• Title/Summary/Keyword: Vertical exhaust duct

Search Result 12, Processing Time 0.02 seconds

Ventilation Performance According to Outdoor and Operating Conditions of the Vertical Exhaust Duct System in High Riser Public Houses (초고층 공동주택의 입상덕트 환기시스템에서 외기조건과 작동조건에 따른 환기성능평가)

  • Kim, Young-Bae;Kim, Jae-Hong;Sung, Jae-Yong;Lee, Myeong-Ho
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.23 no.2
    • /
    • pp.139-146
    • /
    • 2011
  • The ventilation performance of a vertical exhaust duct system in the high riser public house has been evaluated by a commercial software, Fluid Flow, which solves pressure losses through the duct system including bathroom fans and a hybrid roof fan. During the numerical simulations, outdoor wind condition and stack effects in summer and winter were considered as well as the operating conditions of a basement damper and the roof fan. The results show that the bathroom ventilation in summer is the most unsatisfactory. The opening of the basement damper has a problem that the polluted air in the lower floors is exhausted to the underground parking lot, not to the rooftop. If the basement damper is closed, the exhaust flow rate in the lower floors is not sufficient due to the strong flow resistance in the long vertical duct even though the roof fan is under operating.

Control Method to Ensure Uniform Exhaust Function by Household of Apartment House (공동주택의 세대별 균등 배기량을 확보 하는 제어방법에 관한 연구)

  • Kwon, Yong-Il
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.29 no.12
    • /
    • pp.628-637
    • /
    • 2017
  • This study was conducted to present an effective control method for the common duct system to uniformly discharge volume flow rate exhausted from the kitchen and bathroom of each household in an apartment regardless of the position of household. Since the common duct system is installed vertically and the ventilator is installed in the terminal, the static pressure of each household decreases when vertical height increases. Therefore, the volume flow rate exhausted from each household is different. In order to improve such a phenomenon, a constant air volume damper shall be installed in a branch duct coupled with a common vertical duct system. The selected ventilator should also be able to handle the maximum volume flow rate considering diversity factor. Therefore, a uniform volume flow rate must be exhausted from all households where the hood is operated. This paper mainly focuses on suggestion of an optimum exhaust control method by comparing exhaust performance of each household according to the presence or absence of a constant air volume damper.

A Numerical Study on Flow around Exhaust Ducts of Flue Gas from Apartment Heating Boiler (공동주택 보일러 연소배기가스의 실내유입에 관한 수치적 연구)

  • 박외철;정락기
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.15 no.7
    • /
    • pp.557-562
    • /
    • 2003
  • Flue gas from apartment heating gas boiler is exhausted outside through an exhaust duct mounted horizontally in a vertical row on the wall. The flue gas includes nitrogen-oxides (NOx) and carbon monoxide. To investigate the possible entrainment of the flue gas into the apartments through the windows, a large eddy simulation (LES) based numerical method is utilized. Distribution of the velocity intensity and temperature around the exhaust ducts is presented for three numerical parameters: exhaust velocity, temperature of the flue gas, and exhaust duct length. The flow field visualized with particles inserted at the ends of the ducts is also presented. The results clearly show that the exhausted flue gas may flow into the apartments when the windows are open.

A Study on the Wind Power Generation Using Vertical Exhaust Air Duct of the High-Rise Apartments (초고층 공동주택의 주방.욕실 배기 풍속을 풍력발전에 활용하는 방안)

  • Lee, Yong-Ho;Kim, Seong-Yong;Hwang, Jung-Ha;Park, Jin-Chul
    • Journal of the Korean Solar Energy Society
    • /
    • v.32 no.3
    • /
    • pp.1-10
    • /
    • 2012
  • The purpose of this study was to promote the utilization of wind velocity of kitchen and bathroom exhaust ducts for wind power generation in high-rise apartments. The research content can be summarized as follows: 1) Nine high-rise apartments were examined for the installation of kitchen and bathroom exhaust ducts located in the pipe shaft (PS) section. After selecting simulation candidates, a simulation was performed with the STAR-CCM+ Ver 5.06 program. 2) Of nine high-rise apartments, seven had kitchen and bathroom exhaust ducts, whose cross section was in the range of $0.16m^2{\sim}0.4m^2$. The area ratio between the exhaust ducts and PS section (cross section of exhaust duct/area of PS section ${\times}$ 100) was on average 3.2%. 3) The simulation results were analyzed. As a result, the smaller cross section kitchen and bathroom exhaust ducts had, the more advantages there were for increasing exhaust wind velocity. If an out air inlet duct is installed to the old kitchen and bathroom exhaust ducts, it will increase exhaust wind velocity by 3.01~3.98m/s and contribute to the proper wind velocity level (3.0m/s). 4) When the simultaneous usage rate between the kitchen and bathroom exhaust fan increased from 20% to 60%, exhaust wind velocity increased. The "entire house holds" condition for exhaust fan operation provided more even exhaust wind velocity than the "some house holds" condition. 5) Exhaust wind velocity increased in the order of amplified (T-3), induced (T-2) and vertical (T-1) top of kitchen and bathroom exhaust ducts. Of them, the amplified type (T-3) was under the least influence of external wind velocity and thus the most proper for kitchen and bathroom exhaust duct tops.

