation techniques in this work will be useful to predict the fundamental process of charged particles and the breakdown properties of gas mixtures. A two-term approximation of the Boltzmann equation analysis and Monte Carlo simulation have been used to study electron transport coefficients.

Reflecting and Dielectric Characteristics of $P_2O_5-ZnO\;and\;SiO_2-ZnO-B_2O_3$ Dielectric Systems due to the Contents of $TiO_2$ ($TiO_2$ 함량에 따른 $P_2O_5-ZnO$계와 $SiO_2-ZnO-B_2O_3$계 유전체의 반사 및 유전특성)

  • Ryu, Boo-Hyung;Kwon, Soon-Suk
    • Journal of the Korean Society of Safety
    • /
    • v.20 no.4 s.72
    • /
    • pp.29-33
    • /
    • 2005
  • In this paper, reflectance and the dielectric characteristics for $P_2O_5-ZnO-BaO$ system and $SiO_2-ZnO-B_2O_3$ system have been investigated as a function of contents of $TiO_2$. The reflectance was decreased with increasing the contents of $TiO_2$ and the reflectance of $P_2O_5-ZnO-BaO$ system was lowered than that of $SiO_2-ZnO-B_2O_3$ system. The dielectric constant of $P_2O_5-ZnO-BaO$ system was higher than $SiO_2-ZnO-B_2O_3$ system, and the dielectric constant in the both system was increased with increasing of $TiO_2$ contents. This can be explained as the space charge effects. These results are could be applied to the under plate dielectrics of PDP required high reflective ratio and breakdown strength.

Aging Diagnosis of Underground Distribution Power Cables by Isothermal Relaxation Current Measurement Equipment (완화전류 측정에 의한 지중배전케이블의 열화진단)

  • Kim, Ju-Yong;Song, Il-Keun;Kim, Dong-Myung;Yun, Tae-Sang;Jeong, Sang-Bong
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2004.05a
    • /
    • pp.502-505
    • /
    • 2004
  • The purpose of this experiment is to modify diagnosis criterion of isothermal relaxation current(IRC) measurement equipment which is using for distribution cable diagnosis. We're using this system for several years in the field instead of DC leakage current measurement and lots of cables were replaced. But we have to investigate on the reliability of this equipment for our cables because we didn't carried out condition assessment of extracted cables after field diagnosis by this equipment. It is important thing for cable maintenance. If the replacement criterion is improper we can not prevent failures or will waste budget on account of replacement of the sound cables. In this papar we selected field installed cables and injected silicone fluid to the cables for insulation rehabilitation. In order to prove reliability of the diagnosis equipment we compared diagnosis results and AC breakdown strength according to operating time after silicone treatment. This is the results of the field test for 1 year.

  • PDF

Aging Diagnosis and Characteristic Analysis of Distribution ,Power Cables I to Prepare Optimal Replacement Criterion (지중 배전케이블의 최적 교체기준 수립을 위한 열화진단 및 특성분석)

  • 김주용;송일근;정익중;한명관;심유종;문재덕
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.53 no.5
    • /
    • pp.258-263
    • /
    • 2004
  • The purpose of this experiment is to modify diagnosis criterion of isothermal relaxation current(IRC) measurement equipment which is using for distribution cable diagnosis. We're using this system for several years in the field instead of DC leakage current measurement and lots of cables were replaced. But we have to investigate on the reliability of this equipment for our cables because we didn't carried out condition assessment of extracted cables after field diagnosis by this equipment. It is important thing for cable maintenance. If the replacement criterion is improper we can not prevent failures or will waste budget on account of replacement of the sound cables. In this paper we selected field installed cables and injected silicone fluid to the cables for insulation rehabilitation. In order to prove reliability of the diagnosis equipment we compared diagnosis results and AC breakdown strength according to operating time after silicone treatment. This is the results of the field test for 1 year.