• Title/Summary/Keyword: Underground cables

Search Result 243, Processing Time 0.024 seconds

Measurement and Analysis of Sheath Circulating Current in Domestic Underground Transmission Cables (국내 송전 케이블 시스 순환전류 실측 및 분석)

  • 하체웅;김정년;이수길;김동욱;이종범;강지원
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.52 no.4
    • /
    • pp.193-200
    • /
    • 2003
  • The use of underground transmission tables has continuously increased in densely inhabited urban and suburban area. Due to a increasing demand of underground cables, two or more circuits are installed in parallel for several kilometers. It, however, has not been realized that the sheath circulating current is generated in the system where a large number of cables are laid in the same route. In this paper, Author studied diversely the sheath circulating current on underground cables depending on the various length rate, the phase arrangement, and the grounding resistance of the sheath in the cross-bonded section. It was clear that very large circulating current is generated in cable systems due to unbalanced length rate and phase arrangement in the cross-bonded section.

A Review of Strategy to Capture Niche Marketing of HTS Power Distribution Cable

  • Park, Sang-Bong;Nam, Kee-Young;Kim, Dae-Kyeong;Jeong, Seong-Hwan;Ryoo, Hee-Suk
    • KIEE International Transactions on Power Engineering
    • /
    • v.4A no.1
    • /
    • pp.11-17
    • /
    • 2004
  • It becomes difficult and high in cost to construct new ducts and/or tunnels for power cables in domestic areas. This paper presents possible strategy of an HTS distribution cables for distributing electric power in local areas as niche marketing. Reflected were its important distinction such as system configuration, rationale, establishment of strategy and considerably high economical efficiency compared with present underground cables. In this paper, applicable important items by using HTS distribution cables in water pumping powerhouse and distribution substation as example objective regions were reviewed. Based on this, the following items on distribution HTS system are examined. (I)A review of constructing a model system to introduce high temperature superconducting distribution cables to objective areas is presented. (2)The strategy to capture HTS distribution cable in water pumping powerhouse and distribution substation as niche marketing regions were reviewed. (3)In concrete, system configuration, rationale, establishment of strategy and considerably high economical efficiency are reviewed between existing cable and HTS one.

Reduction Methods of Sheath Circulating Current in Underground Cable (지중 송전선로에서 시스 순환전류 저감 방안)

  • Ha, C.W.;Kim, J.N.;Lee, S.K.;Kim, D.W.;Park, W.K.
    • Proceedings of the KIEE Conference
    • /
    • 2002.07a
    • /
    • pp.175-177
    • /
    • 2002
  • The use of underground transmission cables has increased continuously in densely inhabited urban and suburban for power transmission. Two or more transmission lines are outgoing from one substation in many cases, and one line comprises twin circuits. In order to meet the increasing do and for electric power, underground tables of two or fore circuits are installed in ducts in parallel for several kilometer in the same route. It, however, has not been known generally that the sheath circulating current is generated in a system where a large number of cables are laid on the same route. Therefore, this paper describes an improved analysis method for sheath circulating current on underground transmission cables using EMTP. Author propose several methods to reduce sheath circulating current. The analysing method and reduction methods for two or more underground cables will be really improved for cable system utility.

  • PDF

EMTP-Analysis of Sheath Circulating Current on Underground Transmission Cables (EMTP를 이용한 지중 송전 케이블의 시스 순환전류 분석)

  • Ha, C.W.;Kim, J.N.;Lee, S.K.
    • Proceedings of the KIEE Conference
    • /
    • 2001.11b
    • /
    • pp.213-215
    • /
    • 2001
  • This paper describes an improved analysis method for sheath circulating current on three-underground transmission cables using EMTP(Electromagnetic Transient Program). Author studied diversely the sheath circulating current on three-underground cables depending on the various length rate, the phase arrangement, and the grounding resistance of the sheath in the cross-bonded section. It was clear that very large circulating current is generated in cable systems due to unbalanced length rate and phase arrangement in the cross-bonded section. The analysing method for two or more underground cables will be really Improved for cable system utility.

  • PDF

A Study on SVL Transient Characteristics by Switching Overvoltage at Single Point Bonding Section in Underground Transmission Cables (개폐과전압 발생시 지중송전선로 편단접지 구간에서 SVL에 미치는 과도특성에 관한 연구)

  • Jung, Chae-Kyun;Kang, Ji-Won
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.63 no.6
    • /
    • pp.764-769
    • /
    • 2014
  • This paper describes sheath voltage limiter(SVL) transient characteristics by switching overvoltage considering single point bonding in underground transmission cables. The crossbonding system is generally used for grounding methods of underground transmission system. However, the single point bonding system is used in selective area which is difficult to consist of crossbonding major section. The sheath voltage limiters are connected between joints in the single point bonding. Specially, the high overvoltage might be generated in that section as well as the aging of sheath voltage limiter might be progressed by various electrical stress including lightning overvoltage, switching overvoltage and power frequency overvoltage. Therefore, in this paper, the switching overvoltage characteristics in underground cables are firstly analysed using EMTP simulation. Then, the switching overvoltage of sheath voltage limiter is also studied in single point bonding. Finally, the reduction method of sheath voltage limiter switching overvoltage is proposed by various simulation studies including circuit breaker operating order.

