• Title/Summary/Keyword: Zonal calorie measuring

Search Result 1, Processing Time 0.016 seconds

System Implementation for Fair Automatic Heating Operation Based on Spatial Distributing and Zonal Calorie Measuring (공간분활 및 영역열량측정에 의한 공평 자동난방운영시스템 구현)

  • Han, Sang Cheol;Ryu, Kwang Ryol
    • Journal of the Korea Institute of Information and Communication Engineering
    • /
    • v.23 no.8
    • /
    • pp.910-916
    • /
    • 2019
  • This paper describes the system implementation of the heating operation based on spatial distributing and zonal calorie measuring and analyzing of houses to calculate the fair amount of the heating meterage automatically. The heating space is distributed into 4 zones, which the flow rate and calories are checked by one meter respectively. The system is composed of a heating sources, adjuster of thermostat, valve controller, PC converter and total monitering. The returning temperature in the spatial zones is measured for the heating calorie to calculate the zonal calories according to the rooms temperature. The proposed system results in error by 1% or less in comparing with the dedicated experimental equipment, and reduces energy cost by 7% from conventional system. The fair checking system will be enhanced with building energy management system in the future.