• Title/Summary/Keyword: ac ageing

Search Result 12, Processing Time 0.022 seconds

Space Charge Measurement as a Diagnostic Tool to Monitor Ageing in Polymeric Materials

  • Chen, George
    • Transactions on Electrical and Electronic Materials
    • /
    • v.7 no.5
    • /
    • pp.235-239
    • /
    • 2006
  • Charge dynamics in polymeric materials after aged under ac electric field using the pulsed electroacoustic (PEA) technique is reported. The emphasis is placed on charge decay. The charge dynamics of the ac aged additive free low density polyethylene (LDPE) samples under dc bias differ from the sample without ac ageing, indicating changes brought in by ac ageing. It is believed that a slow decay rate of charge in the ac aged sample is related to the formation of deep traps in the material. However, chemical analysis by infrared spectroscope (FTIR) and Raman microscope reveals no significant chemical changes taken place in the bulk of the material after ac ageing. Further experiments on irradiated LDPE have revealed a similar behaviour, i.e. the charge decay is slower in irradiated samples than that of fresh sample. The findings presented clearly indicate that space charge measurement can be used as a diagnostic tool to monitor ageing in polymeric materials.

Investigation on the Dielectric, Physical and Chemical Properties of Palm Oil and Coconut Oil under Open Thermal Ageing Condition

  • Mohamad, Nur Aqilah;Azis, Norhafiz;Jasni, Jasronita;Kadir, Mohd Zainal Abidin Ab;Yunus, Robiah;Ishak, Mohd Taufiq;Yaakub, Zaini
    • Journal of Electrical Engineering and Technology
    • /
    • v.11 no.3
    • /
    • pp.690-698
    • /
    • 2016
  • In this paper, a study is carried out to investigate the dielectric, physical and chemical properties of Palm Oil (PO) and Coconut Oil (CO) under open thermal ageing condition. The type of PO used in this study is Refined Bleached and Deodorized Palm Oil (RBDPO) Olein. The ageing experiment was carried out at 85 ℃ and 115 ℃ for 1, 3, 5, 7 and 14 days. Several parameters were measured such as AC breakdown voltage, dielectric dissipation factor, relative permittivity, resistivity, viscosity, moisture and acidity throughout the ageing duration. Based on the study, it is found that there are no significant changes on the AC breakdown voltages and relative permittivities for both RBDPO and CO. At ageing temperature of 115℃, there are clear reduction trends of dielectric dissipation factor for CO and resistivities for most of RBDPO. On the other hand, no clear trends are observed for viscosities, moisture and acidities of RBDPO and CO throughout the ageing duration.

AC Accelerated Ageing Characteristics of Zinc Oxide Varistors for the Station Class Lightning Surge Arresters (발변전급 피뢰기용 산화아연소자의 AC 가속열화특성)

  • Cho, Han-Goo;Yoon, Han-Soo;Kim, Suk-Soo;Han, Dong-Hee
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2005.11a
    • /
    • pp.315-316
    • /
    • 2005
  • This paper describes the AC accelerated ageing characteristics of zinc oxide varistors for the station class lightning surge arresters. ZnO varistors whose rated voltage were 3.27kV, 4.00kV, and 6.00kV were manufactured with general ceramic production methods. The power loss of sample A varistors rapidly increased and eventually showing the thermal run-away, but sample B and sample C varistors exhibited negative creep phenomena in power losses during the test.