Analysis of Behavior Characteristics of Underground Flexible Pipe (II) (지중 연성관의 거동특성 분석 (II))

  • 이대수;상현규;김경열
    • Proceedings of the Korean Geotechical Society Conference
    • /
    • 2002.03a
    • /
    • pp.287-294
    • /
    • 2002
  • Underground flexible pipes for electric cables are subject to external loads and surrounding soil pressure. Particularly, strain of flexible pipes is of great concern in terms of safety and maintenance for electric cables. In this study, the actual size tests were carried out to investigate strain-deformation relation for underground flexible pipes subject to vehicle loads with various depths and degree of compaction.

  • PDF

Analysis of Sheath Circulating Current on Multi-underground Transmission Cables using EMTP (다회선 지중송전 케이블에서의 EMTP를 이용한 시스 순환전류 분석)

  • Ha, Che-Ung;Kim, Jeong-Nyeon;Lee, Su-Gil;Kim, Dong-Uk;Lee, Jong-Beom;Gang, Ji-Won
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.51 no.10
    • /
    • pp.510-517
    • /
    • 2002
  • The use of underground transmission cables has continuously increased in densely inhabited urban and suburban area. Due to a increasing demand of underground cables, two or more circuits are installed in parallel for several kilometers. It, however, has not been realized that the sheath circulating current is generated in the system where a large number of cables are laid in the same route. In this paper, sheath circulating current is analyzed by the EMTP and compared with the measured values. Unbalance arrangement of cables or cross-bonding length causes a significant effect on the magnitude of the sheath current. Sheath circulating current could be greatly reduced by the symmetrical configuration of cables and installation of the impedance reduction system. Especially, with the impedance system of 1Ω installed, the sheath circulating current is reduced by 85.7%.

Analysis of Induced Voltage in Parallel Telecommunication Cables from Underground Power Cables (지중송전선로와 병행하는 기설통신선의 유도전압 분석)

  • Lim, Kwang-Sik;Chang, Woo-Seog;Han, Chang-Seok;Hong, Dong-Suk;Yoo, Jin-Seon
    • Proceedings of the KIEE Conference
    • /
    • 2011.07a
    • /
    • pp.523-524
    • /
    • 2011
  • This paper covers induced voltage in parallel telecommunication cable with underground power cable to be linked between substations. The simulation was carried out the induced voltage in telecommunication cable according to the transposition of power cables and fault location for various conditions. This study based on the EMTP/ATPDraw with actual underground cable systems while the power cables are in steady state and transient state.

  • PDF

Fault Location of Underground Cables Using Travelling Wave (반사파를 이용한 지중케이블의 고장점 탐지연구)

  • Sun, J.H.;Kang, D.S.;Ryoo, H.S.
    • Proceedings of the KIEE Conference
    • /
    • 2000.07c
    • /
    • pp.1972-1974
    • /
    • 2000
  • In this paper, we made an experiment on fault location of underground cables with travelling wave. The 5C2V coaxial cables of 100, 200m length, connected with discharge gap, are used for simplifying model cable lines of power cable. And 100KHz -2MHz CT and HV probe are installed at one side of the ends. We made travelling pulse in discharge gab and then pulse travelled along the cable to the both ends. Therefore, it is detected in CT and HV probe. Measuring the time difference of the pulse start and arrival, we were able to obtain the distance of pulse travelling. Consequently, our experimental results show the possibility to detect fault location of underground cables with travelling wave.

  • PDF

A Study on System Modeling, Capacity and Voltage rating to supply HTS Power Transmission Cable to Metropolitan Area (고온초전도 케이블의 대도시 계통적용을 위한 모델링 및 송전용량과 전압계급의 검토)

  • 최상봉;정성환;김대경;김학만;문영환;성기철
    • Progress in Superconductivity and Cryogenics
    • /
    • v.4 no.1
    • /
    • pp.61-65
    • /
    • 2002
  • It becomes difficult and high in cost to construct new ducts and/or tunnels for power cables in metropolitan areas. This paper presents possible applications of an HTS superconducting power cables for transmitting electric power in metropolitan areas. Reflected were its important distinction such as compactness for installation in underground ducts and considerably high efficiency compared with present underground cables. In this paper, system modeling, transmission capacity and voltage class of compact HTS cables which should be applied to existing ducts were reviewed. Based on this, the following items on urban transmission system are examined. (1) A method of constructing a model system to introduce high temperature superconducting cables to metropolitan areas is presented. (2)The maximum outer diameter of HTS cables to be accommodated in exiting ducts is calculated based on the design standards for current cable ducts. (3)The voltage level that can be accommodated by existing ducts is examined.