• Title/Summary/Keyword: ZnO arrester

Search Result 100, Processing Time 0.025 seconds

Study on Thermal Stability Characteristics of Surge Arrester for High Power (전력용 피뢰기의 열안정화 특성)

  • Han, Se-Won;Cho, Han-Goo
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2004.07b
    • /
    • pp.1142-1145
    • /
    • 2004
  • ZnO surge arresters continuously endure the operating voltages during the operation course, and in the mean time, which need to withstand occasionally transient voltages of lightning and switching overvoltages. Under these voltages, the ZnO varistors inside arresters would have aging phenomena, one important result of aging phenomena is the increasing of resistive currents of varistors, which leads to the increasing of power losses of varistors. And the operating voltage is continuously applied on the ZnO varistors, there is a degradation phenomenon existing in ZnO varistors. When the degradation reaches a certain degree, then the arrester must stop operation. The degradation is related to the applied voltage ratio, the applied voltage ratio is high, the degradation is quickly. When the power loss is higher than the thermal dispersion ability of house of arrester, then the arrester will thermally breakdown. In this study the thermal stability characteristics of surge arresters for high power wil be discussed on the view point of watt losses and thermal breakdown.

  • PDF

Frequency Dependences of leakage currents flowing through ZnO surge arrester block (ZnO 피뢰기 소자에 흐르는 누설전류의 주파수의존성)

  • Lee, B.H.;Lee, B.;Kang, S.M.
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2005.05a
    • /
    • pp.303-306
    • /
    • 2005
  • This paper presents the frequency-dependent characteristics of leakage currents flowing through ZnO surge arrester block. The leakage current-voltage (I-V) characteristic curves of the commercial ZnO surge arrester blocks were measured. The resistive leakage current was found to increase with increasing frequency in the low conduction region. The capacitance of ZnO block was independent of the magnitude and frequency of the applied voltage. The power losses of ZnO block increase as the frequency of applied voltage increases, because of the dielectric loss related to the frequency of the test voltage.

  • PDF

Aging Characteristics of ZnO Surge Arresters (ZnO 피뢰기의 경년변화 특성분석)

  • 김주용;김찬영;송일근;이병성;한용희
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 1999.05a
    • /
    • pp.383-386
    • /
    • 1999
  • Surge arrestor is used for protection of facilities and lines. Recently lots of arresters fatted prematurely In the distribution lines. It is important to know that what the cause of the failures is. This paper presents characteristics of the aged and new 18kV surge arrester. In order to analyse characteristics, we measured leakage current using specialty made leakage current measurement system and also investigated Tan $\delta$ of the arrester and microstructure of the elements. Through the investigation we found that the characteristics among the ZnO elements in an arrester were a little different, It means that the surge arreste can have non-uniform electric field due to the characteristic difference of The each element. Owing to this concentration of the electric field, the localized aging might be proceeded.

  • PDF

Change of Electrical Characteristics of ZnO Arrester Blocks by Lightning Impulse Current (뇌충격전류에 의한 산화아연형 피뢰기 소자의 전기적 특성변화)

  • Gil, Gyeong-Seok;Han, Ju-Seop;Park, Yeong-Ho
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.48 no.7
    • /
    • pp.550-555
    • /
    • 1999
  • This paper deals with the effect of lightning impulse current on electrical characteristics of ZnO blocks used in distribution lightning arrester. The electrical characteristics of ZnO blocks are degraded by overtime impulse current, and the degraded ZnO block is brought to a thermal runaway and finally destroyed. It is therefore important to estimate the change of electrical characteristics of ZnO blocks. In this study, an impulse current generator which can produce 8/20$[\mus]$, 3[㎄] and 4/10$[\mus]$, 5[㎄] waveform is designed and fabricated to simulate the lightning impulse current of power systems. Total energy applied to the ZnO blocks at each time is 739[J] in 8/20$[\mus]$, and 523[J] in 4/10$[\mus]$, impulse current, respectively. From the experimental results, the 3rd harmonic of the leakage current increases continuously with the number of applied impulse current, but no significant changes in residual voltage and in reference voltage are observed until the ZnO block is destroyed. Also, it is confirmed that the main factor on degradation of ZnO blocks is rather the total energy applied to ZnO blocks than the peak value of the impulse current.

  • PDF

Discharge Luminous Phenomena Caused Between ZnO Surge Arrester Block and Electrodes (산화아연 피뢰기 소자와 전극사이에 발생하는 방전광 현상)

  • Lee, Bok-Hee;Park, Keon-Young;Kang, Sung-Man
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.19 no.3
    • /
    • pp.44-50
    • /
    • 2005
  • This paper deals with the characteristics and reduction methods of the plasma luminosity caused between the ZnO surge arrester block and metal electrodes. In this study, the impulse current generator that can generate $8/20[{\mu}s]$ impulse currents with a peak short-circuit of 10[kA] is designed and fabricated. Plasma luminosity phenomena for fine and used ZnO blocks were observed as a function of the contact states between the ZnO block and electrodes and the polarity of applied impulse voltages. As a result, discharge luminous events are produced near the contact edges between the ZnO block and metal electrodes. The discharge plasma luminosity between the ZnO surge arrester block and low potential electrode is more intensive than that between the ZnO surge arrester block and high potential electrode. Surface flashover of ZnO blocks are mainly caused by plasma generation near the edge of metal electrode. Also, plasma luminosity for the fine ZnO blocks is less than that for the used ZnO blocks. Plasma luminosity at the contact of the ZnO block and ring-type electrode is more intensive than that at the contact of ZnO block and disk electrode. It is desirable to use the disk electrode with the proper contact area to reduce the plasma luminosity caused at the contact point between the ZnO block and electrodes.