  • PDF

Study of Thermal Ageing Behavior of the Accelerated Thermally Aged Chlorosulfonated Polyethylene for Thermosetting Analysis (열경화성 분석을 위한 가속열화 된 Chlorosulfonated Polyethylene의 경년특성 연구)

  • Shin, Yong-Deok
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.66 no.5
    • /
    • pp.800-805
    • /
    • 2017
  • The accelerated thermal ageing of CSPE (chlorosulfonated polyethylene) was carried out for 16.82, 50.45, and 84.09 days at $110^{\circ}C$, equivalent to 20, 60, and 100 years of ageing at $50^{\circ}C$ in nuclear power plants, respectively. As the accelerated thermally aged years increase, the insulation resistance and resistivity of the CSPE decrease, and the capacitance, relative permittivity and dissipation factor of those increase at the measured frequency, respectively. As the accelerated thermally aged years and the measured frequency increase, the phase degree of response voltage vs excitation voltage of the CSPE increase but the phase degree of response current vs excitation voltage decrease, respectively. As the accelerated thermally aged years increase, the apparent density, glass transition temperature and the melting temperature of the CSPE increase but the percent elongation and % crystallinity decrease, respectively. The differential temperatures of those are $0.013-0.037^{\circ}C$ and, $0.034-0.061^{\circ}C$ after the AC and DC voltages are applied to CSPE-0y and CSPE-20y, respectively; the differential temperatures of those are $0.011-0.038^{\circ}C$ and $0.002-0.028^{\circ}C$ after the AC and DC voltages are applied to CSPE-60y and CSPE-100y, respectively. The variations in temperature for the AC voltage are higher than those for the DC voltage when an AC voltage is applied to CSPE. It is found that the dielectric loss owing to the dissipation factor($tan{\delta}$) is related to the electric dipole conduction current. It is ascertained that the ionic (electron or hole) leakage current is increased by the partial separation of the branch chain of CSPE polymer as a result of thermal stress due to accelerated thermal ageing.

Electrical Properties and Lifetime Prediction of Epoxy/$SiO_2$Composites with Water Absorption Ageing (흡수열화에 따른 Epoxy/$SiO_2$ 복합체의 전기적 특성 및 수명예측)

  • 김탁용;이덕진;홍진웅
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.13 no.9
    • /
    • pp.758-763
    • /
    • 2000
  • Dielectric strength of insulators made of epoxy composites rapidly decreases due to ageing to interfaces between the matric resin and filler particles. The adhesion variation of interfaces caused by moisture absorption also alters electrical properties that are the basic characteristics of insulators, particularly, in outdoor use. In this paper, electrical properties of epox/SiO$_2$composites were investigated at boiling absorption condition to observe the influences of moisture. In order to analyze the basic physical properties of samples, scanning electron microscopy and DC, AC and impulse voltage dielectric strength were measured. Also, the breakdown time of samples was measured under AC 6[kV] applied voltage, and the variation of lifetime was verified by using Weibull distribution function.

  • PDF

Comparative Study of DC Breakdown and Space Charge Characteristics of Insulation Paper Impregnated with Natural Ester and Mineral Oil

  • Hao, Jian;Zou, Run-Hao;Liao, Rui-Jin;Yang, Li-Jun;Liao, Qiang;Zhu, Meng-Zhao
    • Journal of Electrical Engineering and Technology
    • /
    • v.13 no.4
    • /
    • pp.1682-1691
    • /
    • 2018
  • Natural ester is a suitable substitute for mineral oil and has been widely used in AC transformer in many countries. In order to further application of natural ester in direct current (DC) equipment, it is needed to investigate its long term insulation property under DC condition. In this paper, a thermal ageing experiment was conducted for both mineral oil-paper and natural ester-paper insulation. The DC breakdown and space charge characteristics of insulation paper impregnated with natural ester and mineral oil was compared. Results show that the resistivity of the paper immersed in natural ester and mineral oil both increase as the ageing goes on. While insulation paper impregnated with natural ester has higher resistivity and DC breakdown voltage than the paper impregnated with mineral oil. The DC breakdown voltage for the oil impregnated insulation paper being DC pre-stressing is higher than that without pre-stressing. The average DC breakdown field strength difference between the test with pre-stressing and without pre-stressing clearly shows that there is an apparent enhancement effect for the homo-charge injection on the DC breakdown.

