• Title/Summary/Keyword: Underground Power Cable System

Search Result 158, Processing Time 0.026 seconds

Development of Oil Filled Power Cable for 345kV Line (345 kV OF cable의 개발)

  • Han, K.M.;Choi, M.K.;Lee, I.H.
    • Proceedings of the KIEE Conference
    • /
    • 1988.11a
    • /
    • pp.224-228
    • /
    • 1988
  • Extensive development work which was carried out by Gold Star Cable Co., Ltd. has led to the optimal design, manufacture and test of fully engineered cable system for 345 kV self- contained oil filled (OF) underground cable. Details of design criteria and of tests are given. development of 345kV OF cable results in sucessful operations for ultra-high voltage power transmission requirement.

  • PDF

Review of the Conceptual Design for the Use of HTS Power Transmission Cable for a Metropolitan Area

  • Park, Sang-Bong
    • KIEE International Transactions on Power Engineering
    • /
    • v.3A no.2
    • /
    • pp.63-69
    • /
    • 2003
  • The necessity of compact high temperature superconducting cables is more keenly felt in densely populated metropolitan areas. Because the compact high-temperature superconducting cables can be installed in ducts and tunnels, thereby reducing construction costs and making the use of underground space more effective, the effect of introducing it to the power system will be huge. Seoul, Korea, is selected as a review model for this paper. The loads are estimated by scenario based on a survey and analysis of 345kV and 154kV power supply networks in this area. Based on this, the following elements for an urban transmission system are examined. (1) A method of constructing a model system to introduce high-temperature superconducting cables to metropolitan areas is presented. (2) A case study is conducted through the analysis of power demand scenarios, and the amount of high-temperature superconducting cable to be introduced by scenario is examined. (3) The economy involved in expanding existing cables and introducing high-temperature superconducting cables(ducts or tunnels) following load increase in urban areas is examined and compared., and standards for current cable ducts are calculated. (4) The voltage level that can be accommodated by existing ducts is examined.

Determination of Proto Type for 345kV CV Cable Accessories (345kV CV 케이블 접속함의 Proto Type 선정)

  • Lee, S.K.;Kim, I.T.;Son, S.H.;Choi, S.G.;Huh, G.D.;Park, W.K.
    • Proceedings of the KIEE Conference
    • /
    • 1998.07e
    • /
    • pp.1629-1631
    • /
    • 1998
  • Crosslinked polyethylene (XLPE) insulated cables are now widely used all over the world for extra-high voltage underground transmission systems. Prefabricated type (compression type) joint has developed in order to shorten the assembly time and lower the possibility of contamination at site by many companies in the world. For outdoor termination, to control the electric field distribution as uniform as possible, especially for the use of extra-high voltage system. much of products are adopting the oil-impregnated condensor cone type instead of electric field control element which uses the permitivity of it only (not capacitance). For Gas-immersed termination, dimension of outer insulation bushing was determined by IEC Publication 859. The highest voltage of underground power cable system is 345kV now, in Korea. We have much of experiences of the development of prefabricated type accessories for CV cable systems (154kV, 161kV, 230kV level). So it was possible to inspect the proto type of accessories for 345kV CV cable system and seems that the need time for the development of products is reduced.

  • PDF

Development of Noise Cancellation Technique for Fault Location on Underground Power Cable System (지중송전계통 고장점 추정을 위한 노이지 제거 기법 개발)

  • Jung, Chae-Kyun;Lee, Jong-Beom
    • Proceedings of the KIEE Conference
    • /
    • 2005.07a
    • /
    • pp.530-532
    • /
    • 2005
  • Actually, it's very difficult to discriminate the transient on underground power cable system because of the reflected signal including many noises. Therefore, in this paper, a solution based on multiple scales correlation of the transient using SWT(Stationary Wavelet Transform) is presented. It's quick and straightforward. For applying all algorithms, we just use the signal captured in single end.

  • PDF

A Study on the Application Effects of HTS Power Cable (고온초전도 전력케이블 적용효과 검토)

  • Seong, Gi-Cheol;Jo, Jeon-Uk;Kim, Hae-Jong;Gwon, Yeong-Gil;Choe, Sang-Bong;Ryu, Gang-Sik;Kim, Bong-Tae;Yu, In-Geun
    • Progress in Superconductivity and Cryogenics
    • /
    • v.2 no.2
    • /
    • pp.32-36
    • /
    • 2000
  • In this study, we performed the long-term expansion planning for the conceptual design of HTS power cable in Seoul area. In Korea, underground power cable has been required gradually with increasing demand of electric power transmission density and low loss characteristics in the comparison with a conventional power cables, so we assumed that the HTS power cable is applied between the downtown area and the outskirts of the city for the large power transmission capacity. This paper is to show the effects of HTS power cables in Seoul based on the power system analysis.

