• Title/Summary/Keyword: Water mist fire extinguishing system

Search Result 33, Processing Time 0.022 seconds

Experimental Study on the Fire Extinguishing Characteristics of Water Mist System (미분무수 소화설비의 소화특성 실험)

  • Hwang, Won-Jun;Kim, Hwang-Jin;Oh, Kyu-Hyung;Lee, Sung-Eun
    • Fire Science and Engineering
    • /
    • v.23 no.2
    • /
    • pp.78-84
    • /
    • 2009
  • We carried out fire extinguishing experiments with three kinds of water mist nozzle system. Fire extinguishing experiment according to installed nozzle height and fuel pan location was done. And fire extinguishing performance was compared with plain water and foam agent mixed solution. Water mist nozzle height was varied with 4m, 3.5m and 3m and position of fuel fan was varied 0.5m and 1m from the center of water mist nozzle. Foam agent that used in this experiment is 3% type of AFFF (Aqueous Film Forming Foam) solution. Experimental result showed the door opening effect was little. Fire extinguishing performance of foam agent mixture water mist was better than the plain water mist only.

Optimum Fire Extinguishing Modeling using Impact Factor Analysis on Water Mist System of Pool Fire (영향인자 분석을 통한 고임화재의 미분무수 최적소화 모델링)

  • Hwang, Won-Jun;Kim, Hwang-Jin;Lee, Sung-Eun;Kim, Sung-Won;Oh, Kyu-Hyung
    • Fire Science and Engineering
    • /
    • v.23 no.5
    • /
    • pp.84-89
    • /
    • 2009
  • In this study, the fire extinguishing experiment was performed using a water mist nozzle with variation of factors which affect on the extinguishing time. The variables were distance from nozzle center to fire location, droplet size, height of nozzle and opening or not. With the experimental data, interaction and sensitivity between factors were analysed with Mini tab and deduce a optimum model of fire extinguishing of water mist system. Based on the experiment and modeling of fire extinguishing with water mist system, the most important factor on extinguishing time is the distance from the center of nozzle to fire and the opening effect was small compare with other factors.

Effectiveness of Friction Loss Calculation Used for Water Mist Fire Extinguishing System on Marine Vessels

  • Lee Kyung-Woo;Kim You-Taek;Lee Young-Ho;Kim Mann-Eung
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.29 no.1
    • /
    • pp.86-97
    • /
    • 2005
  • Nowadays, Water Mist Fire Extinguishing System is increasingly used in maritime field for various application. The fire extinguishing capability of the system should be verified by hydraulic calculation in the same manner as the conventional water based fire extinguishing system such as sprinkler system. water spray system and etc. Additionally, the review of effectiveness of friction loss calculation method used for hydraulic calculation is needed because the pipe flow characteristic of its piping system has higher Reynolds number than that of the conventional system. In this paper the review work was carried out based on the NFPA Code 750.

A Study on Improving Extinguishing Capacity of Mobile Water Mist Equipment (이동식 미분무수 소화장비의 소화능력 향상에 관한 연구)

  • Kong, Ha-Sung;Kim, Jong-Jin
    • Journal of the Korea Safety Management & Science
    • /
    • v.11 no.1
    • /
    • pp.15-26
    • /
    • 2009
  • This research has so far found out problems including the second damage of extinguishant and the short time of emission when using the existing dry chemical extinguisher and gas type extinguisher, and impossibility of constant extinguishing due to the inability of recharge at the field. To solve such problems, a mobile water mist system was developed and used. However, it is judged that more improved mobile water mist system is necessary because the force of the fire changed diversely and remote villages in mountains or islands where the force of fire extinguishing is short or delayed, require high capacity of fire extinguishing. Therefore a new equipment was developed and tested focusing on the improvement of extinguishing capacity and the performance of extinguishing was found out to be improved, compared to the existing mobile water mist system. It also showed a superior extinguishing capacity to dry chemical extinguisher or gas type extinguisher. Afterward an additional research is required of simplification of equipment, price cutting and the development of additive to enable high performance even with just small extinguishant.

Trends of Onboard Fire Extinguishing System (선박용 소화설비의 국제동향)

  • Kim, Mann-Eung
    • Proceedings of the Korean Society of Marine Engineers Conference
    • /
    • 2005.11a
    • /
    • pp.126-127
    • /
    • 2005
  • This paper provides information on the current issues and the progress of on-going researches relating onboard fixed fire extinguishing system in the IMO Sub-committee on Fire Protection. And also prepares to introduce the recent amendment to regulations and technical trends of the water mist fire extinguishing system and high expansion foam system.

