• Title/Summary/Keyword: Vacuum Arcs

Search Result 14, Processing Time 0.033 seconds

Prediction of Anode Temperatures of Free Burning Arcs Using a Simplified Unified Model

  • Jeon, Hong-Pil;Lee, Jong-Cheol
    • Proceedings of the Korean Vacuum Society Conference
    • /
    • 2013.02a
    • /
    • pp.565-565
    • /
    • 2013
  • Free burning arcs where the work piece acts as an anode are frequently used for a number of applications. Our investigation is exclusively concerned with a simplified unified model of arcs and anode under steady state conditions at atmospheric pressure. The model is used to make predictions of arc and anode temperatures and arc voltage for a 200 A arc in argon. The computed temperatures along the axis between the cathode tip and the anode surface compare well the measured data. This knowledge of free burning arcfeatures can play a role in developing the atmospheric plasma systems, however, further investigation should include the modelling of Cu evaporation from anode and non-LTE situation near electrodes for more realistic calculations.

  • PDF

Simulation of High-current Vacuum Arcs: (I)Axial Magnetic Field (진공차단부 대전류 아크 해석: (I)축방향 자기장)

  • Hwang, Jung-Hoon;Lee, Jong-Chul;Choi, Myung-Jun;Kwon, Jung-Lock;Kim, Youn-Jea
    • Proceedings of the KSME Conference
    • /
    • 2007.05b
    • /
    • pp.2500-2505
    • /
    • 2007
  • The vacuum interrupter (VI) is used for medium-voltage switching circuits due to its abilities and advantages as a compact and environmental friendly circuit breaker. In general, the application of a sufficiently strong axial magnetic field (AMF) permits the arc to be maintained in a diffused mode to a high-current vacuum arc. A full understanding of the vacuum arc physics is very important since it can aid to improve the performance of vacuum interrupter. In order to closely examine the vacuum arc phenomena, it is necessary to predict the magnetohydrodynamic (MHD) characteristics by the multidisciplinary numerical modeling, which is coupled with the electromagnetic and hydrodynamic fields, simultaneously. In this study, we have investigated the electromagnetic behaviors of high-current vacuum arcs for two different types of AMF contacts, which are coil-type and cup-type, using a commercial finite element analysis (FEA) package, ANSYS. The present results are compared with those of MAXWELL 3D, a reliable electromagnetic analysis software, for verification.

  • PDF

Numerical Study on a Diffused-mode Arc within a Vacuum Interrupter (진공차단부에서 발생하는 확산형 아크 수치해석)

  • Cho, S.H.;Hwang, J.H.;Lee, J.C.;Choi, M.J.;Kwon, J.R.;Kim, Y.J.
    • 한국전산유체공학회:학술대회논문집
    • /
    • 2008.03b
    • /
    • pp.479-482
    • /
    • 2008
  • In order to more closely examine the vacuum arc phenomena, it is necessary to predict the magnetohydrodynamic (MHD) characteristics by the multidisciplinary numerical modeling, which is coupled with the electromagnetic and hydrodynamic fields, simultaneously. In this study, the thermal-fluid characteristics of high current vacuum arcs were calculated by a commercial multiphysics package, ANSYS, in order to obtain Joule heat, Lorentz force and the interactions with flow variables. We assumed the diffused-mode arc within an AMF vacuum interrupter. It was found with four different currents that the temperature distributions on the anode surface are diffused uniformly without concentration in 7kA for both types (cup and coil-type). But the arc plasma transition and an increase of thermal flux density for increasing the applied current have caused the change of temperature distributions on the anode surface. We should need further studies on the two-way coupling method and radiation model for arc plasmas in order to accomplish the advanced analysis method for multiphysics.

  • PDF

Simulation of Vacuum Arc Expansion with Magnetic Field (자계가 인가된 진공아크의 확장 모의)

  • 최원준;최승길;고광철;강형부
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 1998.11a
    • /
    • pp.183-186
    • /
    • 1998
  • Axial magnetic field generated by special electrode construction in vacuum interrupters is used to extinguish electric plasma arcs. This investigation by FDM should prove to what extent the magnetic field might influence on the arc expansion. The calculated results show that the stronger magnetic field induced the lesser radius of arc plasma. This study will help to offer good data in design of vacuum interrupters.

