• Title/Summary/Keyword: Variable passive harmonic filters

Search Result 4, Processing Time 0.02 seconds

A Study on Harmonic Reduction of Single-phase UPS with Variable Passive Harmonic Filters (가변형 수동 고조파 필터에 의한 단상 무정전전원장치의 고조파 저감에 관한 연구)

  • Kim, Sung-Sam;Hwang, Seon-Hwan
    • Journal of IKEEE
    • /
    • v.23 no.2
    • /
    • pp.495-501
    • /
    • 2019
  • This paper proposes a variable passive harmonic filter for reduction and improvement of harmonics and power factor of single-phase uninterruptible power supply(UPS) with full bridge rectifier. Recently, UPSs have excellent harmonic and power factor operation characteristics by applying 2-level or more levels of power conversion methods. On the other hand, the single-phase UPS of the full bridge rectifier seriously causes the third, fifth, and seventh harmonics, and the power factor reduction on the grid side. Therefore, we present a variable passive harmonic filter for eliminating (2n+1) order harmonics and improving the power factor generated by the full bridge rectifier operation. In order to evaluate the performance of the proposed variable harmonic filter, the its validity is verified by various simulations and experiments.

Characterization and Performance Evaluation of Advanced Aircraft Electric Power Systems

  • Eid, Ahmad;El-Kishky, Hassan;Abdel-Salam, Mazen;El-Mohandes, Mohamed T.
    • Journal of Power Electronics
    • /
    • v.10 no.5
    • /
    • pp.563-571
    • /
    • 2010
  • A model of an advanced aircraft electric power system is developed and studied under variable-speed constant-frequency (VSCF) operation. The frequency of the generator's output voltage is varied from 400-Hz to 800-Hz for different loading scenarios. Power conversions are obtained using 12-pulse power converters. To reduce the harmonic contents of the generator output waveforms, two high-pass passive filters are designed and installed one at a time at the generator terminals. The performance of the two passive filters is compared according to their losses and effectiveness. The power quality characteristics of the studied VSCF aircraft electric power system are presented and the effectiveness of the proposed filter is demonstrated through compliance with the newly published aircraft electrical standards MIL-STD-704F.

A Study on Power Factor Control of Inverter-based DG System with Considering the Capacity of an Active Harmonic Filter and an Inverter (고조파 필터 및 인버터의 용량을 고려한 분산전원 시스템의 역률 제어에 관한 연구)

  • Kim, Young-Jin;Hwang, Pyeong-Ik;Moon, Seung-Il
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.58 no.11
    • /
    • pp.2149-2154
    • /
    • 2009
  • Electric power quality in power transmission/distribution systems has considerably been deteriorated with the increase in the capacity of distributed generators (DGs). It is because inverters, connecting DGs to conventional power grids, tend to generate harmonic current and voltage. For harmonic mitigation, a large amount of research has been done on passive and active filters, which have been operating successfully in many countries. This paper, therefore, presents how to adopt the filters to an inverter-based DG, with considering a system consisting of both inverter-based DG and harmonic filters. In particular, this paper describes the simulation results using the PSCAD/EMTDC: firstly, the relationship between total harmonic distortion(THD) of current and output power of DG: secondly, the harmonic mitigation ability of passive and active filters. The system, furthermore, is obliged to satisfy the regulations made by Korean Electric Power Corporation(KEPCO). In the regulations, power factor should be maintained between 0.9 and 1 in a grid-connected mode. Thus, this paper suggests two methods for the system to control its power factor. First, the inverter of DG should control power factor rather than an active filter because it brings dramatic decrease in the capacity of the active filter. Second, DG should absorb reactive power only in the range of low output power in order to prevent useless capacity increase of the inverter. This method is expected to result in the variable power factor of the system according to its output power.

A Synthesis and Design of the LPF with Novel Spurious Suppression Characteristics Using High Efficiency Inductor (고 효율 인덕터를 이용한 우수한 고조파 억압 특성을 갖는 저역 통과 필터 합성 및 설계)

  • Kim, Yu-Seon;An, Jae-Min;Pyo, Hyun-Seong;Lee, Hye-Sun;Lim, Yeong-Seog
    • Journal of the Institute of Electronics Engineers of Korea TC
    • /
    • v.46 no.9
    • /
    • pp.46-51
    • /
    • 2009
  • This paper propose the new approach of the quantity effect by high efficiency inductor characteristic to the harmonic suppression of the lowpass filter. We applied the reliable de-embedding process in order to extract the precise elements values. Moreover, for the effective its application and comparison, the variable stepped impedance low pass filters with a same specification are designed. The proposed procedure is expected to handle the overall filter performance and to construct a synthesized equivalent circuit from its determined specification.