  • PDF

Performance of Fire Extinguishing of Water Mist Nozzle for Power Transformer Fire Scenario (주 변압기실 화재시나리오에 적용한 미세물분무 노즐의 소화성능)

  • Lee, Kyoung-Duck
    • Journal of the Korean Society of Safety
    • /
    • v.21 no.6 s.78
    • /
    • pp.46-54
    • /
    • 2006
  • Fire extinguishing experiment was conducted with water mist nozzle in case of the pool fire, cascade fire and spray fire on flammable liquid of class B whether water mist system can be effective system for power transformer fire scenario. In the event of a pool fire, flow rate and time to extinguish was inclined to be increased according to the obstruction rate of ignition space. Furthermore, the performance of fire extinguishing depended upon the spraying angle of the nozzles. In case of cascade fire, the effect of extinguishment was began to show from a combustion pan filled with fuel and fuel flowing plate later on.

He Study of Fire Suppression Capability of Low Pressure Water-Mist System for Wooden Cultural Properties (목조한옥에 대한 저압식 미분무 소화설비의 소화성능에 관한 연구)

  • Roh, Sam-Kew;Kim, Dong-Cheol;Ham Eun-Gu
    • Journal of the Society of Disaster Information
    • /
    • v.8 no.4
    • /
    • pp.401-410
    • /
    • 2012
  • The study verified the extinguishing performance of the low pressure water-mist system, which is used to extinguish fire at domestic wooden architecture, through a fire test. Made of inflammable materials, a wooden house is vulnerable to fire, and the size of fire may vary from the early stage in case of arson. With the discharging pressure of 8 bar and the flow rate of 35 lpm, the low pressure water-mist nozzle used in the experiment has considerable discharging amount compared to other water-mist nozzles. The extinguishing performance was tested based on the size of fire and architecture. Test results demonstrated that the extinguishing performance was not affected by the size of a house, but decreased significantly when the size of fire was above unit 1. Taking into account that the environment of actual wooden cultural properties is more vulnerable than that of the experiment model, sufficient investigation on extinguishing performance is required to apply the water-mist extinguishing system to wooden architecture.

An Experimental Study on the Improvement of Fire Extinguishing Performance of Water Mist with Foam (포 소화약제를 혼합한 미분무수 소화시스템의 소화성능 향상 방안에 관한 실험적 연구)

  • Hwang, Won-Jun;Kim, Hwang-Jin;Oh, Kyu-Hyung;Lee, Sung-Eun;Kim, Sung-Won
    • Fire Science and Engineering
    • /
    • v.23 no.3
    • /
    • pp.61-66
    • /
    • 2009
  • We carried out the water mist fire extinguishing experiments with the 3 kinds of foaming agents varied on the nozzle height. Test result showed that 2% AFFF (Aqueous Film Forming Foam) and 1% synthetic foaming agent for water mist system are the faster extinguishing time than the pure water mist and 3% AFFF solution. Additionally, the best fire extinguishing performance of pure water mist was shown at 3.5m nozzle height and that of the foaming agents shown at 4m nozzle height.

Efficiency of Water Mist Suppression System Containing Viscosity Agent to Extinguish Wood Cribs Fire (증점제를 함유한 미분무수의 목재화재 소화효과)

  • Kim, Min Hyung;Shin, Changsub
    • Journal of the Korean Society of Safety
    • /
    • v.29 no.4
    • /
    • pp.78-84
    • /
    • 2014
  • Viscosity agents were added to water to improve extinguishing performance of low pressure water mist suppression system on wood cribs fire, and a small scale wood cribs fire experiment was conducted to measure the extinguishing performance. CMC and agar were used for viscosity agent and as the amount of viscosity agent enlarges, it showed the increase of the viscosity of aqueous solution and the decrease of the fluidity. On wood cribs fire experiment, the extinguishing efficiency was improved with supplemental viscosity agent as it enhanced the adhesive time of aqueous solution on the wood, and therefore expanded the contact time of fire surface. The surface tension of aqueous solution was decreased with the addition of agar which to be assumed as an increase factor of extinguishing efficiency. By the extinguishing experimental result, the most effective extinguishing agent was CMC 0.6 wt.%, with the flame suppression time and the extinguishing time were reduced by 70s and 93s respectively at this concentration.

Extinguishing Characteristics of Cooking Oil Fire by Water Mist added with AFFF Agent (수성막포 약제를 첨가한 미분무수의 식용유 화재 소화특성)

  • Shin, Chang-Sub;Kim, Seong-Yong
    • Journal of the Korean Society of Safety
    • /
    • v.24 no.5
    • /
    • pp.21-27
    • /
    • 2009
  • Effective way of cooking oil fire extinguishment is using water mist system which has cooling and smothering effects. Low pressure water mist system has advantage because it is compatible with existing sprinkler systems. To increase the effectiveness of low pressure water mist system, additives can be used which increase the momentum of water particle and the chemical effect. In this experiment, aqueous film forming form(AFFF) agent is used as additive and the effect of additive concentration and water pressure are experimented. For the extinguishment of cooking oil fire such as soybean and olive oils, AFFF agent is effective and can decrease the fire extinguishing time and water consumption.