Leakage Current Analysis of 18 kV Lighting Arrester (18kV 배전용 피뢰기의 누설전류 분석)

  • Park, J.N.;Lee, Y.H.;Shin, Y.S.;Su, J.M.;Jang, S.H.
    • Proceedings of the KIEE Conference
    • /
    • 2002.07c
    • /
    • pp.1906-1908
    • /
    • 2002
  • In general, ZnO lighting arrester are known to exhibit an increases in resistive current with time, the rate of increase being exacerbated with increasing applied voltage. In addition, since the resistive leakage current caused by deterioration of ZnO lighting arrester mainly caused an increase of the third harmonic component, thereby it is possible the arrester degradation diagnosis by measuring the third harmonic component in the total leakage current. So, in this paper, we presents a leakage current measuring and analysis system of 18[kV] ZnO lighting arrester.

  • PDF

A Study of Electrical Characteristics for ZnO Varistor in HST (전철용 ZnO 바리스타(IEC 10kA)의 전기적 특성 연구)

  • Hwang, M.K.;Youn, B.H.;Huh, C.S.
    • Proceedings of the KIEE Conference
    • /
    • 1998.07d
    • /
    • pp.1519-1521
    • /
    • 1998
  • A Gapless HST(high speed train) arrester design is not possible without the highly non-linear ZnO(ZincOxide) varistors. Zno varistors combine excellent protective characteristics with steady state performance to maximize protection, the ZnO varistors are selected for each unit based on leakage current and residual voltage, to verify that the residual voltage is the residual voltage published for HST arrester.

  • PDF

Structure of Station Class Lightning Arresters and Electrical Characteristics of ZnO Varistor Blocks (발변전용 피뢰기의 구조 및 ZnO 바리스터 소자의 전기적 특성)

  • Cho, Han-Goo;Han, Se-Won;Lee, Un-Yong;Yoon, Han-Soo;Choi, In-Hyuk
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2004.07b
    • /
    • pp.1158-1161
    • /
    • 2004
  • This paper presents structural characteristics of station class lightning arresters and electrical characteristics of manufactured ZnO varistor blocks which are usable in those arresters. Three types of station class lightning arresters were investigated and those are a ceramic arrester, a FRP tube type polymer arrester, and a FRP rod type polymer arrester. Each arrester has merits and demerits with structural characteristics. In general, polymer arresters were made of silicon rubber for housing materials, FRP tube or rod for mechanical strength, ZnO blocks for electrical characteristics, and metal parts for electrical contact and the silicon rubber, the housing materials, was directly injected to the arrester module which was assembly composed of electrodes, ZnO blocks and FRP tube or rod, and to prevent the nonlinear electric fields distribution on upper parts of arresters, the grade ring was adopted to the upper electrodes. The reference voltage, nonlinear coefficient, residual voltage, and voltage ratio of manufactured ZnO varistors are 4.90kV, 50, 9.54kV, 1.94, respectively. Compared to designed electrical characteristics, the reference voltage was low for 600v and the voltage ratio was slightly high. However, the characteristics of discharge withstand was so excellent that the mechanical destruction does not occur at the impulse current of $8/20{\mu}s$ 10kA for 100 times.

  • PDF

ZnO Arrester Diagnosis by Measurement of Temperature (온도측정에 의한 산화아연형 피뢰기 진단)

  • Kim Gyung-Suk;Han Ju-Seop;Song Jae-Yong;Seo Hwang-Dong;Moon Seung-Bo;Park Tae-Gone
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.54 no.8
    • /
    • pp.361-364
    • /
    • 2005
  • In this paper, surface temperatures of ZnO arresters as a function of ambient temperatures and leakage currents were experimentally investigated. The variations of the leakage current was below 10 uA, which comes about $4.5\%$ of the normal leakage current. Temperature differences between the ambient and the surface of arresters were not shown until $150\%$ to the normal leakage current, and were remarkable over $200\%$. From the results, we deduced a couple of polynomials which enables the calculation of the leakage current by the measurement of surface temperature. Tests on used arresters have shown the same results as the experimental one. Also, we expect that an arrester diagnosis is possible by measuring the surface temperature of them after more studies on the effect of wind, moisture penetration, and arrester types.

The electrical properties of in 18kV ZnO surge arrestor with mixed direct and 60Hz Alternating Voltage (중첩전압(직류 +60Hz 교류)에서 18kV 배전용 피뢰기의 전기적 특성)

  • Lee, Bok-Hee;Lee, Seung-Ju;Lee, Su-Bong;Jung, Dong-Cheol;Baek, Young-Hwan
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2007.05a
    • /
    • pp.291-294
    • /
    • 2007
  • This paper preserts the characteristics of leakage currents flowing through 18 kV zinc oxide (ZnO) surge arrester under the mixed DC and AC voltages. The I-V curves of ZnO surge arrester were measured as a function of the voltage ratio K The I-V curves under the mixed DC and AC voltages lay between the pure DC and AC characteristics, and the cross-over phenomenon in I-V curves was observed at the low current region As a result, the increase of DC component to mixed voltages causes the increase of resistive component of total leakage current th ZnO surge arrester.

  • PDF