A Study on the Improvement for the Lifetime of Epoxy Composites (에폭시복합체의 수명개선에 관한 연구)

  • Kim, T.Y.;Lee, D.J.;Shin, J.Y.;Shin, S.K.;Hong, J.W.;Kim, J.H.
    • Proceedings of the KIEE Conference
    • /
    • 2000.11c
    • /
    • pp.485-487
    • /
    • 2000
  • Dielectric strength of insulators made of epoxy composites rapidly decreases due to ageing to interfaces between the matrix resin and filler particles. The adhesion variation of interfaces caused by moisture absorption also alters electrical properties that are the basic characteristics of insulators, particularly, in out door use. In this paper, electrical properties of epoxy/$SiO_2$ composites were investigated at boiling absorption condition to observe that influence of moisture. The breakdown time of samples were measured under AC 6[kV] applied voltage, and the variation of lifetime was varified by using Weibull distribution function.

  • PDF

A Study on the DC Voltage Withstand test for the Ageing of XLPE Power Cable (직류내전압 시험이 전력케이블(CV) 절연체에 미치는 영향연구)

  • Lee, Jun;Lim, Yong-Bae;Kim, Jong-Seo
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 1999.11a
    • /
    • pp.613-616
    • /
    • 1999
  • Polyehtylene[PE] in polymer insulation materials of used power cable have carried out in abundance of experiment and study for electrical conduction, insulation breakdown, dielectric character and so on. when apply to field for power cable to make PE, application of DC withstand test to put in practice for inspection is get to effect accumulated space charge. In this paper, to make use of Pulsed Electro-Acoustic(PEA), It is analysis to take shape space charge under AC and DC, clear up the point at issue for DC withstand test impressing

  • PDF

The Improvement on Insulation Performance of Underground Distribution Power Cables (지중배전케이블 절연성능 향상 방안)

  • Lee, Jae-Bong;Lee, Byung-Sung;Kim, Sang-Joon;Jang, Sang-Ok;Han, Yong-Huei;Oh, Jae-Hyoung
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2004.05a
    • /
    • pp.497-501
    • /
    • 2004
  • The primary failure causes of underground distribution power cables are water penetration in insulation layer and stress enhancement at inner semi-conductive layer. Accordingly, it is needed to improve the materials and the structure of power cables for extending lifetime and preventing failure. We uses non-flaming PE materials instead of PVC as a covering material and encapsulating structure. We also use super smooth class material as a inner semi-conductive layer. The newly developed cables are improved in AC breakdown voltage after ageing tests.

  • PDF

Natural Rubber Electrical Conduction Mechanism in High and Low Electric Fields (고전계와 저전계에서 천연고무의 전기전도기구)

  • Yun, Ju-Ho;Choi, Yong-Sung;Moon, Jong-Dae;Lee, Kyung-Sup
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2007.11a
    • /
    • pp.307-308
    • /
    • 2007
  • This work shows the experimental results obtained from ageing at a temperature of 100 C for 48, 70 and 312 h, although the application of AC electrical tension in samples and the measuring of current leakage are presented. The measurements in samples were carried out with samples prepared from the deformulated commercial materials and respectively reformulated into thin films. The obtained results showed the mechanisms of conduction of samples in low and high electric fields. It was also identified an electric tension transition showing that in low fields it prevails the Ohm's law conduction, and in high electric fields it prevails the conduction of space charge limited current (SCLC). These results can support the natural rubber formulation process having as their main objective the reducing of the mechanisms that occur under high conduction current in high electric fields, which leads the material to a dielectric breakdown. Raw Natural rubber in Brazil is extracted from rubber trees (Hevea brasiliensis) in farms in So Paulo State by using some new plantation technology in smaller spaces, with trees placed a few meters from each other. In the Amazon rain forest the rubber trees are found naturally and their spacing may be of hundreds of meters or even kilometers between them. It is necessary to research this raw material from different internationally standard clones to characterize dielectric and electric properties for industrial applications. Moreover, this natural material has a low commercial price when compared to the synthetic ones.

  • PDF