Study on the Performance Improvement of Roof Fan Used for Local Exhaust System Installed in Apartment (공동주택의 국소배기용 루프팬 성능개선에 관한 연구)

  • Kwon, Yong-Il;Jeong, Yeol-Wha;Ahn, Jung-Hun
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.24 no.2
    • /
    • pp.136-141
    • /
    • 2012
  • Performance improvement of local exhaust system used in toilet and cooking place are main concern in a field of ventilation. In Korea, There are many high riser residential apartments in recent years. These buildings were not viewed as being major contributors to exhaust pollutants producted in indoor. It was because many engineers thought that exhaust in high riser building depends on stack effect. This study investigates on the performance improvement of terminal device, roof fan, of vertical spiral duct used in high riser residential apartments. This paper focuses mainly on the effect of accessories, number or shape of blades, composed of roof fan with function of exhaust air volume of toilet and cooking place. Roof fan with 10 blades is observed at optimum exhaust performance in this study.

Experimental and Numerical Studies on the Possibility of Duct Flow Low-power Generation Using a Butterfly Wind Turbine

  • Hara, Yutaka;Kogo, Shohei;Takagaki, Katsuhiro;Kawanishi, Makoto;Sumi, Takahiro;Yoshida, Shigeo
    • International Journal of Fluid Machinery and Systems
    • /
    • v.10 no.1
    • /
    • pp.19-29
    • /
    • 2017
  • An objective of this study is to demonstrate the validity of using a small wind turbine to recover the fluid energy flowing out of an exhaust duct for the generation of power. In these experiments, a butterfly wind turbine of a vertical axis type (D = 0.4 m) is used. The output performance is measured at various locations relative to the exit of a small wind tunnel (W = 0.65 m), representing the performance expected in an exhaust duct flow. Two-dimensional numerical analysis qualitatively agrees with the experimental results for the wind turbine power coefficient and rate of energy recovery. When the turbine is far from the duct exit (more than 2.5 D), an energy recovery rate of approximately 1.3% is obtained.

Simulation of Jet Plume Impinging onto a Duct (닥트에 분사되는 제트플륨의 수치계산)

  • Hong Seung-Gyu;Lee Gwang-Seop;Baek Dong-Gi
    • Journal of computational fluids engineering
    • /
    • v.2 no.2
    • /
    • pp.44-50
    • /
    • 1997
  • Accurate simulation of jet plume exhausting into the open space as well as onto the opposing wall is of interest both numerically and physically; the latter, from a system designer's point of view. In the current work, Navier-Stokes computation is undertaken to capture the flow pattern of a supersonic jet impinging onto a rectangular duct which deflects the vertical jet horizontally. Of particular interest are the flow structure in the jet exhaust area, pressure pattern and the magnitude of pressure force at the bottom wall. Usefulness of present characteristic boundary condition applied at the exiting plane of the duct is demonstrated by capturing such complex flow structures for different lengths of the deflection duct.

  • PDF

The ventilation performance of a vertical exhaust duct in a high-rise building (초고층 건물의 입상배기관을 통한 환기성능)

  • 김신도;김경분;황의현;김형수
    • Proceedings of the Korea Air Pollution Research Association Conference
    • /
    • 2001.11a
    • /
    • pp.375-376
    • /
    • 2001
  • 건축 기술의 발달과 도시토지 이용의 효율성을 강화하기 위하여 최근에는 초고층 건물이 많이 건설되고 있다. 이러한 초고층 건물은 에너지 절약적인 설계로 높은 기밀성을 가질 뿐 아니라, 외주부 또한 개폐할 수 없는 유리벽에 의하여 구획되므로 자연 환기에 열악한 특성을 지니고 있다. 초고층 건물의 경우 배기시스템으로 중앙집중배기방식을 채택하고 있으며, 중앙배기시스템은 배기입상덕트의 형상 및 규격, 흡출기의 성능, 그리고 기상조건 등 여러 변수들에 의해 영향을 받는다. (중략)

  • PDF