  • PDF

Changes of Electrical Conductivity and Temperature Caused by Cathode Erosion in a Free-Burning Argon Arc

  • Jeon, Hong-Pil;Lee, Jong-Cheol
    • Proceedings of the Korean Vacuum Society Conference
    • /
    • 2014.02a
    • /
    • pp.255.2-255.2
    • /
    • 2014
  • Electrode erosion is indispensable for atmospheric plasma systems, as well as for switching devices, due to the high heat flux transferred from arc plasmas to contacts, but experimental and theoretical works have not identified the characteristic phenomena because of the complex physical processes. Our investigation is concerned with argon free-burning arcs with anode erosion at atmospheric pressure by computational fluid dynamics (CFD) analysis. We are also interested in the energy flux and temperature transferring to the anode with a simplified unified model of arcs and their electrodes. In order to determine two thermodynamic quantities such as temperature and pressure and flow characteristics we have modified Navier-Stokes equations to take into account radiation transport, electrical power input and the electromagnetic driving forces with the relevant Maxwell equations. From the simplified self-consistent solution the energy flux to the anode can be derived.

  • PDF

Understanding Switching Arcs and Dielectric Capability of a SF6 Self-Blast Interrupter

  • Lee, Won-Ho;Kim, Cheol-Su;Lee, Jong-Cheol
    • Proceedings of the Korean Vacuum Society Conference
    • /
    • 2016.02a
    • /
    • pp.196.2-196.2
    • /
    • 2016
  • The design and development procedures of SF6 gas circuit breakers are still largely based on trial and error through testing although the development costs go higher every year. The computation cannot cover the testing satisfactorily because all the real processes arc not taken into account. But the knowledge of the arc behavior and the prediction of thermal plasmas inside SF6 interrupters by numerical simulations are more useful than those by experiments due to the difficulties to obtain physical quantities experimentally and the reduction of computational costs in recent years. In this paper, in order to get further information into the interruption process of a SF6 self-blast interrupter, which is based on the combination of thermal expansion and arc rotation, gas flow simulations with a CFD-arc modeling are performed during the whole switching process such as high-current period, pre-current zero period, and current-zero period. Through the complete work, the temperature of residual arcs as well as the breakdown index after current zero should be a good criterion to predict the dielectric capability of interrupters.

  • PDF

The Vacuum Arc Analysis of Vl Applied Axial Magnetic Field (축자계형 진공차단기의 진공아크 해석)

  • Kang, Jin;Kim, Min-Soo;Choi, Seung-Kil;Ko, Kwang-Cheol;Kang, Hyung-Boo
    • Proceedings of the KIEE Conference
    • /
    • 1999.07e
    • /
    • pp.2221-2223
    • /
    • 1999
  • Axial magnetic field($B_z$) generated by special electrode construction in vacuum interrupters(Vl) is used to extinguish electric plasma arcs because that restrains this form expending. So VI applied axial magnetic field has more interruption capacity as compared with other VI. Also, the profile of toroidal field($B_{\theta}$) generated by $B_z$, is important to VI design. In this study, it was represented that the behavior of vacuum arc. In addition, The relationship between $B_z$ and $B_{\theta}$ was represented by using Dynamo theory. I hope that this study will be a good data in design of vacuum interrupters.

  • PDF

Effects of Electrode Configurations on the Characteristics of Axial Magnetic Fields in Vacuum Interrupter (전극형상 변화가 진공차단기내 축방향 자기장 특성에 미치는 영향)

  • Hwang, Jung-Hoon;Lee, Jong-Chul;Kim, Youn-Jea
    • Transactions of the Korean Society of Mechanical Engineers A
    • /
    • v.32 no.1
    • /
    • pp.7-12
    • /
    • 2008
  • The vacuum interrupter (VI) is used for medium-voltage switching circuits due to its abilities and advantages as a compacted environmental friendly circuit breaker. In general, the application of a sufficiently strong axial magnetic field (AMF) permits the arc to be maintained in a diffused mode to a high-current vacuum arc. A full understanding of the vacuum arc physics is very important since it can aid to improve the performance of vacuum interrupter. In order to closely examine the vacuum arc phenomena, it is necessary to predict the magnetohydrodynamic (MHD) characteristics by the multidisciplinary numerical modeling, which is coupled with the electromagnetic and hydrodynamic fields, simultaneously. In this study, we have investigated the effect of changing geometrical parameters for electromagnetic behaviors of high-current vacuum arcs with two different types of AMP contacts, which are coil-type and cup-type, using a commercial finite element analysis (FEA) package, ANSYS. The present results are compared with those of MAXWELL 3D, a reliable electromagnetic analysis software, for verification.