  • PDF

Underground Transmission Cable Sheath Voltage Analysis Using EMTP (EMTP를 이용한 송전케이블 시스전압 분석)

  • Oh, Dong-Soo
    • Proceedings of the KIEE Conference
    • /
    • 2000.07a
    • /
    • pp.428-430
    • /
    • 2000
  • This paper describes under-ground transmission cable sheath voltage by using EMTP and proposes a new design method for calculating cable sheath voltage in steady state. The cross bonding system of power cable is modeled on ${\pi}$ equivalent circuit and the sheath voltage(current) of cable can be analyzed with comparing to conventional method.

  • PDF

Analysis and Estimation of the Transient Thermal Characteristics of OF Cable systems (OF 케이블 계통 과도상태 열특성 해석 및 평가)

  • Kang, Ji-Won;Lee, Dong-Il;Jung, Chae-Kyun;Lee, Jong-Beom
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.54 no.10
    • /
    • pp.487-495
    • /
    • 2005
  • This paper reviews the characteristic of thermal and temperature of oil field cable in transient state such as grounding fault and lightning surge. For analysis in various conditions, many actual underground power cable systems are modeled using ATP. These results are applied for the examination of temperature increase when the single line to ground fault by the breakdown of insulation part and hitting of lightning surge are occurred. The inner part temperature of OF cable is analysed according to the various kinds of cable using the thermal model of transient state. The temperature increase of sheath and crossbonded lead bv fault current is also analysed using IEC 60949.

Impedance Calculation of an Underground Transmission Cable System Installed with a Sheath Current Reduction Device

  • Jung, Chae-Kyun;Lee, Jong-Beom;Kang, Ji-Won;Wang, Xin Heng;Song, Yong Hua
    • KIEE International Transactions on Power Engineering
    • /
    • v.4A no.4
    • /
    • pp.236-242
    • /
    • 2004
  • Previous research results indicated that the designed current reduction device could effectively reduce the sheath circulating current and that its RDP protection device could shield it against both fault and lightning strokes. In this paper, cable impedance is analyzed using wavelet analysis and distance relay algorithm following the installation of these devices so that the operation of distance relay can be estimated. The test results confirm that in these devices, the fault inception angle and SVL bonding types have no impact on the change of cable impedance. In other words, the conventional distance relay can be used without a new relay setting. Thus we can finally assert that the designed current reduction device and its protection device are effective and can be safely installed on the cable transmission system without disturbance.

Analysis of transient state between Korea and Japan in Underground Transmission Cable System (국내외 지중송전시스템의 과도상태 해석)

  • Kang, J.W.;Jang, T.I.;Hong, D.S.;Lee, D.I.;Jung, C.K.;Lee, J.B.
    • Proceedings of the KIEE Conference
    • /
    • 2005.07a
    • /
    • pp.462-464
    • /
    • 2005
  • This paper analyses the transient phenomena against single line to ground fault and lightning surge between Korea and Japan on underground power cable systems. For analysis, find proper earthing resistance of neutral grounding system adopted in Japan. This paper is expected to contribute the establishment of proper protection methods against transients on underground power cable systems.

  • PDF

A Study on Lightning Surges in Underground Distribution Systems

  • Jung Chae-Kyun;Kim Sang-Kuk;Lee Jong-Beom
    • KIEE International Transactions on Power Engineering
    • /
    • v.5A no.2
    • /
    • pp.171-176
    • /
    • 2005
  • The effects of surge arresters for the protection of transmission systems against direct lightning strokes have already been reviewed by many researchers. However, their studies have not encompassed underground cable systems. Therefore, in this paper we investigate the 22.9kV combined distribution systems that have arresters and ground wires. In addition, we analyze the overvoltages on underground distribution cable sections when direct lightning strokes contact the overhead ground wire using EMTP. Finally, we discuss the effect of lightning strokes according to the change of cable length and installation of arresters. This study provides insulation coordination methods for reasonable system design in 22.9kV underground distribution cable systems.