A Study on the Characteristics of High-Current Arc Plasma Influenced by Axial Magnetic Field (축방향 자기장에 의한 대전류 아크 특성에 관한 연구)

  • Cho, S.H.;Lee, J.C.;Choi, M.J.;Kwon, J.R.;Kim, Y.J.
    • Proceedings of the KSME Conference
    • /
    • 2008.11b
    • /
    • pp.2515-2518
    • /
    • 2008
  • The vacuum interrupter (VI) is widely used in medium-voltage switching circuits due to its abilities and advantages as an environmental friendly circuit breaker. An understanding of the vacuum arc flow phenomena is very important for improving the performance of vacuum interrupter. In order to closely examine the vacuum arc phenomena, it is necessary to predict the magnetohydrodynamic (MHD) characteristics by the multidisciplinary numerical modeling, which is coupled with the electromagnetic and the thermal flow fields, simultaneously. In this study, we have investigated arc plasma constriction phenomena and an effect of AMF on the arc plasma with the high-current vacuum arcs for the cup-type AMF electrode by using a commercial finite element analysis (FEA) package, ANSYS. The simulation results applied with various AMFs and constant Joule heat generation show that strong axial magnetic field (AMF) permits the arc to be maintained in a diffused mode to a high-current vacuum arc. However, further studies are required on the two-way coupling method and radiation model for arc plasma in order to accomplish the advanced analysis method.

  • PDF

Three-Dimensional Numerical Analysis of Arc Plasmas with an Axial Magnetic Field Vacuum Interrupter (축자계 진공차단부에서 발생하는 아크 플라즈마 3차원 수치해석)

  • Seo, Hyeon-Seok;Kim, Yun-Je;Lee, Jong-Cheol
    • Proceedings of the Korean Vacuum Society Conference
    • /
    • 2011.02a
    • /
    • pp.249-249
    • /
    • 2011
  • 전력용 개폐장치인 진공차단기의 차단부가 송배전 시스템에 30 [kA] 정도의 커다란 사고전류가 흐르는 것을 방지하기 위하여 동작될 때 차단부 내부 전극 사이에 25,000 [K] 이상의 아크 플라즈마가 발생하게 된다. 두 전극 사이에 발생된 아크 플라즈마는 약 10 ms~20 ms 동안 지속되다가 교류전원의 전류영점 부근에서 회복된 절연성능으로 인하여 자연스럽게 소멸되지만, 대전류 구간동안 아크 플라즈마의 집중 현상 등에 의하여 전극의 심각한 손상 등이 발생되면 절연성능이 요구된 만큼 회복되지 못하여 사고전류를 차단하지 못하며 시스템에 연결된 기기들에게 심각한 손상을 입히고 정전사고를 일으킨다. 본 연구에서는 전자계-열유동 연성해석기법을 이용한 축자계 진공차단부에서 발생하는 아크 플라즈마의 3차원 수치해석을 통하여 전극의 심각한 손상을 입히는 아크플라즈마의 집중 현상에 관한 축자계의 영향을 고찰하고자 한다. 수치해석을 위한 아크 영역은 양극과 음극의 직경과 같은 직경의 원기둥으로 가정하였고, 전자계 해석으로부터 얻어진 로렌츠 힘과 줄열을 열유동 해석을 위한 Navier-Stokes 방정식의 파라미터로 입력하여 해석을 수행함으로써 전자계와 유체역학적인 영역을 동시에 연계한 순차적 일방향 연성해석 기법을 적용하였다. 컵형 축자계 진공차단부 내 아크영역에서의 로렌츠 힘의 특성과 온도분포에 대하여 수치해석을 수행하였고, 크기가 다른 두 로렌츠 힘에 의하여 양극표면으로 집중되는 온도분포의 크기를 비교함으로써 진공아크 플라즈마의 집중현상에 영향을 미치는 주요 요소를 규명할 수 있었다.

  • PDF